22
ENd USER
Operating
line
User
level
Function
Default value
Range
Unit
Range
Min
Max
907 (**)
E
release
24h/day ¦ Time programs HCs ¦ Time pro-
gram 5
24 h/day
-
Heating circuit 2
1010
E
Comfort cooling setpoint
20.0
Op line
1012
Operating
line 1016
°C
1012
E
Reduced setpoint
16
Op line
1014
Operating
line 1010
°C
1014
E
Frost protection setpoint
10.0
4
Operating
line 1012
°C
1016
F
Comfort setpoint maximum
35.0
Op line
1010
35
°C
1020
E
Heating curve slope
1.50
0.10
4.00
-
1030
E
Summer/winter heating limit
18
− − − /
8
30
°C
Heating circuit P
1300
E
Operating mode
Protection ¦ Automatic ¦ Reduced ¦
Comfort
Automatically
-
1310
E
Comfort cooling setpoint
20.0
Op line
1312
Op line
1316
°C
1312
E
Reduced setpoint
16
Op line
1314
Op line
1310
°C
1314
E
Frost protection setpoint
10.0
4
Op line
1312
°C
1320
E
Heating curve slope
1.50
0.10
4.00
-
1330
E
Summer/winter heating limit
18
− − − /
8
30
°C
DHW
1610
E
Nominal setpoint
55
Op line
1612
BZ 1614
OEM
°C
Swimming pool
2055
F
Setpoint solar heating
26
8
80
°C
2056
F
Setpoint source heating
22
8
80
°C
Maintenance / special operation
7130
E
Chimney sweep function
Off ¦ On
Off
-
7140
E
manual operation
Off ¦ On
Off
-
Diagnostics, heat generation
8526
E
24-hour yield solar energy
0
0
999.9
kW/h
8527
E
Total yield solar energy
0
0
9999999.9
kW/h
8570
E
Hours run solid fuel boiler
0
0
65535
h
w