background image

©2021 RICHTECH INDUSTRIES       

1.800.677.7791       RICHTECHINDUSTRIES.COM

3

This system is designed to operate reliably with an 

SLA Deep Cycle Marine Battery (not included).
The use of an AGM battery is strongly recommended. 

The use of wet-cell batteries is strongly discouraged. 

Automotive batteries are not suitable for this 

application and will result in system failure.
WARNING: TO REDUCE THE RISK OF FIRE, 

ELECTRIC SHOCK OR INJURY: 
•  WEAR SAFETY GLASSES WHEN CONNECTING OR 

DISCONNECTING THE BATTERY.

•  KEEP SPARKS AND FLAMES AWAY FROM THE 

BATTERY.

•  KEEP METAL TOOLS FROM CONTACTING THE 

BATTERY POSTS AND CREATING A SHORT 

ACROSS THE TERMINALS. A SHORT CIRCUIT MAY 

CAUSE AN EXPLOSION.

•  FOLLOW ALL INSTRUCTIONS PUBLISHED BY THE 

BATTERY MANUFACTURER. FAILURE TO DO SO 

MAY RESULT IN PROPERTY DAMAGE, SERIOUS 

INJURY OR DEATH.

The Pitboss Battery Backup System displays system information on the 

Message Center. There are two types of messages: 

Informational

 and 

Alarms

Informational

 messages do not require immediate attention and do not 

sound an alarm. If more than one message is active, they rotate on the 

display.

Alarm

 messages require your immediate attention and will sound the 

unit’s audible alarm. If more than one alarm is active, they rotate on the 

display. Alarm messages take precedence over information messages, 

no informational messages are displayed when there is an active alarm.

The Pitboss Battery Backup System is an automatic 

system and will automatically operate during a power 

outage or when the primary sump pump fails to 

operate. The System automatically maintains and 

recharges the battery. 
The Pitboss Battery Backup System performs a full 

system test once per week. The system will cycle 

the backup pump and test the battery performance. 

If any issues are found during the self test, the 

appropriate alarm message will be displayed, and the 

audible alarm will be activated.

The Pitboss Battery Backup System features two 

push buttons on the controller.
The PUMP TEST button activates the backup pump. 

The pump will continue to run as long as the button 

is pressed. Do not run the backup pump in a dry 

sump pit for extended periods. 
The ALARM MUTE button will silence the audible 

alarm for 24 hours when pressed. It will also clear 

the alarm message from the LCD screen, so take 

note of the cause of the alarm. If the same alarm 

repeats during the 24 period, the audible alarm will 

not sound. If a different alarm is triggered during 

this period, the audible alarm will sound. Pressing 

the alarm mute button a second time will cancel the 

alarm mute.
To activate the weekly system test, press and hold 

the ALARM MUTE button. This will activate the full 

system test sequence.

INFORMATIONAL MESSAGES

System OK

Displayed when no messages 

active or after alarm muted.

System is working properly

Pump 

Running

Displays when the pump is on, 

showing in seconds the length 

of time the pump is on.

System is working properly

AC Power 

Failure

Displayed if AC power is lost.

Check that unit is plugged in. 

Check GFI/breaker for trip. 

 Normal during power loss.

ALARM MESSAGES

Reverse 

Polarity

Battery Red/Black leads are 

 connected  backwards.

Connect leads to correct terminals.

PWR OK/

Backup On

Backup pump is on while AC  

power is present.

Check primary sump pump  for 

proper operation. Replace  sump 

pump if necessary.

CHECK 

PUMP

Backup pump active but no 

 current draw is detected.

Check that pump cord is  firmly 

connected to controller  jack. Call 

for service.

Batt Low 

Voltage

Battery voltage drops below 

11.4 volts (50% discharged).

Check that unit is plugged in. Check 

GFI/breaker for trip. Normal during 

extended power loss.

Batt Crit 

Voltge

Battery voltage drops below 

10.4  volts (90% discharged).

Check that unit is plugged in. 

Check GFI/breaker for trip. Replace 

battery if power remains out.

Auto Test 

Failed

System fault detected 

during system self-test. 

Alarm message  will be 

displayed alternately.

Correct the issue in the  displayed 

alarm message.

Excessive 

Runtime

Backup pump has run more 

than  50 seconds.

Check that backup float sensor can 

move freely, not caught on wires. 

Normal during extremely heavy 

rains.

Check 

Fuse / Batt

Blown Fuse

Check that pump cord is firmly 

connected to controller jack.  Call 

for service.

Batt Not 

Detected

No battery is detected.

Check battery connections. Replace 

battery if necessary.

BATTERY INFORMATION

SYSTEM OPERATION

USING THE 

CONTROLLER BUTTONS

MESSAGES

Содержание PITBOSS SSBOS12

Страница 1: ...d as a long term replacement for a primary sump pump This unit must be installed with a working primary sump pump This complete kit includes a high performance DC sump pump solid state system controller float sensor and battery case SAVE THESE IMPORTANT SAFETY INSTRUCTIONS READ ALL INSTRUCTIONS CONTAINED IN THIS MANUAL BEFORE USING THIS PRODUCT Save these instructions for future reference Failure ...

Страница 2: ...me damaged or the connection falls into the sump pit NOT SUITED FOR POTABLE WATER APPLICATIONS WARNING Do not use this pump to transfer water that will be used for potable drinking water This pump is only to be used in applications for which it is designed WARNING Do not use to pump flammable or explosive liquids such as gasoline fuel oil kerosene etc WARNING Do not use in a flammable or explosive...

Страница 3: ... backup pump in a dry sump pit for extended periods The ALARM MUTE button will silence the audible alarm for 24 hours when pressed It will also clear the alarm message from the LCD screen so take note of the cause of the alarm If the same alarm repeats during the 24 period the audible alarm will not sound If a different alarm is triggered during this period the audible alarm will sound Pressing th...

Страница 4: ... of shipping will be paid one way This warranty does not cover products purchased from a party that is not an authorized retailer dealer or distributor of PitBoss Battery Backup System products OTHER IMPORTANT TERMS This warranty is not transferable and may not be assigned This warranty shall be governed and construed under the laws of the state of Ohio The warranty period will not be extended by ...

Отзывы: