2406
1
GB
ENGLISH
TECHNICAL DATA
■
Burner with CE marking in conformity with EEC Directives: Machine Directive 2006/42/EC, Low Voltage
Directive 2006/95/EC, Electromagnetic Compatibility 2004/108/EC and Efficiency 92/42/EEC.
■
The burner meets protection level of IP 40, EN 60529.
TYPE
482 T58
Thermal power – output
95 – 240 kW
-
8 – 20 kg/h
Fuel
Light oil, viscosity 4 – 6 mm
2
/s at 20 °C
Electrical supply
Single phase,
220 V
± 10%
~
60Hz
Motor
Run current 2.2 A – 3250 rpm – 340 rad/s
Capacitor
4
µ
F
Ignition transformer
Secondary 8 kV – 16 mA
Pump
Pressure 8 – 15 bar
Absorbed electrical power
0.41 kW
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Hydraulic jack with air-damper
7 – Combustion head adjustment screw
8 – Reset button with lock-out lamp
9 – Flange with insulating gasket
10 – Start delaying device
D8077
Fig. 1
BURNER EQUIPMENT
Quantity
Description
2
1
4
1
1
1
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Maintenance assembly
Cable grommet
Screw with two nuts for flange