Start-up, calibration and operation of the burner
5.3
Burner start-up
Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches, set the parameters on
the RWF 40 regulator. Please refer to the spacific manual for this
operation.
Turn the switch of Fig. 37 to position
“ON”
and turn the
switch of Fig. 37 to position
“LOCAL”
.
DANGER
Make sure that the lamps or testers connected to
the solenoids, or indicator lights on the solenoids
themselves, show that no voltage is present. If volt-
age is present, stop the burner
immediately
and
check the electrical wiring. When the burner starts,
check the direction of the motor rotation, as indi-
As the burner is not fitted with a device to check the
sequence of the phases, the motor rotation may be
incorrect. As soon as the burner starts up, go in front
of the cooling fan of the fan motor and check it is
rotating anticlockwise. See Fig. 37.
If this is not the case:
place the switch of Fig. 37 in position
“0”
and
wait for the control box to carry out the switch-
off phase;
disconnect the electrical supply from the
burner;
invert the phases on the three-phase power
supply.
DANGER
Adjusting gas/air delivery
– Move slowly towards the maximum output (but-
terfly gas valve completely open);
– adjust the required maximum output with the gas
pressure stabilizer;
– adjust the combustion parameters with the air
servomotor and store the maximum combustion
point;
complete the procedure slowly, synchronizing the
combustion with the two servomotors and storing
the different setting points.
WARNING
For the start-up procedure and the parameters
calibration, refer to the specific instruction man-
ual of the LMV37... electronic cam supplied with
the burner.
REMOTE
LOCAL
ON
OFF
Fig. 37
D10448