Riello REG 35.5 Скачать руководство пользователя страница 6

2416

4

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and
CO

2

 concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.

To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of
the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267). They refer to 12.5% CO

2

 at sea

level and with light oil and room temperature of 20°C.

PUMP PRESSURE

: 12 bar, the pump leaves the factory set at this value.

RECOMMENDED NOZZLES

:  Delavan type W -B; Danfoss type S - B; Monarch type R; Steinen type S - Q.

Nozzle

GPH Angle

Pump pressure

bar

Burner output

kg/h 

±

 4%

Comb. head adjustment

Set-point

Air damper adjustment

Set-point

0.60

80°

11

2.3

0.5

2.5

0.65

60°

12

2.6

1

3.5

0.75

60°

12

3.0

1.5

3.5

0.85

60°

12

3.4

2.5

5.0

1.00

60°

12

4.0

3

7.5

1.10

60°

12

4.4

4

9.0

1.25

60°

12

5.0

4

10.0

COMBUSTION ADJUSTMENT

– Remove the nozzle holder assembly from the

burner (see page 3).

– Remove the diffuser-disc assembly 

(1)

 from the

nozzle holder 

(2)

 after loosening the screw 

(3)

.

– Insert the proper nozzle 

(6)

 into the nozzle holder

and tighten securely.

– REPLACE THE DIFFUSER-DISC ASSEMBLY (1)

AND INSERT IT IN THE NOZZLE HOLDER (2)
UNTIL THE END. LOCK WITH SCREW (3).

– Remove the nozzle holder assembly (see page 3).

– Loosen the screw 

(4)

, move the electrodes assem-

bly 

(5)

 and lock the screw 

(4)

.

It depends on the output of the burner and is carried
out by rotating clockwise or counterclockwise the set-
ting screw 

(1)

 until the set-point marked on the regu-

lating rod 

(2)

 is level with the outside plane of the

nozzle holder assembly 

(3)

.

Loosen the screw 

(1)

 and move the indicator towards

the required set-point and then lock the screw 

(1)

.

NOZZLE POSITIONING

 

(Fig. 10)

ELECTRODE SETTING

 

(Fig. 10)

COMBUSTION HEAD SETTING

 

(Fig. 11)

Fig. 11

S7032

1

2

3

MEASURES MUST BE
RESPECTED

WARNING:

Fig. 10

D5268

4.5 

– 0.5 mm

0

2 – 2.5 

mm

6

3

1

2

4

5

AIR DAMPER ADJUSTMENT

    

(Fig. 12)

Fig. 12

S7033

Содержание REG 35.5

Страница 1: ...Installation use and maintenance instructions 2902416 5 05 2016 Light oil burner CODE MODEL TYPE 3772216 REG 35 5 722T GB ...

Страница 2: ......

Страница 3: ...UIPMENT No 1 Flange with insulating gasket No 2 Flexible pipes with nipples O Burner with CE marking in conformity with EEC directives EMC 2014 30 UE Low Voltage 2014 35 UE Machines 2006 42 EC and Efficiency 92 42 EC O The burner meets protection level of IP X0D IP 40 EN 60529 O CE Certification No 0036 0342 03 as 92 42 EC TECHNICAL DATA 7 8 D5263 Fig 1 ø 89 121 5 80 FIRING RATE as EN 267 2 2 5 3 ...

Страница 4: ...of the valve It is necessary to install a filter on the fuel supply line H difference of level L max lenght of the suction line I D internal diameter max 4 m Fig 5 H H meters L meters I D 8 mm I D 10 mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 O Before starting the burner make sure that the return pipe line is not clogged An excessive back pressure would cause the damage of the pump seal O The pump is...

Страница 5: ...stat Remote lock out signal 230V 0 5A max Remove the protection crankcase 8 fig 1 page 1 after removing the 3 retainer screws Widen the upper slit and remove the protection crankcase inserting the oil pipe and the flexible oil lines Insert PG 13 5 cable gland 1 into the wire access hole and tighten it with the nut Insert the electrical cable into the con nector and make electrical connec tions as ...

Страница 6: ...11 2 3 0 5 2 5 0 65 60 12 2 6 1 3 5 0 75 60 12 3 0 1 5 3 5 0 85 60 12 3 4 2 5 5 0 1 00 60 12 4 0 3 7 5 1 10 60 12 4 4 4 9 0 1 25 60 12 5 0 4 10 0 COMBUSTION ADJUSTMENT Remove the nozzle holder assembly from the burner see page 3 Remove the diffuser disc assembly 1 from the nozzle holder 2 after loosening the screw 3 Insert the proper nozzle 6 into the nozzle holder and tighten securely REPLACE THE...

Страница 7: ......

Страница 8: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com ...