GB
3.6
COMBUSTION MAMAGER CM222
The Combustion Manager CM222 is a microprocessor-controlled gas burner safety control system designed for use with forced draught modulating
gas burners.
OPERATION
The range-limits of the potentiometer are expert parameters. Adjustments of the potentiometers are immediately active in all program steps.
To deactivate the potentiometers set the minimum limit and the maximum limit of each potentiometer equal.
Then these equal values are the active setpoints.
The values of the min. capacity potentiometer and the max. capacity potentiometer are the limits for the modulation of the burner capacity. These
limits are used during program step ‘Burner operation’.
The value of the max. capacity potentiometer is also the setpoint for the prepurge speed.
The value of the start capacity potentiometer is the setpoint for the burner capacity during program step ‘Ignition’ and ‘Flame stabilization’.
ERROR CODE
If the burner control is in lockout the error code is shown in the display as a blinking number. The following error codes will be displayed as a blinking
number:
PROGRAM STEPS
No.
Error code
Explanation
Buner off
Lockout
1
Failure fan
Fan speed check. Deviation too high
x
x
2
Failure gas pressure
No signal from the gas pressure switch
x
-
3
Failure flame
No flame signal after burner start-up /
Flame loss during burner operation /
Flame signal without burner operation
x
x
4
Failure BCC
Wrong BCC connected / BCC lost /
BCC parameter block is not valid
x
x
5
Failure Remote Reset
More than 5 remote resets in 15 minutes /
Permanent remote reset (> 10 sec)
x / -
x / -
6
Failure gas valve circuit
Gas valve V1/V2 leak
x
x
7
Failure air pressure
No signal from the air pressure switch
x
x
8
Failure CRC
The parameter block is not valid
x
x
9
Failure power supply
The power supply is not sufficient (lower than
185VAC or higher than 270VAC).
x
-
E
Safety shut down
The safety operating system has done a safety
shut down.
x
x
No.
Program step
Explanation
0
Standby
Waiting for heat demand; All actors off
1
Standstill check
Fan standstill check; APS-Off-Check
2
Prepurge check
Fan speed check; APS-On-Check
3
Prepurge
Fan: prepurge speed; Time is parameter
4
Waiting for ignition speed
Waiting until fan reached ignition speed
5
Safety time
Ignition and gas valves on; Fan: ignition speed; Time is parameter
6
Flame stabilization time
Fan: ignition speed for flame stabilization; Time is parameter
7
Burner operation
Fan: Modulation speed
8
Gas valve circuit V1/V2 check
Checking gas valves tightness with flame signal
9
Postpurge
Fan: postpurge speed; Time is parameter
POTENZIOMETER MAX
POTENZIOMETER START
DISPLAY AND RESET BUTTON
POTENZIOMETER DI MINIMUM