51
Operating
line
User level Function
Default value
Min
Max
Unit
6046 I
Function of input H2
Optg mode changeover HCs + DHW
¦ Optg mode changeover HCs ¦
Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode
changeover HCP ¦ Heat generation
lock ¦ Error/alarm message ¦ Min flow
temp setpoint ¦ Excess heat discharge
¦ Swimming pool enable ¦ Dewpoint
monitor (**) ¦ Flow temp. setpt increase,
hygro (**) ¦ Refrig request (**) ¦ Heat
request 10V ¦ Refrig. request 10V (**) ¦
Pressure measurement 10V ¦ Rel. room
humidity 10V (**) ¦ Room temperature
10V (**)
Optg mode chan-
geover HCs+DHW
6047 I
Contact type H2
NC ¦ NO
NO
-
6048 (**)
I
Function value, contact H2
70
8
130
°C
6048 (***) I
Min flow temp setpoint H2
70
8
120
°C
6049 (**)
I
Voltage value 1, H2
0
0
10
Volt
6050 (**)
I
Function value 1, H2
0
-100
500
-
6050 (***) I
Temp value 10V H2
100
5
130
°C
6051 (**)
I
Voltage value 2, H2
10
0
10
Volt
6052 (**)
I
Function value 2, H2
70 -100
500
-
6052 (***)
I
Pressure value 3.5V H2
5.0
0.0
10.0
bar
6070 (***) I
Function output UX
None ¦ Boiler pump Q1 ¦ DHW pump Q3
¦ DHW interm circ pump Q33 ¦ Heat circ
pump HC1 Q2 ¦ Heat circ pump HC2 Q6
¦ Heat circ pump HCP Q20 ¦ Collector
pump Q5 ¦ Solar pump ext exch K9 ¦
Solar pump buffer K8 ¦ Solar pump swi
pool K18 ¦ Collector pump 2 Q16 ¦ Boiler
setpoint ¦ Output setpoint ¦ Heat request
None
6071 (***) I
Signal logic output UX
Standard ¦ Inverted
Standard
6075 (***) I
Temperature value 10V UX
100
5
130
°C
6097 F
Sensor type collector
NTC 10k ¦ Platinum 1000
NTC 10k
6098
F
Readjustm collector sensor
0
-20
20
°C
6099
F
Readjustm coll sensor 2
0
-20
20
°C
6100
F
Readjustm outside sensor
0
-3.0
3.0
°C
6101 F
Sensor type flue gas temp
NTC 10k ¦ Platinum 1000
NTC 10k
6102
F
Readjustm flue gas sensor
0
-20
20
°C
6110
F
Time constant building
15
0
50
h
6112
O
Gradient room model
60
0
300
Min/°C
6116 (**)
O
Time constant setp compens
10
0
14
min
6117
O
Central setp compensation
20
− − − / 1
100
°C
6118 O
Setpoint drop
delay
60
− − − / 1
200
k/min
6120 F
Frost protection for the plant
Off ¦ On
Off -
6128
F
Heat request below OT
− − −
− − − /
-50
50 °C
E
=End user
I
=Commissioning
F
=Heating engineer
O
=OEM
BZ
=Operating line
(*) QAA75../78.. only, (**) RIELLOtech CLIMA COMFORT only, (***) RIELLOtech CLIMA TOP only.