![Riello RS5F Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/riello/rs5f/rs5f_installation-use-and-maintenance-instructions_1459899031.webp)
29
20141167
GB
5.13 Programming menu
5.13.1 General notes
The programming menu can be accessed via the integrated reset
button, or by remote reset during OPERATION and in STAND-
BY.
If in page menu the reset or remote reset button is not pressed
within 10 seconds the page will be automatically be exited and
there will be a green led flashing for the time set.
If the number of presses on the reset or remote reset button
exceeds the maximum allowable, the value that stays in memory
will be the maximum one.
If the reset or remote reset button is pressed for more than 60
seconds, a button error will be displayed and the control-box will
restart.
5.13.2 Block diagram for entering the menu
Tab. Q
Fig. 21
POST-PURGING/
CONTINUOUS
PURGING
10 SEC.
INTERMITTENT
OPERATION
20 SEC.
TEST OF
SWITCHING OFF
5 SEC.
LONG PRE-PURG-
ING
30 SEC.
DISPLAYING
LOCKOUT
LOG
35 SEC.
PROGRAMMING
MENU PARAME-
TER RESET
40 SEC.
2 RED
OUTPUT
AUTOMATIC
1 GREEN
3 GREEN
10 SEC. AFTER
RELEASE
5 GREEN
6 GREEN
7 GREEN
OPERATION (WITH FLAME) AND STAND-BY
TYPE OF
FUNCTION
NUMBER
BLINKS
OUTPUT
TIME OF
RELEASE
BUTTON
BURNER STATE
S9653
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
Function
Button
release time
No. of blinks of
the LED for
menu page
No. of pressing times
of the reset button
No. of blinks of
the LED (green)
Quitting the menu
Test of
Switching off
5s
≤
t < 10s
2 blinks
RED
/ none
/ none
Automatic starting
from the end of the blink
Post-purging/
Continuous
purging
10s
≤
t < 15s
1 GREEN blink
1 = 1 minute
2 = 2 minutes
3 = 3 minutes
4 = 4 minutes
5 = 5 minutes
6 = 6 minutes
7 = continuous purging
8 = 0 m (deactivated)
(
default
)
1 flash
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
10 sec. after the release of the
button
Operation
intermittent
20s
≤
t < 25s
3 blinks
GREEN
1 = 1 hour
2 = 24 hours (
default
)
1 flash
2 blinks
10 sec. after release push-button
Pre-purging
long
30s
≤
t < 35s
5 blinks
GREEN
1 = activated
2 = deactivated
(
default
)
1 flash
2 blinks
10 sec. after release push-button
Display
lockout log
35s
≤
t < 40s
6 blinks
GREEN
1 = last lockout
2 = 9th lockout
3 = 8th lockout
4 = 7th lockout
5 = 6th lockout
6 = 5th lockout
7 = 4th lockout
8 = 3rd lockout
9 = 2nd lockout
10 = less recent lockout
Displaying the
type of lockout
according to
Tab. N
10 sec after the release of the
button (if at level 1).
When at level 2, 10 sec after the
display of the type of lockout or
else pressing the button again
before 10 sec you return to level
1 from where, 10 seconds after
nothing has been done to the
buttons, you exit the menu
Parameter
reset
programming
menu
40s
≤
t < 45s
7 blinks
GREEN
1 = reset of the lockout log
2 = reset of the no. of
lockouts
3 = reset of hours of
operation
4 = reset of the no. of heat
requests
5 = restoration of default
values of the menu
parameters
/
10 sec. after release push-button