Riello GAS 3 Скачать руководство пользователя страница 8

20144819

GB

Safety and prevention

3.1

Background

The  burners  have  been  designed  and  built  in  compliance  with
current regulations and directives, applying the known technical
rules of safety and envisaging all the potential danger situations.
It is necessary, however, to bear in mind that the imprudent and
clumsy use of the equipment may lead to situations of death risk
for the user or third parties, as well as the damaging of the burner
or other items. Inattention, thoughtlessness and excessive confi-
dence often cause accidents; the same applies to tiredness and
sleepiness.
It is a good idea to remember the following:

The burner must only be used as expressly described. Any
other use should be considered improper and therefore dan-
gerous.

Namely:
it can be applied to boilers operating with water, steam, diather-
mic oil, and to other uses expressly named by the manufacturer;

the type and pressure of the fuel, the voltage and frequency of the
electrical power supply, the minimum and maximum deliveries for
which the burner has been regulated, the pressurisation of the
combustion chamber, the dimensions of the combustion cham-
ber and the ambient temperature must all be within the values in-
dicated in the instruction manual.

Modification of the burner to alter its performance and desti-
nations is not allowed.

The burner must be used in exemplary technical safety con-
ditions. Any disturbances that could compromise safety must
be quickly eliminated.

Opening  or  tampering  with  the  burner  components  is  not
allowed, apart from the parts requiring maintenance.

Only  those  parts  envisaged  by  the  manufacturer  can  be
replaced.

3.2

Personnel training

The user is the person, body or company that has acquired the
machine and intends to use it for the specific purpose. He is re-
sponsible for the machine and for the training of the people work-
ing around it.
The user:

undertakes  to  entrust  the  machine  exclusively  to  suitably
trained and qualified personnel;

undertakes to inform his personnel in a suitable way about
the  application  and  observance  of  the  safety  instructions.
With that aim, the user undertakes to ensure that everyone
knows the use and safety instructions for his own duties;

Personnel must follow all the danger and caution indications
shown on the machine.

Personnel must not carry out, on their own initiative, opera-
tions or interventions that are not within their province.

Personnel  are  obliged  to  inform  their  superiors  of  every
problem or dangerous situation that may arise.

The assembly of parts of other makes, or any modifications,
can alter the characteristics of the machine and hence com-
promise  operating  safety.  The  manufacturing  company
therefore accepts no responsibility whatsoever for any which
may result from the use of non-original parts.

In addition:

3

Safety and prevention

WARNING

The  manufacturer guarantees  safety  and  proper
functioning only if all burner components are intact
and positioned correctly.

the  user  must  take  all  the  measures  neces-
sary  to  prevent  unauthorised  people  gaining
access to the machine;

the  user  must  inform  the  manufacturer  if
faults  or  malfunctioning  of  the  accident  pre-
vention  systems  are  noticed,  along  with  any
presumed danger situation;

Personnel must always use the personal pro-
tective  equipment  envisaged  by  legislation
and follow  the indications given  in  this man-
ual.

Содержание GAS 3

Страница 1: ...ation use and maintenance instructions 20144819 3 01 2019 Forced draught gas burners One stage operation CODE MODEL TYPE 3751918 GAS 3 519 T1 3751617 GAS 4 516 T1 3751717 GAS 5 517 T1 3751817 GAS 6 51...

Страница 2: ...Translation of the original instructions...

Страница 3: ...n 13 5 1 Notes on safety for the installation 13 5 2 Handling 13 5 3 Preliminary checks 13 5 4 Operating position 14 5 5 Preparing the boiler 14 5 5 1 Boring the boiler plate 14 5 5 2 Blast tube lengt...

Страница 4: ...eset 26 6 8 3 Visual diagnostics 26 6 8 4 Software diagnostics 26 7 Maintenance 27 7 1 Notes on safety for the maintenance 27 7 2 Maintenance programme 27 7 2 1 Maintenance frequency 27 7 2 2 Safety t...

Страница 5: ...ds EN 676 EN 12100 and according to the European Directives GAR 2016 426 EU only 519 T1 Gas Devices Directive MD 2006 42 EC Machine Directive LVD 2014 35 EU Low Voltage Directive EMC 2014 30 EU Electr...

Страница 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Страница 7: ...of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasonab...

Страница 8: ...ose parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific purpose He is...

Страница 9: ...230 50 Direct 3751617 GAS 5 TC 3 230 400 50 Direct 3751717 GAS 6 TC 3 230 400 50 Direct 3751817 Country of destination Gas category SE FI AT GR DK ES GB IT IE PT IS CH NO I2H DE I2ELL NL I2L I2E I2 43...

Страница 10: ...arts list No 1 MODEL GAS 3 GAS 4 GAS 5 GAS 6 Type 519 T1 516 T1 517 T1 518 T1 Electrical supply 1 PH 1N 230V 50 Hz Electrical supply 3 PH 3 230 400V 10 50 Hz Electrical motor rpm kW V A 2750 0 250 230...

Страница 11: ...amber 0 7 mbar the maximum pressure curve in comb chamber If the burner develops an output of 240 kW at a pressure in com bustion chamber of 5 mbar the work point is found on the maxi mum pressure cur...

Страница 12: ...set in relation to special test boilers accord ing to EN 676 regulations In Fig 3 you can see the diameter and length of the test combus tion chamber Example Output 1500 Mcal h diameter 80 cm length...

Страница 13: ...S 3 4 models 6 Motor contactor and thermal relay in GAS 5 6 models 7 Terminal board 8 Cable grommets for electrical wiring to be carried out by the installer 9 Control box with lockout pilot light and...

