MLM INTEGRATION WITH BMS
MCU 2 BACnet to BMS setup
The MCU 2 supports both BACnet/IP or BACnet ms/tp. Note MLM Tool V8.xx is required to bind the MCU 2 to
other devices in a BACnet installation.
The BACnet ms/tp MCU connects via a RS485 transceiver port to the ms/tp network, whereas BACnet /IP inter-
face to the Ethernet IP port on the MCU.
Please note the MCU ms/tp conforms electrically to the RS485 network specification as recommended by
ASHRAE. The RS485 port on MCU 2 is optically isolated. For the interconnection and shielding instructions, refer
to Addendum y of ANSI/ASHRAE Standard 135-2008.
A major advantage of BACnet/IP implementation is that the MLM Tool application can run simultaneously with
the BMS BACnet client on the same (PC) hardware platform. This greatly simplifies system commissioning and
diagnostics.
Bacnet/IP setup
To configure a MCU 2 into a BACnet/IP network, connect to the MCU web page by entering the MCU 2 IP ad-
dress into an Internet browser. The default IP address is 192.168.0.251. The following information will be dis-
played on the web page:
The Serial number and Software Version number - cannot be changed.
The Device Name can be changed by the user and usually identify the physical location of the MCU.
BACnet State indicates if the BACnet key has been activated, i.e. the BACnet/IP protocol is active on the
MCU.
The default unique BACnet device ID (instance) is derived from the Ethernet mac address. This parameter
can be changed by the user (edit and press save) to comply with the BMS requirements.
BACnet key entered to activate the BACnet protocol. This is a once-of setting normally activated during
manufacture. To convert a MCU 2 Standard device to BACnet a key value can be procured from the man-
ufacturer and entered into this field.
Note:
The BACnet ID and Device Name fields indicated are contained in the Object Identifier and Object Name
properties of the BACnet Device Object.
To change MCU IP addresses consult the Hardware/Master Comms Unit section in the MLM Tool Help
menu.
To revert to the default IP address (192.168.0.251) press and hold the BOOT button on the MCU until the
ST1 LED flashes. Release BOOT, press and release the DEF button. After a few seconds the CH1…4 LED’s
will flash to indicate a reset condition. The IP address is now set to default.