Having opened the package, start by checking the contents.
UPS
BATTERY BOX (optional)
Metal slides, Guarantee document, User manual,
Serial connecting cable, 4 battery fuses (to be
inserted in the "SWBATT" fuse holders), Front door
key (
MSM
version only
), Short circuit bar (with 3
fastening screws)
Metal slides, Guarantee document, 4 battery fuses (to be
inserted in the "SWBATT" fuse holders), Front door key
(
MSM
version only
)
I
NSTALLING THE
UPS
AND THE
B
ATTERY
B
OX
When installing the equipment, the following points should be considered:
The wheels are to be used exclusively for fine positioning, and thus for small distances only.
The plastic parts and the door are not to be used for gripping or pushing the UPS.
Sufficient space should be left in front of the equipment for it to be turned on/off and maintenance operations to be
performed on it (
1.5 mt )
The rear part of the UPS should be set at least 30 cm from the wall, to enable the air blown by the ventilation fans to
flow away correctly
No objects should be left on its top surface
Having set the equipment in position, secure it by engaging the brake rod (see "Front Views of the UPS" point 8) situated bel ow
the connecting terminals.
(MSM version only):
In seismic areas or for mobile systems, the brackets used to fasten the unit to the pallet (ramps) can be
reused to anchor the UPS to the floor (see the figure below). In normal conditions, the brackets are not necessary.
S
TEPS TO BE
T
AKEN TO
G
AIN
A
CCESS TO THE
T
ERMINALS OF THE
UPS
/
B
ATTERY
B
OX
The operations indicated below are to be performed with the UPS disconnected from the mains powers,
turned off and with all the switches and fuse holders of the equipment open.
Follow the instructions provided below to open the UPS:
Open the door
Remove the terminal and switches cover (see "Views of the UPS" ref. 7)
Having completed the installation operations inside the equipment, replace the terminal cover and close the door.