53
COMMISSIONING AND MAINTENANCE
EEPROM CONTROL
The burner controller automatically checks for errors in the mi-
crocontroller EEPROM and enters lockout if an error is detect-
ed. An error is indicated by the LED flashing (see the “Fault diag-
nosis - lockouts” section on page 49).
3.4
Error List
When a technical anomaly occurs, the control interface display
shows a text message (small digit) and a number (large digit),
which indicate the type and level of the detected error.
There are 3 error levels:
1
Permanent: heating and/or DHW requests are suspended
and burner and circulator are switched off. For the error to
disappear, keep the key ENTER/RESET on the control inter-
face pressed for 3 seconds or reset the power supply by
using the main switch.
2 Temporary: heating and/or DHW requests are suspend-
ed and burner and circulator are switched off. The error
disappears automatically when the cause which generated
it is solved.
3 Alert: the thermal unit is not locked out, but its functions
may be limited according to the signalled alert code.
The log of the last ten errors occurred can be viewed through
the error log (menu 9000 - installer level) (from Par. 9001 to Par.
9010).
3.4.1
Permanent Errors
Message
Error No.
Description
Loc
E010
Ignition failure
Loc
E020
Safety thermostat tripped
Loc
E040
Low water pressure - Load the
system
Loc
E042
Pressure transducer not connected
or read value outside of the permit-
ted range
3.4.2
Temporary Errors
Message
Error No.
Description
Err
E046
Pressure decreasing alarm (<0.8)
(temporary)
Err
E060
Domestic hot water probe in short
circuit or disconnected.
Err
E070
Delivery probe in short circuit or
disconnected. Delivery probe fault /
delivery probe overtemperature
Err
E080
Return probe fault / return probe
overtemperature
Err
E099
Too many resets from remote con-
trol. NO MORE RESETS
Err
E100
Communication lost in zone 1 (tem-
porary)
Err
E101
Zone 1 limit thermostat triggering
(temporary)
Err
E102
Zone 1 delivery probe (temporary)
Err
E104
Communication lost in zone 2 (tem-
porary)
Err
E105
Zone 2 limit thermostat triggering
(temporary)
Err
E106
Zone 2 delivery probe (temporary)
Err
E108
Communication lost in zone 3 (tem-
porary)
Err
E109
Zone 3 limit thermostat triggering
(temporary)
Err
E110
Zone 3 delivery probe (temporary)
3.4.3
Warnings
Message
Error No.
Description
Atte
E041
Primary circuit pressure insuffi-
cient (temporary)
Air
E043
Venting cycle in progress (tem-
porary)
Atte
E044
Primary circuit pressure too high
(temporary)