Страница 14: ...the development of conden sate and humidity Otherwise before switching on again make sure that the entire control box is perfectly dry Static charges must be avoided since they can damage the control...

Страница 15: ...be free from hazardous mixes e g chloride fluoride halo gen if present it is highly recommended to carry out cleaning and maintenance more frequently WARNING The handling operations for the burner can...

Страница 16: ...on device in refractory material 7 must be in serted between the boiler refractory 8 and the blast tube 6 This protective fettling must not compromise the extraction of the blast tube WARNING The burn...

Страница 17: ...e them Finally put back the fan 4 Fig 9 on the slide bars 3 put back the screws 2 and with the burner open proceed to the adjustment of the combustion head 5 6 Positioning the probe electrode If the p...

Страница 18: ...W boiler Considering an efficiency of 89 the burner should deliver about 270 kW The diagram Fig 13 shows that the gas and air adjustments for this burner output are carried out on notch 4 5 NOTE The d...

Страница 19: ...00 kW 9 Gasket for flanged versions only 10 Pressure adjuster 11 Train Burner adaptor supplied separately P2 Upstream pressure of valves adjuster P3 Upstream pressure of the filter L Gas train supplie...

Страница 20: ...that there are no gas leaks Pay attention when handling the train danger of crushing of limbs Make sure that the gas train is properly installed by checking for any fuel leaks The operator must use th...

Страница 21: ...mbustion chamber 2 mbar 10 3 2 8 3 mbar A pressure of 5 3 mbar column 1 corresponds in Tab F to an output of 277 kW This value serves as a rough guide the effective output must be measured at the gas...

Страница 22: ...x to per form checks of its own start up efficiency Normally burner stopping is guaranteed by the boiler s thermostat pres sure switch If this is not the case a time switch should be fitted in series...

Страница 23: ...ry CABLE SECTIONS Section not indicated 1 5 mm2 Tab G 5 10 Calibration of the thermal relay only 3pH versions This is required to avoid motor burn out in the event of a signifi cant increase in power...

Страница 24: ...he flame does not appear and the control box goes into lockout reset and wait for a new ignition attempt If ignition is still not achieved it may be that gas is not reaching the combustion head within...

Страница 25: ...to measure the ignition output Remove the UV sensor 29 Fig 4 on page 11 the burner starts and locks out after the safety time Perform 10 ignitions with consecutive lockouts Read the quantity of gas bu...

Страница 26: ...the burner operating in the 2nd stage increase adjustment pressure by slowly turning the relative knob clockwise until the burner stops Then turn the knob anticlockwise by 0 2 kPa 2 mbar and repeat b...

Страница 27: ...lockout within 3s from the opening of the gas valve and 43 s from the closure of the TL re mote control 0s Control remote control TL closes Electrical control box programme starts 2s The fan motor st...

Страница 28: ...linked The number of blinks indicates the reason for the malfunctioning refer to the coding in Tab M on page 31 6 8 4 Software diagnostics Gives an analysis of the life of the burner through optical c...

Страница 29: ...or open ing closing position indicators that are activated when they are powered 7 2 3 Checking and cleaning Burner Check that there are not excess wear or loosen screws The screws securing the electr...

Страница 30: ...Safety components The safety components should be replaced at the end of their life cycle indicated in the following table The specified life cycles do not refer to the warranty terms indi cated in th...

Страница 31: ...rner by means of the main system switch DANGER Close the fuel interception tap Wait for the components in contact with heat sources to cool down completely Fig 28 D202 WARNING When the burner is closi...

Страница 32: ...t switch on and the lock out appears Air pressure switch in operating position Adjust or replace The burner switches on but then stops in lockout Air pressure switch does not switch owing to lack of a...

Страница 33: ...ce The burner continues to repeat the start up cy cle without lockout The gas pressure in the gas mains lies very close to the value to which the gas pressure switch has been set The sudden drop in pr...

Страница 34: ...rial and fully encloses the burner The casing is mounted on wheels can be easily moved for burner inspection A Appendix Accessories COD 3000605 L 185 L1 320 mm GAS 3 COD 3000606 L 187 L1 320 mm GAS 4...

Страница 35: ...articularly subject to radio dis turbance emission of signals exceeding 10 V m owing to the presence of an INVERTER or in applications where the length of the thermostat connections exceeds 20 metres...

Страница 36: ...ASE DIAGRAM A Electrical system external connections without valve leak control burners GAS 3 4 SINGLE PHASE DIAGRAM B Electrical system external connections with valve leak control burners GAS 5 6 TH...

Страница 37: ...35 20144819 GB Appendix Electrical panel layout GAS 3 4 SINGLE PHASE D2855 DIAGRAM A...

Страница 38: ...20144819 36 GB Appendix Electrical panel layout GAS 5 6 THREE PHASE D2861 DIAGRAM A...

Страница 39: ...37 20144819 GB Appendix Electrical panel layout 20144739 GAS 3 4 SINGLE PHASE DIAGRAM B...

Страница 40: ...20144819 38 GB Appendix Electrical panel layout DIAGRAM B GAS 5 6 THREE PHASE 20144741...

Страница 41: ...39 20144819 GB Appendix Electrical panel layout GAS 3 4 SINGLE PHASE DIAGRAM C 20144742...

Страница 42: ...20144819 40 GB Appendix Electrical panel layout DIAGRAM C GAS 5 6 THREE PHASE 20144743...

Страница 43: ...S1 Lockout signal of the remote leak detection control TL Limiter control device shuts down the burner when the temperature or the boiler pressure reaches the pre set value TS Safety limit control dev...

Страница 44: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: