background image

27 

20054085

GB

Start-up, calibration and operation of the burner

6.6.3

Minimum output

Min output must be selected within the firing rate range shown on
page 9.
Press the “reduce output” button 2)(Fig. 28), and keep it pressed
until the servomotor has closed the air damper and the gas but-
terfly valve at 50° (adjustment made in the factory).

Adjustment of gas delivery

Measure the gas delivery on the gas meter.

If it is necessary to reduce it, slightly reduce the angle of cam
III (Fig. 32) with small, regular movements (i.e. bring it from
an angle of 65° to 63° - 61°....).

If it is necessary to increase it, lightly press the “increase out-
put” button 2)(Fig. 28) (open the gas butterfly valve by 10-
15°) and increase the angle of cam III (Fig. 32) with small,
regular movements (i.e. bring it from an angle of 65° to 67° -
69°....).
Now press the “reduce output” button until the servomotor is
in the minimum opening position, and measure the gas out-
put.

NOTE

The servomotor only follows the adjustment of cam III when the
angle of the cam is reduced. 
If you need to increase the angle of the cam, you must first in-
crease the angle of the servomotor with the aid of the “increase
output” button.
Now increase the angle of cam III, then bring the servomotor
back to the MIN output position using the “reduce output” button.
For any necessary adjustment of cam III, especially for small
movements, use the specific key 10)(Fig. 32).

Air adjustment

Progressively adjust the initial profile of the cam 4) (Fig. 31) by
turning the screws 5). 

6.6.4

Intermediate outputs

Adjustment of gas delivery

No adjustment of gas delivery is required.

Air adjustment

Lightly press the “increase output” button 2)(Fig. 28) so the ser-
vomotor rotates by about 15°. 
Adjust the screws until optimal combustion is obtained. Proceed
in the same way with the other screws. 

Switch off the burner via the switch 1)(Fig. 28) (“OFF” posi-
tion).

Release the cam 4 from the servomotor by pressing the but-
ton 3) and moving it to the right.

Manually rotate the cam 4) backwards and forwards several
times to make sure it moves smoothly.

Now engage cam 4) again to the servomotor by shifting but-
ton 2) to the left.

Once optimum adjustment has been reached, fix it with the
screws 6).

NOTE

Once you have finished adjusting the MAX - MIN - INTERMEDI-
ATE outputs, check ignition once again: noise emission at this
stage must be identical to the following stage of operation. 
If you notice any sign of pulsations, reduce the ignition output.

Key (Fig. 32)
1

Servomotor

2

Servomotor 1) - cam 4): constrained

3

Servomotor 1) - cam 4): released

10 Spanner for adjusting cam III

CAUTION

It is preferable not to turn the first screw, as this
one is used to bring the air damper to its fully
closed position.

WARNING

Take care that the cam profile variation is progres-
sive.

WARNING

As far as is possible, try not to move those screws
at the ends of the cam that were previously adjust-
ed for the opening of the air damper to MAX and
MIN output.

D3922

10

2

3

 Fig. 32

Содержание RS 150/M

Страница 1: ...ion use and maintenance instructions 20054085 2 05 2013 Forced draught gas burners Progressive two stage or modulating operation CODE MODEL TYPE 20044638 20044639 RS 150 M 890T 20051315 20051316 RS 150 M 890T GB ...

Страница 2: ...Translation of the original instructions ...

Страница 3: ... 11 4 11 Control box RMG M 88 62C2 12 4 12 Servomotor SQN31 76 13 5 Installation 14 5 1 Notes on safety for the installation 14 5 2 Handling 14 5 3 Preliminary checks 14 5 4 Operating position 15 5 5 Preparing the boiler 15 5 5 1 Boring the boiler plate 15 5 5 2 Blast tube length 15 5 6 Securing the burner to the boiler 16 5 7 Positioning the probe electrode 17 5 8 Combustion head adjustment 17 5 ...

Страница 4: ...6 7 2 Operation 29 6 7 3 Ignition failure 29 6 7 4 Burner flame goes out during operation 29 6 8 Stopping of the burner 30 6 9 Final checks with burner operating 30 6 9 1 Checking the air and gas pressure on the combustion head 30 7 Maintenance 31 7 1 Notes on safety for the maintenance 31 7 2 Maintenance programme 31 7 2 1 Maintenance frequency 31 7 2 2 Checking and cleaning 31 7 3 Opening the bu...

Страница 5: ...12100 and according to the European Directives GAD 2009 142 EC Gas Devices Directive MD 2006 42 EC Machine Directive LVD 2006 95 EC Low Voltage Directive EMC 2004 108 EC Electromagnetic Compatibility Such products are marked as follows The quality is guaranteed by a quality and management system certified in accordance with UNI EN ISO 9001 Legnago 18 02 2013 Executive Director RIELLO S p A Burner ...

