19
20009654
GB
Installation
5.7
Securing the burner to the boiler
Prepare an adequate system of hoisting by hooking onto the
rings 3)(Fig. 12).
Slip the thermal protection (standard equipment) onto the
blast tube 4)(Fig. 12).
Place entire burner on the boiler hole arranged previously,
see (Fig. 11), and fasten with the screws given as standard
equipment.
5.8
Accessibility to the interior of the combustion head
In order to reach inside the combustion head proceed as follows:
Open burner at hinge (Fig. 13) after removing the 4
screws 1).
Disconnect the wires 2) from the electrodes.
Disconnect the oil pipes by unscrewing the two connec-
tors 3).
Unscrew the under part of the elbow 4) until it comes free
of its slot.
Extract the internal part 5) of the combustion head.
WARNING
The burner-boiler seal must be airtight.
Fig. 12
D3507
WARNING
While unscrewing, some fuel may leak out.
Fig. 13
1
4
1
2
5
3
A
D3508