ARTICULATED ARM OPENERS USER MANUAL

10

Antenna

3.

3

 Gate-moving Logic

(A) In gate-opening phase:  The gates stop if the transmitter/push button/key selector is activated, and close when

the transmitter/push button/key selector is reactivated.

(B) In gate-closing phase:  The gates stop if the transmitter/push button/key selector is activated, and open when

the transmitter/push button/key selector is reactivated.

(C) In gate-opening or gate-closing phase:  For safety purpose, the gates stop if encountering obstacles.

3.

4

 Checking the Gate Movement

1). Release the gear with the release key and move the gate to the middle so that it can move in both

     opening and closing directions; then lock the gear.

2). Operate the gate to opened and closed position several times, and make sure the gates reaches the limit   

     switch at least 2~3 centimeters before the mechanical stop.

LED2

L

LED4

L

LED3

L

LED Indicat

ion

ED2 D Key/S Ke

y

Key selector, or the push button is activated, LED2 will be on.

ED4 Ph

1

LED4 will be on when Ph1 are triggered.

ED3 Ph

2

LED3 will be on when Ph2 are triggered.

Antenna

Lit+

Lit- Lat+ Lat- M1+ M1- M2+ M2-

Lmt3 Lmt4

Lmt2

SKey

Ph1 PhVcc

Ph2 PhVcc

5V

S1

S2

ANT

GND

GND DKey

GND

GND

GND Lmt1

GND

J5

RF1

K3

K2

K1

J4

J3

J7

J8

CO

NC

NO

CO

-

+

-

+

CO

NO

NC

-

+

CO

NO

NC

NC

NO

CO

-

+

11111111            

 1

4

    

 

2

            

  

19   

19   

19   

19 

19

19     

19   

19 

LED2

LED4 LED3

33.

5

 

3.5

.1 Function Of The LED Display

LED Display         Programmable Functions

LED Display         Programmable Functions

When the gate is opening, the LED Display 

show ‘OPN’ for 2s and then change to Amp 

current indication 

When the gate is stopped, the LED Display show 

‘STP’ until next commend has been made, after 

10s no further movement, the LED turns to OFF

When the gate is closing, the LED Display show 

‘CLS’ for 2s and then change to Amp current 

indication 

LED display shows “S01” means the panel did not 

detected the M1+/M1 and M2+/M2 both been 

connected before the system learning procedure, 

check for motor wire connection, for dual gate 

system

The memory of the system is all deleted/cleaned 

by press and hold the UP + SET+ DOWN button 

together for 5s and the panel will be back to 

default settings

LED display shows “S02” means the panel did not 

detected the M1+/M1 but detected M2+/M2 been 

connected, notice the installer to check the motor 

wire connection, if this is single gate system, 

motor wire should connect to M1+/M1 not on 

M2+/M2

LED display show “S03” means same button on 

the remote has been identified for more than 2 

functions

[LEA] means motor into the system learning 

mode, do not interrupt during this procedure.

[D-G] means motor completed the learning 

procedure for dual gate installation

.

[S-G] means motor completed the learning 

procedure for single gate installation

.

[N-L] means system learning failed.

3

            

5

    

6

    

7

    

8

    

9

    

10

    

11

    

12

    

13

    

14

    

15

    

16

    

17

    

18

    

20

    

2

1

    

2

2

    

2

3

    

2

4

    

2

5

    

2

6

    

Содержание GTR502

Страница 1: ...GTR502 GTR503 ARTICULATED ARM OPENERS 24V DC MOTOR FOR RESIDENTIAL USER MANUAL Software Version PS21068B...

Страница 2: ...ly by turning off the magneto thermic switch connected upstream and apply the hazard area notice required by applicable regulations 3 Make sure the existing structure is up to standard in terms of str...

Страница 3: ...that the gate moves smoothly and that 1 Hinges are properly positioned and greased 2 No any obstacle in the moving area 3 No frictions between two leaf gates and on the ground while moving 4 Installat...

Страница 4: ...surface of the brackets to be installed is smooth vertical and rigid 3 Arrange the cables for power supply cable of the motors make sure power supply cable is connected to motor 4 Motor installation a...

