COMMISSIONING AND MAINTENANCE

24

Avoid using mobile phones.

3.2.1  Refrigerant label

According to EC Regulation No. 517/2014 regarding certain fluor-
inated greenhouse gases, the total amount of refrigerant con-
tained within the installed system must be indicated. This infor-
mation can be found on the outdoor unit technical data plate.

A   Standard  charge
B   Additional  charge
C   Total  charge
D   Equivalent total weight of CO2

QUESTO APPARECCHIO CONTIENE 

GAS AD EFFETTO SERRA COPERTI 

DAL PROTOCOLLO DI KYOTO.   

INFORMAZIONI SUL REFRIGERANTE 

 

Refrigerante

Carica addizionale

Carica totale

Carica di fabbrica

(vedi etichetta tecnica)

É VIETATO DISPERDERE

 

IL GAS R32 DIRETTAMENTE

 

IN ATMOSFERA  

Istruzioni per compilare l’Etichetta “F-Gas Label”:

1 - Annotare le quantità sull’etichetta con inchiostro indelebile

2 - Collocare l’adesivo plastico di protezione (consegnato assieme al manuale)

3 - Peso equivalente CO2 del sistema in tonnellate = Carica totale in kg / 1000 x GWP

GW

P

675

R32

A

B

C
D

Peso equivalente CO2

kg
kg
kg

t

To fill in the tag:

 

note the quantity onto the label with indelible ink

 

place the refrigerant gas label on the outdoor unit

This unit contains fluorinated greenhouse gases covered 
by the Kyoto protocol. Maintenance and disposal activities 
must be carried out exclusively by skilled personnel.

Global warming potential of the R32 refrigerant gas: GWP=675

If necessary, the refrigerant must be recovered and not dis-
persed into the environment.

 

0

It is forbidden to disperse the refrigerant into the environ-
ment.

3.3  Ordinary maintenance

Periodical maintenance is fundamental to keep the device effi-
cient, safe and reliable over time, and it can be carried out on 
a regular basis, depending on the type of intervention required, 
by our Technical Support Service, which is technically trained and 
licensed and can also provide original spare parts if necessary.

For units installed in a seaside environment, the mainte-
nance intervals shall be halved.

Original conditions must be restored after performing the 
required maintenance operations.

All described operations MUST be carried out under the fol-
lowing conditions:

 

cold device

 

device NOT supplied with electric power

 

suitable personal protection equipment

 

0

It is forbidden to open the access doors and carry out any 
technical or cleaning operation before disconnecting the 
device from the power supply by positioning the system 
main switch to "OFF"

ON 

OFF 

 

set the system main switch to “OFF”

Wait 10 minutes before touching the device electric compo-
nents.

Check with a tester that the voltage between connectors 
CN25 and CN 28 of the main electronic board is lower than 
10 Vdc.

Yearly operations

The annual maintenance plan includes the following checks:

 

power supply voltage

 

electric connection tightening

 

status of cooling and hydraulic joint

 

finned coil cleaning

 

electric absorption

 

fan grille cleaning

Cleaning the heat exchanger fins

The thermal exchange bank must be cleaned with compressed 
air.
Cleaning must be performed at least once a year, depending on 
the location, because the dirt gathering in the rows narrows the 
passageway section and reduces the exchange capacity.

 

check the alignment of the aluminium fins of the coil and, 
if necessary, straighten them with a suitable comb

 

check that the condensate discharge pipe is clean

Do not use any means to accelerate the defrosting.

Do not use systems different from the ones indicated in this 
manual.

Emptying of the evaporator

This operation may be necessary to perform reparations on the 
low pressure side (evaporator), the device reallocation or the re-
placement of the indoor unit without losing the whole refriger-
ant charge.
Proceed as follows:

 

remove the covering plug from the shut-off valve

 

check that the three-way shut-off valve is fully open

 

let the device operate in cooling mode for 10 - 15 minutes

 

stop the device for about 3 minutes

 

connect the charging tube of the pressure gauge unit to 
the three-way valve service connection on gas side

 

vent the air from the charging tube

 

close the two-way shut-off valve on liquid side

 

operate the equipment in cooling mode until pressure 
gauge reads a suction pressure of approx. -1 MPa

 

close the three-way shut-off valve on gas side

 

stop the unit

 

disconnect the pressure gauge unit

 

refit the valve covering plug

Содержание AARIA START

Страница 1: ...AARIA START SERIES R32 11 2017 cod Doc 0086715 rev 0 EN INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...

Страница 2: ...mps are compliant with the following European Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU RoHS Directive 2011 65 EU ErP Directive 2009 125 EC and Reg...

Страница 3: ...Place of installation p 12 2 7 Recommended distances p 12 2 8 Positioning p 13 2 9 Installation on old systems or systems in need of upgrading p 14 2 10 Refrigerating connection p 14 2 11 Wiring diag...

Страница 4: ...operate carefully so as to avoid damaging the gas circuit and the fin bank 9 Do not place any inflammable object spray cans within a 1 metre radius from the air expulsion 9 According to EU Regulation...