Страница 6: ...ried out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks with le thal consequences DANGER FLAMMABLE MATERIAL This symbol indicates the presence of flammable materials DANGER BURNING This symbol indicates the risks of burns due to high temperatures DANGER CRU...

Страница 7: ...event of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasonable use of the burner intervention of unqualified personnel carrying out of unauthorised modifications on the equipment use of the burner with safety devices that are faulty incor rectly applied a...

Страница 8: ...intenance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific purpose He is re sponsible for the machine and for the training of the people work ing around it The user undertakes to entrust the machine exclusively to suitably trained and qualified personnel ...

Страница 9: ...trol system FS1 FS2 Standard 1 stop every 24 h Continuous working 1 stop every 72 h Electrical supply of the system 3 400 50 3 230 50 Voltage of auxiliaries 230 50 60 110 50 60 R S 150 M TC Emission C01 or Class 1 EN676 BLU or BLU Class 3 EN676 FS1 3 400 50 230 50 60 BASIC DESIGNATION EXTENDED DESIGNATION 3N 400V 50Hz 3 230V 50Hz 230V 50 60Hz 110V 50 60Hz Heavy oil E Electronic cam EV Electronic c...

Страница 10: ...ry SE FI AT GR DK ES GB IT IE PT IS CH NO I2H DE I2ELL NL I2L FR I2Er BE I2E R B LU PL I2E Model RS 150 M Code 20044638 20044639 20051315 20051316 Power 1 Delivery 1 min max kW 300 900 1850 Fuels Natural gas G20 methane gas G21 G22 G23 G25 Gas pressure at max output 2 Gas G20 G25 mbar 17 5 27 1 Operation Intermittent min 1 stop in 24 hours Progressive two stage or modulating by kit See Accessories...

Страница 11: ...ust discharge head of the fan are reduced It is therefore important to know if the maximum output requested from the burner at a determinate combustion chamber pressure remains within the firing rate of the burner even with the changed temperature and altitude conditions To check it proceed as follows 1 find the corrective factor F relating to the air temperature and altitude of the system in Tab ...

Страница 12: ...ING The combustion head should be adjusted in rela tion to the equivalent output Qe H1r H1 x Qr Q 2 Altitude Average baro metric pressure F Air temperature C m above sea level mbar 0 5 10 15 20 25 30 40 0 100 200 300 400 500 600 700 800 900 1000 1200 1400 1600 1800 2000 2400 2800 3200 3600 4000 1013 1000 989 978 966 955 944 932 921 910 898 878 856 836 815 794 755 714 675 635 616 1 087 1 073 1 061 ...

Страница 13: ...g to be carried out by the installer 12 Control box with lockout pilot light and lockout reset button 13 Flame inspection window 14 Minimum air pressure switch differential operating type 15 Slide bars for opening the burner and inspecting the com bustion head 16 Gas pressure test point and head fixing screw 17 Air pressure test point 18 Flame sensor probe 19 Air damper 20 Fan air inlet 21 Screws ...

Страница 14: ...separately as far as possi ble from the control box and the other cables When wiring the unit make sure the 230V AC mains voltage cables are run strictly separate from extra low voltage cables to avoid the risk of electrocution Electrical wiring of the flame detector It is important for signal transmission to be almost totally free of any disturbances or loss Always separate the detector cables fr...

Страница 15: ...he servomotor and connecting the damp er the gears can be disengaged by means of a lever allow ing the drive shaft to be easily adjusted in both directions of rotation Technical data Tab H WARNING To avoid accidents material or environmental damage observe the following instructions Avoid opening modifying or forcing the actuators The servomotor contains electric and electronic components that mus...

Страница 16: ...must be free from hazardous mixes e g chloride fluoride halo gen if present it is highly recommended to carry out cleaning and maintenance more frequently WARNING The handling operations for the burner can be highly dangerous if not carried out with the great est attention keep any unauthorised people at a distance check the integrity and suitableness of the available means of handling Check also ...

Страница 17: ...ce in refractory material 13 must be inserted between the boiler fettling 14 and the blast tube 12 For boilers with a water cooled frontal a refractory lining 13 14 is not necessary unless expressly requested by the boiler manu facturer Tab J WARNING The burner is designed to operate only in positions 1 2 3 and 4 Fig 10 Installation 1 is preferable as it is the only one that allows the maintenance...

