Installation
23
20029324
4.10 Gas supply pressure
The diagram (Fig. 23) show minimum load losses at combustion
head depending on the maximum burner output operation with nat-
ural gas (G 20).
Gas pressure is measured at the test point 1)(Fig. 22), with:
•
Combustion chamber at 0 mbar
•
Burner working at maximum output
•
Ring nut 2) (Fig. 17) adjusted as in the diagram of Fig. 16
NOTE
To know the approximate output at which the burner is operating at
its maximum:
–
subtract the combustion chamber pressure from the gas pres-
sure measured at test point 1)(Fig. 22);
–
find, in the diagram (Fig. 23) the pressure value closest to the
result you want;
–
read the corresponding output on the left.
Example for RS 120/E LN
• Maximum output operation
• Natural gas
• Gas ring 2)(Fig. 16, page 20) adjust as indicated in diagram
•
Gas pressure at test point 1)(Fig. 22)
= 5.11 “WC
•
Pressure in combustion chamber
= 1.18 “WC
5.11 - 1.18
= 3.93 “WC
A maximum output of 3030 MBtu/hr shown diagrams RS 120/E LN
corresponds to 3.93 “WC pressure.
This value serves as a rough guide, the effective delivery must be
measured at the gas meter.
NOTE
To know the required gas pressure at test point 1) (Fig. 22), set the
maximum output required from the burner operation, then:
–
find the nearest output value in the table for the burner in ques-
tion.
–
read, on the diagram (Fig. 23), the pressure test point 1)
(Fig. 22);
–
add this value to the estimated pressure in the combustion
chamber.
Example for RS 120/E LN
•
Maximum output required: 3750 MBtu/hr
•
Ring nut 2) (Fig. 17) adjusted as in the diagram of Fig. 16
•
Gas pressure at output of 2815 MBtu/hr
=
6 “WC
•
Pressure in combustion chamber
= 1.18 “WC
6 + 1.18
= 7.15 “WC
pressure required at pressure test point 1) (Fig. 22).
p “wc gas butterfly 2)(Fig. 22)
Fig. 22
1
2
D2441
RS 68/E LN
RS 120/E LN
MBtu/hr
kW
p “WC
MBtu/hr
kW
p “WC
1194
350
0.04
2047
600
0.1
1365
400
0.04
2218
650
0.1
1535
450
0.04
2440
715
0.2
1706
500
0.1
2593
760
0.2
1877
550
0.1
2815
825
0.2
2047
600
0.1
3037
890
0.2
2218
650
0.1
3258
955
0.2
2388
700
0.1
3480
1020
0.3
2559
750
0.2
3719
1090
0.3
2730
800
0.2
3992
1170
0.3
2934
860
0.2
4265
1250
0.4
3071
900
0.2
4335
1300
0.5
3241
950
0.2
4606
1350
0.5
4777
1400
0.5
Fig. 23
Burner output operation
D3182
p (“WC)
p (“WC)
RS 6
8
/E
L
N
RS 12
0/E L
N
Burner output operation
Содержание RS 120/E LN