Technical description of the burner
3.6
Firing rate
The
maximum output
is chosen within area of the Fig. 2.
The
minimum output
must not be lower than the minimum limit of
the diagrams.
RS 28/M = 198 MBtu/hr 58 kW
RS 38/M = 266 MBtu/hr 78 kW
RS 50/M = 321 MBtu/hr 94 kW
NOTE:
The FIRING RATE areas given in figure (A) have been reduced
by 10% with respect to the maximum range that can be
reached. See “Procedure to refer burner operating condition
at an altitude and/or at a combustion supporter air tempera-
ture different to the standard values (328 ft above sea level, 68
°F).” on page 9 for operation at different ambient temperatures
and/or altitudes.
WARNING
The firing rate was obtained considering a room
temperature of 68 °F and an atmospheric pressure
of 394 “WC (approx. 0 ft above sea level), with the
combustion head adjusted.
Fig. 2
C
ombustion chamber
pressure
“WC
Combu
stion chamber
pressur
e
“W
C
C
ombust
ion chamber
pressure
“W
C
D2259