Страница 18: ...e screw 1 Fig 13 take out the inner part 2 Fig 13 of the head and then cali brate them Once this operation if necessary has been carried out fix the flange 11 Fig 12 to the boiler plate interposing the insulating gasket 9 Fig 12 supplied Use the 4 screws supplied with a tightening torque of 35 40 Nm after protecting their thread with anti seizing products Provide an adequate lifting system WARNING...

Страница 19: ...s with the indicator 3 tighten the screws 4 Example burner output 1300 kW and combustion chamber pressure equal to 0 mbar The diagram Fig 15 shows that the gas and air adjustments for this output are carried out on notch 4 WARNING When positioning the probe and electrode re spect the dimensions shown in Fig 14 WARNING Do not rotate the probe leave it as in Fig 14 since if it is located too close t...

Страница 20: ...nnect the socket of the maximum gas pressure switch refit the screws 2 on the slide bars 3 fix the burner to the pipe coupling with the screws 1 reconnect the articulated coupling 7 to the graduated sector 6 WARNING When fitting the burner on the two slide bars it is advisable to gently draw out the high voltage ca ble and the flame detection probe cable until they are slightly stretched Carry out...

Страница 21: ... outputs over 1200 kW 9 Gasket for flanged versions only 10 Pressure adjuster 11 Train Burner adaptor supplied separately P2 Upline pressure of valves adjuster P3 Upstream pressure of the filter L Gas train supplied separately L1 The responsibility of the installer Explosion danger due to fuel leaks in the pres ence of a flammable source Precautions avoid knocking attrition sparks and heat Make su...

Страница 22: ...te output at which the burner oper ates subtract the combustion chamber pressure from the gas pressure measured at test point 1 Fig 23 Find in Tab K related to the burner concerned the pressure value closest to the result of the subtraction Read off the corresponding output on the left DANGER Disconnect the electrical power using the main switch Check that there are no gas leaks Pay attention when...

Страница 23: ...eter To calculate the required gas pressure at test point 1 Fig 23 set the maximum modulating output required from the burner op eration find the nearest output value in Tab K for the burner in ques tion Read on the right column 1 the pressure at the test point 1 Fig 23 Add this value to the estimated pressure in the combustion chamber Example with natural gas G20 Operation at maximum modulating o...

Страница 24: ... up efficiency Normally burner stopping is guaranteed by the boiler s thermostat pres sure switch If this is not the case a time switch should be fitted in series to TL to stop the burner at least once every 24 hours Refer to the wiring diagrams The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system made according to current standards It...

Страница 25: ...hermal relay press but ton 1 Fig 25 5 12 Measuring the ionisation current The burner is fitted with an ionisation system to check that a flame is present The minimum current for control box operation is 6 µA The burner provides a much higher current so controls are not normally required If it is necessary however to measure the ionisation current dis connect the plug socket 2 Fig 26 on the ionisat...

Страница 26: ...ding so you can notice the smell of gas Connect two lamps or testers to the two gas line solenoids to check the exact moment in which voltage is supplied This operation is unnecessary if each of the two solenoids is equipped with a pilot light that signals voltage passing through 6 Start up calibration and operation of the burner WARNING The first start up of the burner must be carried out by qual...

Страница 27: ... 30 simultaneously adjusts the air damper by means of the variable profile cam and the gas butterfly valve The servomotor rotates by 130 in 42 seconds Cam I 130 Limits rotation toward maximum position When the burner is at MAX output the gas butterfly valve must be fully open 90 Cam II 0 Limits rotation toward minimum position When the burner is shut down the air damper and gas butterfly valve mus...

Страница 28: ...y the formula for ts 3s Vg volume supplied in ignitions carried out Sm3 Qa ignition delivery Sm3 h n number of ignitions 10 ts safety time sec Example for gas G20 9 45 kWh Sm3 ignition output 150 kW corresponding to 15 87 Sm3 h After 10 ignitions with lockout the output read on the meter must be equal to or less than 6 6 2 Maximum output MAX output must be selected within the firing rate range sho...

Страница 29: ...ic key 10 Fig 32 Air adjustment Progressively adjust the initial profile of the cam 4 Fig 31 by turning the screws 5 6 6 4 Intermediate outputs Adjustment of gas delivery No adjustment of gas delivery is required Air adjustment Lightly press the increase output button 2 Fig 28 so the ser vomotor rotates by about 15 Adjust the screws until optimal combustion is obtained Proceed in the same way with...

Страница 30: ...f cardboard until the CO value does not exceed 100 ppm Slowly turn the appropriate knob clockwise until the burner goes into lockout Check the indication of the arrow pointing upwards on the graduated scale Turn the knob clockwise again until the value shown on the graduated scale corresponds with the arrow pointing down wards and so recovering the hysteresis of the pressure switch shown by the wh...

