31
20165123
GB
Start-up, calibration and operation of the burner
6.4
Adjustments prior to ignition (gas)
Combustion head adjustment is already described on page 20.
In addition, the following adjustments must also be made:
open the manual valves upstream of the gas train.
Adjust the minimum gas pressure switch to the start of the
scale (Fig. 40).
Adjust the air pressure switch to the start of the scale
(Fig. 39).
Bleed off the gas line air. We recommend using a plastic
tube routed outside the building and to purge air until gas is
smelt.
Fit a U-type pressure gauge (Fig. 35) to the gas pressure
test point on the pipe coupling.
Used to approximately calculate burner output in the 2nd
stage using the Tab. K on page 25.
Connect two lamps or testers in parallel to the two gas line
solenoid valves VR1 and VS in order to check the exact
moment at which voltage is supplied.
This operation is not required if each of the two solenoid
valves is equipped with a pilot light that signals voltage
passing through.
6.5
Burner start-up (gas)
Close the remote controls and turn:
switch 1)(Fig. 33 on page 30) in “
BURNER ON
” position;
switch 2)(Fig. 33 on page 30) in “
1st STAGE
” position:
fuel selector switch in “
GAS
” position (Fig. 36).
As soon as the burner starts, check that the lamps or the testers
connected to the solenoid valves or the warning lights on the
solenoid valves indicate no voltage presence. If they indicate the
presence of voltage, stop the burner
immediately
and check the
electric connections.
6.6
Burner ignition
Once the above steps are completed, the burner should ignite.
If the motor starts but the flame does not appear and the control
box goes into lockout, reset and wait for a new ignition attempt.
If ignition does not occur, it is possible that gas is not reaching the
combustion head within the safety time period of 3 seconds.
Therefore, it is necessary to increase gas ignition delivery.
The arrival of gas to the sleeve is indicated by the U-type
pressure gauge (Fig. 35).
If the burner locks out again, refer to chapter "Problems - Causes
- Remedies signalled by LED indicators” on page 43.
Once ignition has taken place, proceed with burner global
calibration operations.
CAUTION
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas
delivery at the minimum.
Fig. 35
D1138
ATTENTION
It is recommended to adjust first the light oil burner
and then the gas burner.
Carry out the fuel change with burner off.
OIL
GAS
OFF
Fig. 36
20141121
ATTENTION
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
If the burner locks out for a third time, contact the
customer service.
DANGER
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
Содержание RLS 28
Страница 2: ...Translation of the original instructions ...
Страница 54: ...20165123 52 GB Appendix Electrical panel layout 0 1 1 1 ...
Страница 55: ...53 20165123 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 5 5 RLS 28 ...
Страница 56: ...20165123 54 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1 5 5 RLS 50 ...
Страница 61: ......
Страница 62: ......
Страница 63: ......