Technical description of the burner
7
20122392
GB
Tab. C
(*)
Firing Rate for C-ETL Canadian Listing
(1)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 5)(Fig. 3) with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
(4)
Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr.
Model
RS 410/E
RS 510/E
Output delivery
(1)
High
kW
1.172
4.719
4.247*
1.465
5.627
5.064*
Mbtu/hr
(4)
4.000
16.100
14.490*
5.000
19.200
17.280*
Low
kW
479
-
-
586
-
-
Mbtu/hr
(4)
1.635
-
-
2.000
-
-
Fuel
Natural gas
Gas max. delivery
SCFH
15.941
19.010
Gas pressure at max delivery
(2)
"WC
26.0
32.6
Operation
Low-high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32-104 (0-40°C)
Combustion air temperature
°F Max.
140 (60°C)
Noise level (gas)
(3)
dBA
82,9
83,6
Содержание RS 280
Страница 2: ...Original instructions ...
Страница 37: ...Appendix Spare parts 35 20122392 GB A Appendix Spare parts ...
Страница 41: ......
Страница 42: ......
Страница 43: ......