Start-up, calibration and operation of the burner
45
20036644
GB
5.9
Final checks (with the burner working)
Open the control limit operation
Open the high limit operation
The burner must stop
Rotate the maximum gas pressure switch knob to the mini-
mum end-of-scale position
Rotate the air pressure switch knob to the maximum end of
scale position
Rotate the maximum oil pressure switch at the minimum of
the scale
The burner must stop in lockout
Switch off the burner and disconnect the voltage
Disconnect the minimum gas pressure switch
Rotate the minimum low oil pressure switch at the maximum
of the scale
The burner must not start
Cover the QRI flame detector
The burner must stop in lockout due to firing failure
WARNING
Make sure that the mechanical locking systems on
the different adjustment devices are fully tightened.