6423
28
GB
Maintenance
Flame inspection window
Clean the glass whenever necessary (Fig. 32).
Hoses
Check periodically the flexible pipes conditions. They have
to be replaced at least
every 2 years
.
In case of use of gas oil and bio fuel blends, it is strongly
recommended to inspect
even more frequently
the hoses
and replace them where contamination has occurred.
Check to make sure that the hoses are still in good condi-
tion.
Fuel tank
If water or contamination is present within the fuel tank, it is es-
sential that this is removed before the equipment is to be used.
This is extremely important when gas oil containing Bio diesel is
in use. If in doubt about how to achieve this then please contact
the fuel or oil tank supplier.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Fuel pump and/or couplings replacement
In conformity with Fig. 33.
9.3
Opening the burner
–
Remove screw 1 and withdraw the casing 2)(Fig. 34)
–
Unscrew screw 3)(Fig. 34)
–
Fit the two extensions 4), on the burner, on the guides 5)
(model with nozzle 351 mm)
–
Pull part A backward keeping it slightly raised to avoid dam-
aging the disk 6) on blast tube 7).
9.4
Closing the burner
Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
Fig. 32
D484
Fig. 33
D1108
DANGER
Disconnect the electrical supply from the
burner.
D486
Fig. 34
Содержание RL 50
Страница 2: ......
Страница 38: ......
Страница 39: ......
Страница 40: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com ...