2508
1
TECHNICAL FEATURES
◆
The burner meets protection level of IP 40, EN 60529.
Thermal power – output
44 / 54 – 120 kW
–
3.7 / 4.5 – 10 kg/h
Fuel
Kerosene, min. viscosity at 20
°
C: 1.6
mm
2
/s
Gas oil, max. viscosity at 20
°
C: 6
mm
2
/s
Electrical supply
Single phase,
220 V
+
10%
–
15%
~
60Hz
Motor
Run current 1.1 A – 3300 rpm – 345 rad/s
Capacitor
2.5
m
F
Ignition transformer
Secondary 8 kV – 16 mA
Pump
Pressure: 7 – 15 bar
Absorbed electrical power
0.2 kW
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pressure regulator, 2
nd
stage
5 – Vacuum gauge connection
6 – Hydraulic jacks with air-damper
7 – Combustion head adjustment screw
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Regulation pressure, 1
st
stage
11 – Economizer
EQUIPMENT
Quantity
Description
2
1
2
1
1
1
1
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Hinge
Screw with two nuts for flange
7 pin plug
4 pin plug
S7349