27
20035745
GB
Maintenance
8.1
Notes on safety for the maintenance
The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
Before carrying out any maintenance, cleaning or checking oper-
ations:
8.2
Maintenance programme
8.2.1
Maintenance frequency
The combustion system should be checked at least once a year
by a representative of the manufacturer or another specialised
technician.
8.2.2
Checking and cleaning
Combustion
The optimum calibration of the burner requires an analysis of the
flue gases.
Significant differences with respect to the previous measure-
ments indicate the points where more care should be exercised
during maintenance.
Combustion head
Check to make sure that all the parts of the combustion head are
in good condition, positioned correctly, free of all impurities, and
that no deformation has been caused by operation at high tem-
peratures.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Burner
Check for excess wear or loose screws. Also make sure that the
screws securing the electrical leads in the burner connections are
fully tightened. Clean the outside of the burner.
Photocell
Clean the glass cover from any dust that may have accumulated.
Photocell 1)(Fig. 29) can be removed by pulling it outward force-
fully.
Filters
Check the filtering baskets on line and at nozzle present in the
system. Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a
separate pump to lift any water and other impurities that may
have deposited on the bottom of the tank.
Pump
The delivery pressure must be stable. The depression must be
less than 0.4 bar. Unusual noise must not be evident during pump
operation.
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner. This meas-
ure permits the cause of the anomaly to be traced to either the
suction piping or the pump.
If the pump is found to be responsible, check to make sure that
the filter is not dirty. The vacuometer is installed upstream from
the filter and consequently will not indicate whether the filter is
clogged or not. Contrarily, if the problem lies in the suction line,
check to make sure that the filter is clean and that air is not enter-
ing the piping.
Please check that the supply line and filters are clear. The use of
a pump vacuum gauge will assist in this. This measure permits
the cause of the anomaly to be traced to either the suction line or
the pump.
8
Maintenance
DANGER
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
tents of this manual and in compliance with the
standards and regulations of current laws.
DANGER
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
Fig. 29
D3327
1
Содержание RL 300/B MZ
Страница 2: ......
Страница 38: ...20035745 36 GB Appendix Electrical panel layout RL 300 B MZ ...
Страница 39: ...37 20035745 GB Appendix Electrical panel layout RL 400 B MZ ...
Страница 40: ...20035745 38 GB Appendix Electrical panel layout ...
Страница 41: ...39 20035745 GB Appendix Electrical panel layout ...
Страница 44: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com ...