Страница 5: ...6 1 Adjust the gate to full opened position and after the position decided fixe with corresponding mechanical stopper 6 2 Adjust the gate to full opened position and after the position decided make t...

Страница 6: ...ver and transmitter should be properly aligned 4 Power up the photocells and make sure the LED light on receiver and transmitter are ON Step 1 Step 2 Step 3 Step 4 Detection Method Sensing Range Input...

Страница 7: ...2 UP SET SET DOWN RF LEARN RF LEARN LED2 LED4 LED3 11 2 M 2 M 1 M 1 M t a L t a L t i L t i L D N G 4 t m L 3 t m L D N G 2 t m L 1 t m L D N G 2 S 1 S V 5 GND Ph1 Ph2 PhVcc PhVcc y e K S y e K D D N...

Страница 8: ...Limit switch ANT GND PC190 PCB1 40121 377 A1 T4 SW3 UP J1 Q17 R113 R112 R111 R110 R108 R107 R106 R105 R104 R103 R102 J5 SW1 RF LEARN RF1 MOV1 K5 K3 K2 K1 J4 J3 J7 J2 F1 DB1 J8 SW4 SET SW5 DOWN NC NO...

Страница 9: ...2 K1 J4 J3 J7 J2 F1 DB1 J8 SW4 SET SW5 DOWN NC NO CO NC NO CO CO NO NC CO NO NC NC NO CO LED2 LED3 LED4 M1 Limit1 Limit2 GND M1 Motor1 Power Limit Switch Antenna ANT GND RF J7 NC NO CO CO NO NC CO NO...

Страница 10: ...out any new remote learn then the LED will be off The transmitter learning is completed Antenna figure 1 figure 1 RF Learn New Remote Press any desired button UP A B SET DOWN RF LEARN 3 Sec RF LEARN S...

Страница 11: ...eck the parameter setting of F1 Dual Single before going into system learning Restore system default setting Press and Hold the UP DOWN button for 5 secs and panel restores back to default setting Not...

Страница 12: ...19 19 19 19 19 LED2 LED4 LED3 3 3 5 3 5 1 Function Of The LED Display LED Display Programmable Functions LED Display Programmable Functions When the gate is opening the LED Display show OPN for 2s an...

Страница 13: ...Gate Closing Motor Speed for Opening F1 F3 F4 F5 F11 F22 F23 F31 F32 F33 F34 F41 F42 F43 F44 F51 F52 F F5 54 4 Over current Default Limit Switch Hall Sensor 2A 3A 4A Default 5A 2A 3A 4A Default 5A 50...

Страница 14: ...peed 40 of full speed Default 50 of full speed 1 The factory setting is F83 Deceleration Point for Opening F91 F92 F93 F94 F9 F95 75 of full distance 80 of full distance 85 of full distance Default 90...

Страница 15: ...h for 3 seconds before the gate operates If set OFF the flash light will operate with motor at the same time 2 The factory setting is FG0 1 The factory setting is FH0 1 The factory setting is FI0 1 Th...

Страница 16: ...NO met Table FW Over current Sensitivity Setting F Para W1 FW2 FW3 FW4 1 The factory setting Description is FW5 FW5 FW6 FW9 F FW7 W7 FW8 FWA er 0 1 sec 0 3 sec 0 2 sec 0 4 sec 0 6 sec 0 5 sec Default...

Страница 17: ...ime Open No effect Reload automatic closing time PH2 Photocell CLOSE Open Open Open No effect Position of Gate When safety devices are activated FE4 Double photocell set up Type of Safety Device FULLY...

Страница 18: ...old Separately 433 92MHz 200 transmitters memory Built in PCBA 20o C 50o C 275mm x 195mm x 102mm Conduct the following operations at least every 6 months If you are a high intensity user please shorte...

Страница 19: ...551 2233 Richmond Wheel Castor Co declines all responsibility for any consequences resulting from improper use of the product or use which is different from the expected and specified in the present d...

Страница 20: ...at safety Durability Solid material apply with lasting usage Silence Worm gear application give silence operation Manual release device with easy use and highly protection Key Release EZ Instal Easy i...