2916122
13
GB
Maintenance
6.1
Notes on safety for the maintenance
The periodic maintenance is essential for the good operation,
safety, yield and duration of the gas train.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
Before carrying out any maintenance, cleaning or checking oper-
ations:
6.2
Maintenance programme
6.2.1
Maintenance frequency
6.2.2
Checking and cleaning
6.2.3
Filter maintenance
The filter is an integral part of the system’s safety and must not
therefore be removed under any circumstances.
Replace the filter cartridge if:
–
the
∆
p between the input pressure test point 10)(Fig. 1,
page 4) and the output pressure test point 13) is greater than
10 mbar
–
the
∆
p between the pressure test points has doubled since
the last check.
To replace it:
➤
loosen the screws 1)(Fig. 12) of the cover 2) in the lower part
of the valve
➤
replace the filter cartridge 3)
➤
retighten the screws, but without forcing them
➤
perform an operating check and a leak detection check
p
max
= 360 mbar.
Replace the filtering element if the
∆
p between the pressure test
points 1) and 2)(Fig. 13) is greater than 10 mbar.
To replace it:
➤
loosen the screws of the cover 3)(Fig. 13) and carefully
clean the filter compartment
➤
replace the old filtering element with the new one
➤
replace the cover, then tighten the screws
➤
perform a leak detection check on the filter cover.
6
Maintenance
DANGER
The maintenance interventions and the calibration
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
DANGER
Disconnect the electrical power using the main
switch.
DANGER
Close the fuel interception tap.
Wait for the components in contact with heat
sources to cool down completely.
The gas combustion system should be checked at
least once a year by a representative of the man-
ufacturer or another specialised technician.
The operator must use the required equipment
during maintenance.
WARNING
You are advised to carry out a periodic check to
see how clean it is and, in any case, replace it at
least once a year.
Where the filter is being replaced regularly it is ad-
visable to replace the fixing screws.
MBC 1200/1
MBC 1900-3100-5000/1
1
2
3
Fig. 12
S8569
3
1
2
Fig. 13
S8550
Содержание MBC 1200/1
Страница 2: ......
Страница 30: ...2916122 14 D Wartung 3 1 2 Abb 13 S8550...
Страница 73: ...14 2916122 NL Onderhoud 3 1 2 Fig 13 S8550...
Страница 91: ......