32
INSTALLATION
Menu
Par.
No. Description
Range
Default setting
INSIEME EVOe 32
B/110 LN
UM
Ac-
cess
1000
1056 Total hours of operation in heating mode
h x 10
U
1000
1057 Total hours of operation in domestic mode
h x 10
U
1000
1058 Total hours of operation
h x 10
U
1000
1063 Input signal 0-10V
V
U
Heating general settings
2000
2001
Heating operating mode
0 = Operation with fixed setpoint and ambient ther-
mostat
1 = Operation with climatic curve and ambient ther-
mostat
2 = Continuous operation with climatic curve and
night reduction with ambient thermostat
3 = Continuous operation with fixed setpoint and
night reduction with ambient thermostat
4 = Operation with variable setpoint with input signal
0-10V
0…4
0
I
2000
2007 Switch-off hysteresis in heating mode
0…20
3
°C
I
2000
2008 Ignition hysteresis in heating mode
0…20
3
°C
I
2000
2005 Circulator post-circulating time in heating mode
10…900
120
sec
I
2000
2009
Burner restart time
It defines the stand-by time for a subsequent restart
after a switch-off, regardless of the delivery temper-
ature decrease. If it goes below the value set in Par.
2010 the thermal unit remains on.
10...900
180
sec
I
2000
2010
Temperature differential for burner restart
It defines the temperature difference below which
the burner restarts regardless of the elapsed time
indicated in Par. 2009.
0...20
16
°C
I
2000
2025 Minimum 0-10V input voltage in heating mode Par.
2001= 4
0...10
1
V
I
2000
2026 Maximum 0-10V input voltage in heating mode Par.
2001= 4
0...10
9
V
I
2000
2002
Configuration of the thermal module output
0 = 25 KW
1 = 32 KW
0...1
1
I
2000
2080
Anti-legionella function
0 = deactivated
1 = daily
2 = weekly
0...2
2
I
2000
2090
Venting function
0 = deactivated
1 = activated
0...1
1
I
2000
2096
Overtemperature protection
If the boiler temperature exceeds this value, the
burner turns off and the circulator continues its op-
eration to discharge the excessive heat.
85...95
85
°C
I
Direct Zone / Zone 1 Heating Settings
3000
3100
Use of Zone 1 control accessory
0 = NO
1 = Yes
If Zone 1 control accessory is used, AT and AP inputs
are not enabled. AT input is used only to enable the
night reduction on all the active zones (Par. 2001 = 2
and 3)
0…1
0
I
3000
3101
Zone 1 mode
0 = direct
1 = mixed
0…1
1
I
2000
2103
Direct Zone/Zone 1 setpoint in heating mode Par.
2001= 0 and 3
The thermal unit adjustment determines the boiler
setpoint in heating mode, using the highest value
among the requests of all the active zones (Par. 1101,
1201, 1301)
If Zone 1 is configured as mixed, the value set in pa-
rameter 1112 will be used as setpoint
If Zone 1 is not ena-
bled:
(Par. 2121, Par. 2024)
If Zone 1 is enabled:
BT: (Par. 2121, 45)
AT: (Par. 2121,Par. 2024)
70 (AT)
45 (BT)
°C
U