![Riello RS 280 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/riello/rs-280/rs-280_installation-use-and-maintenance-instructions_1460061032.webp)
20122392
30
GB
Start-up, calibration and operation of the burner
5.5
Burner start-up
Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches, set the parameters on
the RWF55 regulator.
Please refer to the specific manual for this operation.
Turn the switch of Fig. 29 to position
“ON”
and turn the switch of
Fig. 29 to position
“LOCAL”
.
5.6
Adjusting gas/air delivery
Move slowly towards the maximum output (butterfly gas valve
completely open);
adjust the required maximum output with the gas pressure sta-
bilizer;
adjust the combustion parameters with the air servomotor and
store the maximum combustion point;
complete the procedure slowly, synchronizing the combustion
with the two servomotors and storing the different setting
points.
DANGER
Make sure that the lamps or testers connected to
the solenoids, or indicator lights on the solenoids
themselves, show that no voltage is present. If volt-
age is present, stop the burner
immediately
and
check the electrical wiring.
WARNING
For the start-up procedure and the parameters
calibration, refer to the specific instruction man-
ual of the LMV37... electronic cam supplied with
the burner.
ON
OFF
REMOTE
LOCAL
Fig. 29
20124957
WARNING
For the start-up procedure and the parame-
ters calibration, refer to the specific instruc-
tion manual of the LMV37... electronic cam
supplied with the burner.