Faults - Possible causes - Solutions
The control box has a self-diagnostic system, which easily allows
identifying the operating faults (signal:
RED LED
).
To use this function, wait at least ten seconds from the safety lock
out, and then press the reset button for a minimum of 3 seconds.
After releasing the button, the RED LED starts flashing as shown
in the diagram below.
The pulses of the LED constitute a signal spaced by approxi-
mately 3 seconds. The number of pulses will provide information
about the possible faults, according to Tab. N.
8
Faults - Possible causes - Solutions
RED LED ON - press the release button
for 10s
Press the button
for > 3s
Signal
3s interval
Signal
SIGNAL
FAULT
PROBABLE CAUSE
RECOMMENDED SOLUTION
2 blinks
Once the pre-purging
phase and safety time
have passed, the burner
goes into lockout with-
out the appearance of
the flame
The operation solenoid lets little gas through
Increase
One of the two solenoid valves does not open
Replace them
Gas pressure too low
Increase pressure at governor
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
High voltage cable defective
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Ignition transformer defective
Replace
Incorrect valve or transformer electrical wiring
Check
Defective control box
Replace
A closed valve upline the gas train
Open
Air in pipework
Bleed air
Gas valves unconnected or with interrupted coil Check connections or replace coil
3 blinks
The burner does not
switch on, and the lock-
out appears
Air pressure switch in operating position
Adjust or replace
The burner starts and
then goes into lockout
Air pressure switch inoperative due to insufficient air pressure:
Air pressure switch poorly adjusted
Adjust or replace
Pressure switch pressure point pipe blocked
Clean
Poorly adjusted head
Adjust
High pressure in the furnace
Connect air pressure switch to fan
suction line
Lockout during pre-
purging phase
Defective motor control contactor
Replace
Defective electrical motor
Replace
Motor lockout
Replace
4 blinks
The burner starts and
then goes into lockout
Flame simulation
Replace the control box
Lockout when burner
stops
Permanent flame in the combustion head or
flame simulation
Eliminate persistence of flame or re-
place control box
6 blinks
The burner switches on,
but then stops in lockout
Defective or incorrectly adjusted servomotor
Adjust or replace
Содержание RS 150/M
Страница 2: ...Translation of the original instructions ...
Страница 41: ...39 20054085 GB Appendix Electrical panel layout ...
Страница 42: ...20054085 40 GB Appendix Electrical panel layout ...
Страница 43: ...41 20054085 GB Appendix Electrical panel layout ...
Страница 44: ...20054085 42 GB Appendix Electrical panel layout ...
Страница 45: ...43 20054085 GB Appendix Electrical panel layout ...
Страница 46: ...20054085 44 GB Appendix Electrical panel layout ...