3350
18
GB
6.2
TROUBLE DURING OPERATION
Burner starts with an
ignition delay.
Ignition electrode is wrongly posi-
tioned.
Adjust properly as indicated herein.
Air output is too high.
Set the air output according to the
instructions of this manual.
Valve not open enough with insuffi-
cient gas allowed through.
Set correctly.
The burner does not
pass through the pre-
purging and locks out.
Flame is detected.
Valve defective: replace.
FAULTS
PROBABLE CAUSE
SUGGESTED REMEDY
B u r n e r l o c k s o u t
during operation.
Valve lets too little gas through.
Check supply grid pressure and/or ad-
just valve as indicated herein.
Valve is defective.
Replace.
Probe has ground fault.
Check right position and, if necessary,
adjust as indicated herein.
Clean or replace ionisation probe.
Flame disappears four times.
Check gas supply grid pressure and/or
adjust valve as indicated herein.
FAULTS
PROBABLE CAUSE
SUGGESTED REMEDY