Страница 31: ...lame and the correct position of the air and maximum gas pressure switches If the temperature or pressure is low so the TR is closed the burner progressively increases the output up to the MAX value tract C D If the temperature or pressure then increases until the TR opens the burner progressively decreases its output to the MIN value section E F The sequence repeats endlessly The burner stops whe...

Страница 32: ...rations then reassemble the hood and all the burner safety and protection de vices Open the thermostat pressure switch TL Open the thermostat pressure switch TS Æ The burner must stop Turn the gas maximum pressure switch knob to the mini mum end of scale position Turn the air pressure switch to the maximum end of scale position Æ The burner must stop in lockout Turn off the burner and cut off the ...

Страница 33: ...ase the cam 4 Fig 31 on page 26 from the servomotor by pressing and shifting the button 3 Fig 32 on page 27 to the right Manually rotate it backwards and forwards to make sure it moves smoothly Now engage the cam again by shifting the button 2 Fig 31 on page 26 to the left Burner Check for excess wear or loose screws in the mechanisms con trolling the air damper and the gas butterfly valve Also ma...

Страница 34: ... fully back Now extract the gas distributor 5 after having removed the screw 6 7 4 Closing the burner Push the burner to approximately 100mm from the pipe cou pling Reconnect the cables and slide in the burner until it comes to a stop Replace the screws 3 Fig 40 and carefully pull the probe and electrode cables out until they are slightly taut Reconnect the articulated coupling 7 to the graduated ...

Страница 35: ...place High voltage cable defective Replace High voltage cable deformed by high tempera ture Replace and protect Ignition transformer defective Replace Incorrect valve or transformer electrical wiring Check Defective control box Replace A closed valve upline the gas train Open Air in pipework Bleed air Gas valves unconnected or with interrupted coil Check connections or replace coil 3 blinks The bu...

Страница 36: ...ice is open Adjust or replace Line fuse blocked Replace Defective control box Replace No gas supply Open the manual valves between contactor and train Mains gas pressure insufficient Contact your gas company Minimum gas pressure switch fails to close Adjust or replace Servomotor fails to move to min ignition position Replace The burner continues to repeat the start up cy cle without lockout The ga...

Страница 37: ...every burner start up Once read the burner repeats the start up cycle by briefly press ing the control box button GREEN LED ON press the reset button for 10s Press the button for 3s Signal 3s interval Signal Signal Flame detection time 1 blink 0 4 s 2 blinks 0 8 s 6 blinks 2 8 s WARNING If the result is 2 s ignition will be retarded Check the adjustment of the hydraulic brake of the gas valve the ...

Страница 38: ...egulator kit Two components should be ordered the analogue signal converter the potentiometer PC interface kit A Appendix Accessories Burner Standard head length mm Extended head length mm Code RS 150 M 280 415 20052186 Burner Thickness mm Code RS 150 M 135 3010129 Burner Code RS 150 M 3010094 Burner Type Reduction of noise average Code RS 150 M C4 5 10 dB A 3010404 Burner Type Code RS 150 M RWF40...

Страница 39: ... of signals exceeding 10V m owing to the presence of an INVERTER or in applications where the length of the thermostat connections exceeds 20 metres a protection kit is available as an interface between the control box and the burner Gas trains in compliance with EN 676 Please refer to manual Burner Head length mm Code RS 150 M TC 20050064 TL 20050065 Burner Code RS 150 3010386 ...

Страница 40: ...tion of references 3 Functional layout RMG M 230V 3 Functional layout RMG M 400V 4 Functional diagram 5 Electrical wiring that the installer is responsible for 230V 5 Electrical wiring that the installer is responsible for 400V 6 Functional layout RWF40 1 2 Sheet no 1 A1 Co ordinates Indication of references ...

Страница 41: ...39 20054085 GB Appendix Electrical panel layout ...

Страница 42: ...20054085 40 GB Appendix Electrical panel layout ...

Страница 43: ...41 20054085 GB Appendix Electrical panel layout ...

Страница 44: ...20054085 42 GB Appendix Electrical panel layout ...

Страница 45: ...43 20054085 GB Appendix Electrical panel layout ...

Страница 46: ...20054085 44 GB Appendix Electrical panel layout ...

Страница 47: ...F1 Fan motor thermal relay H Remote lockout signal K1 K1 relay K2 K2 relay MV Fan motor PA Air pressure switch PE Burner earth PGM Maximum gas pressure switch PGMin Minimum gas pressure switch S1 Off automatic manual selector S2 Power increase power reduction selector SM Servomotor TA Ignition transformer TL Limit thermostat pressure switch TR Adjustment thermostat pressure switch TS Safety thermo...

Страница 48: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com ...

Отзывы: