Faults - Possible causes - Solutions
Find a list of faults, causes and possible solutions for a set of failures that may occur and result in irregular burner operation or no
functioning at all.
If a burner malfunction is detected, first of all:
•
check that the electrical wiring is adequately connected;
•
check whether fuel is delivered;
•
check that every adjustment parameter is adequately set.
GAS OPERATION
Symbol
(1)
Problem
Possible cause
Recommended remedy
The burner does not start No electrical power supply
Close all switches and check connections
A limit or safety thermostat/pressure switch
open
Adjust or replace
Control box lockout
Release the control box
Control box fuse interrupted
Replace it
(2)
Incorrect electrical wiring
Check
Defective control box
Replace
No gas supply
Open the manual valves between meter
and train
Mains gas pressure insufficient
Contact your GAS COMPANY
Minimum gas pressure switch fails to close
Adjust or replace
Air pressure switch in operating position
Adjust or replace
The servomotor contact does not intervene
(closure cam 0°)
Adjust the closure cam 0°
or replace the servomotor
The burner does not
switch on, and the lock-
out appears
Flame simulation
Replace the control box
Faulty motor remote control switch
Replace
Defective electrical motor
Replace
Motor lockout
Release the thermal relay
The burner starts up but
stops at the damper
maximum opening
The servomotor contact does not intervene
(maximum cam opening)
Cam adjustment (maximum opening)
or replace the servomotor
The burner starts and
then goes into lockout
Air pressure switch does not commute due to
insufficient air pressure:
Adjust or replace
Pressure switch pressure point pipe blocked
Clean
Air pressure test point defective or broken
Check the assembly or replace it
Dirty fan
Clean
High depression in the furnace
Contact our Technical Department
The burner turns on and
then remains in lockout
mode
Failure to the flame detection circuit
Replace the control box
The burner remains in
pre-purging phase
The servomotor contact does not intervene
(minimum cam)
Cam adjustment (minimum)
or replace the servomotor
Once the pre-purging
and the safety time has
elapsed the burner goes
into lockout without the
flame appearing
The VR solenoid lets too little gas through
Increase
The VR or VS solenoid or does not open
Replace the coil or the rectifier panel
Gas pressure too low
Increase pressure at governor
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
Faulty or grounded high voltage cable
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Faulty ignition transformer
Replace
Incorrect valve or ignition transformer connec-
tions
Redo them
Defective control box
Replace
A closed valve upline the gas train
Open
Air in pipework
Bleed air
Lockout with flame
appearing
The VR solenoid lets too little gas through
Increase
Dirty flame sensor
Check, replace flame sensor
Faulty connection
Check, replace flame sensor
Insufficient detection current
Measure current, replace flame sensor
Flame sensor exhausted, faulty
Replace
Maximum gas pressure switch intervention
Adjust or replace
Defective control box
Replace
P
1
Содержание RLS 310/M MX
Страница 2: ...Original instructions ...
Страница 62: ...20084880 60 GB Appendix Electrical panel layout RLS 310 410 M MX 230 400V DSU ...
Страница 63: ...61 20084880 GB Appendix Electrical panel layout RLS 310 410 510 610 M MX 400V ST ...
Страница 66: ...20084880 64 GB Appendix Electrical panel layout 0 0 0 ALL MODELS ...
Страница 67: ...65 20084880 GB Appendix Electrical panel layout 0 0 0 1 ALL MODELS ...
Страница 68: ...20084880 66 GB Appendix Electrical panel layout 0 1 1 2 1 1 1 1 1 1 1 0 1 ALL MODELS ...
Страница 69: ...67 20084880 GB Appendix Electrical panel layout ALL MODELS ...