Installation
4.15 Burner operation
4.15.1 Burner starting
•
Operating closes.
Fan motor starts.
•
Servomotor starts:
90° rotation to right, until contact is made on red cam.
The air damper is positioned to MAX. output.
•
Pre-purge stage with air delivery at MAX. output.
•
After pre-purge stage, servomotor rotates to left up to the angle
set on blue cam for MIN. output.
•
The air damper and the gas butterfly are positioned to MIN. out-
put.
•
Ignition electrode strikes a spark.
•
Pilot valve opens. The pilot flame is ignited.
•
After about 12s the main flame ignites and starting cycle ends.
4.15.2 Steady state operation
Burner without modulating control RWF
At the end of the starting cycle, the servomotor control then passes
to the load control for boiler pressure or temperature.
(The flame safeguard continues, however, to check that the flame
is present and that the air pressure switch is in the correct position.)
•
If the temperature or pressure is low, the burner progressively
increases its output to the MAX. value.
•
If the temperature or pressure is high, the burner progressively
decreases its output to the MIN. value. And so on.
•
The burner locks out when demand for heat is less than the
heat supplied by the burner at min. output. Load control opens.
The servomotor returns to the 0° angle limited by contact with
orange cam. The air damper closes completely to reduce ther-
mal dispersion to a minimum.
Every time output is changed, the servomotor automatically modi-
fies gas delivery (gas butterfly valve) and air delivery (fan damper).
Burner with modulating control RWF
See the handbook enclosed with the modulating control.
Switching times are given in seconds, in the burner start-up se-
quence.
Tab. L
4.15.3 Firing failure
If the burner does not fire, it locks out within 2.5 seconds from
opening the pilot valve and then within 5 seconds from opening
the main valves.
4.15.4 Burner flame goes out during operation
If the flame should accidentally go out during operation, the burner
will lock out within 1 s.
Key for the times
t1
Pre-purge time with air damper open
t2
Safety time
t3
Pre-ignition time, short (ignition transformer on terminal 16)
t4
Interval between start of t2 and release of valve at terminal 19
t5
Interval between end of t4 and release of load controller or
valve at terminal 20
t5
Running time of air damper into OPEN position
t6
Running time of air damper into low-flame position (MIN)
t7
Post-purge time
t8
Interval until OPEN command for the air damper is given
t9
Running time of pilot
TL
Operating control
TR
Modulating controller
MV
Fan Motor
SM
Air and Fuel Actuator
TA
Ignition transformer
VP1
Safety pilot valve
VP2
Main pilot valve
V1
Safety gas valve
V2
Main gas valve
RFGO A13
t1
t2
t3
t4
t5
30s
2s
4s
20s
optional
t6
t7
t8
t9
optional
12s
4s
16s
Fig. 24
FULL MODULATION
20159662
Fig. 25
LOW - HIGH
20159663