3066
15
GB
COLOUR CODE OF CONTROL BOX RESET BUTTON LED
(
*
) only for applications where this is an option.
4.7.4 LOCKOUT TYPES AND TRIGGERING TIMES IN CASE OF BURNER MALFUNCTION
(
*
) only for applications where this is an option.
4.7.5 CONTROL BOX RESET
To carry out the control box reset, proceed as follows:
³
Hold the reset button down for between 1 and 2 seconds. If the burner does not restart, you must make sure
the limit point thermostat
(TL)
is closed.
³
If the control box reset button keeps flashing, reporting the cause of the malfunction (RED LED), you
must press the button again, holding it down for no more than 2 seconds.
Warning:
If the reset button is pressed for more than 2 seconds, the control box goes into visual diagnostic mode and
the indicator LED begins to blink (see CONTROL BOX VISUAL DIAGNOSTIC page 18).
4.7.6 RE-CYCLE FUNCTION
The control box allows re-cycling, i.e. the complete repetition of the starting programme, for 3 attempts maxi-
mum, in the event the flame goes out during operation.
If the flame goes out again (4
th
time), this will cause the burner to lock out. If there is a new demand for heat dur-
ing the recycle, the 3 attempts are reset when the limit thermostat
(TL)
switches.
4.7.7 LOGGING OF BURNER OPERATION PARAMETERS
With this control box, data - i.e. the number of lockouts that have occurred, the type of lockout that has
occurred (just the last one) and the oil valve opening operating time - can be logged even when there is no
power supply. That way, you can determine how much fuel has been consumed during operation.
To view these parameters, you will need to connect the software diagnostics kit, as described in section
(1.2) on page 2.
Operating status
LED colour codes
Flashing
speed
ON
OFF
Seconds
Standby
LED unlit
Pre-purging
Green
Long pre-purging
Green
Transformer ignition
Green + Yellow flashing
Fast
0.3
0.3
Regular flame
Green + Yellow flashing
Slow
0.3
2
Post-purging
Green + Yellow
Recycle
Green + Yellow flashing
Medium
2
1
Continuous purging (
*
)
Green
Extraneous light during standby
Yellow blinking
Fast
0.3
0.3
Extraneous light during post- or continuous purging (
*
)
Green + Yellow flashing
Fast
0.3
0.3
Extraneous light during lockout
Red + Yellow flashing
Fast
0.3
0.3
Lockout
Red
Lockout with continuous purging (
*
)
Red + Green
DESCRIPTION OF FAULT TYPES
LOCKOUT
Extraneous light when the burner is turned on and off
After max. 30 seconds
Extraneous light detected during standby time
After max. 30 seconds
Extraneous light detected during pre-purging
Within 1 second
Extraneous light detected during post-purging or continuous purging (*)
After max. 30 seconds
Flame goes out during operation
After 3 recycles
No flame is detected after safety time
Immediate