Страница 5: ...board that is triggered in order to adjust the flow of refrigerant gas or to stop the unit in case of overtemperature 40 C outdoor air temperature sensor which transmits the de tected value to the el...

Страница 6: ...lve 15 Terminal board for electric connec tions 16 Electric panel cover 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 13 MODEL 35 1 Upper panel 2 Fan protection grille 3 Connections cover 4 Handle for handling...

Страница 7: ...xpansion valve 15 Terminal board for electric connec tions 16 Electric panel cover 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 MODEL 70 1 Upper panel 2 Fan protection grille 3 Connections cover 4 Handle fo...

Страница 8: ...ed air flow 3 40 4 20 6 00 8 10 kW Absorbed power at rated air flow 0 91 1 13 1 61 2 18 kW COP 3 71 kW kW Capacity at maximum air flow 4 60 5 40 6 90 10 00 kW Absorbed power at maximum air flow 1 50 1...

Страница 9: ...tics Power supply 230 1 50 V Ph Hz Compressor Compressor Rotary Type Oil FW50S Type Oil charge 0 32 0 27 0 35 0 52 l Refrigerant R32 Type Refrigerant charge 0 70 0 72 0 95 1 20 kg Fan Fan Axial Type Q...

Страница 10: ...ating it During the summertime the cycle is reversed and the thermal energy is extracted from the room air which is cooled and is delivered to the outdoor air A Outdoor unit B Indoor unit 1 Compressor...

Страница 11: ...nical Service in English Warranty Spare parts labels energy label etichetta gas refrigerante contact sheet It is also supplied as kit Condensate outlet hose 4 x vibration dampers screws to connect ref...

Страница 12: ...ch as it can be dangerous It must be disposed of ac cording to the regulations in force 2 6 Place of installation The location of R AARIA START devices must be determined by the system s designer or b...

Страница 13: ...llow for the condensate discharge 9 If the device is installed in an area that is subject to heavy snowfalls place the unit in a raised position so as to pre vent the air flow from being blocked or in...

Страница 14: ...1 2 Pollici Charge connection 1 2 Pollici Liquid line connection 6 35 mm Gas line connection 9 52 12 7 mm Charge connection 12 7 mm To access the cooling connections unscrew the fastening screw push d...

Страница 15: ...facing down remove the flare nut on the unit connection insert it into the connection pipe flare the tube A Pipe A mm inches mm 6 35 1 4 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 1 Key 2 Torque...

Страница 16: ...rvice it may be required to open and close the valves A Opening B Closing 1 Service connection blanking plug 2 On off valve shaft 3 Refrigerating pipe attachment 4 On off valve cover plug 5 Hex wrench...

Страница 17: ...ut off valves closed A High pressure B Low pressure 1 Pressure gauge unit 2 Vacuum pump 3 3 way valve service connection A B 1 2 3 connect the vacuum pump to the pressure gauge unit connect the pressu...

Страница 18: ...9 Carefully check for absence of leakages from the closing point of the plug 9 Do not force beyond the stop point to prevent damaging the shaft and causing leakage as a consequence 9 Once the check h...

Страница 19: ...sensor CS TC Defrosting sensor Outdoor air sensor HW Power supply 230V 1F 50Hz CN17 MODEL 35 1 N 3 C 2 L GR GR MODULE BOARD MAIN PCB BOARD BLOCK R W B C W S V R U COMPRESSOR M BL OR P U V W W B AC N A...

Страница 20: ...pressor sensor Defrosting sensor Outdoor air sensor TC CS HW 2 12 Electrical connection AARIA START It leaves the factory completely wired and only re quires a connection to the electrical power grid...

Страница 21: ...to connect to the terminal board For the sizing of the electrical power cables and safety devices use the following table Model 25 35 50 70 Electrical characteristics Power supply 230 1 50 V Ph Hz Pr...

Страница 22: ...and differential protection in stalled near the equipment connect the device to a properly functioning earthing sys tem make sure that the electrical power supply system is com pliant with the current...

Страница 23: ...of the above listed controls have problems turn the device off and call the Technical Service immediately 9 Do not touch the device pipes to prevent potential burns 9 Take anti static precautions in...

Страница 24: ...erations MUST be carried out under the fol lowing conditions cold device device NOT supplied with electric power suitable personal protection equipment 0 0 It is forbidden to open the access doors and...

Страница 25: ...scharge The unit resets automatically when the temperature drops under 110 C After 3 consecutive interventions in 30 minutes the unit resets after problem resolution 9 Fan motor malfunction After 3 co...

Страница 26: ...resets after problem resolution 24 Compressor motor overcurrent The unit resets automatically 25 Overcurrent protection for single phase of the compressor The unit resets after problem resolution In...

Страница 27: ...rials shall be disposed of separately so as to re cover and recycle them Refrigerant and oil must be recovered and not dispersed into the environment At the end of its ser vice life the device shall b...

Страница 28: ...39 0442 630111 fax 39 0442 630371 www riello it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment and accessories indicat...

Отзывы: