VOLTAGE RANGE
NOTE: USING AN INCORRECT VOLTAGE SETTING COULD LEAD TO THE
DOOR OPERATING AT AN UNSAFE SPEED.
This operator is designed to work with
SINGLE PHASE
voltages from 110-240Vac (for 3
phase voltage, use optional external transformer). There are 2 available settings, 110-130V
or 208-240V, and proper selection for your installation
MUST
to be made prior to operation.
Failure to do so could result in damage to the operator and door. To access this option,
toggle between menu options using the OPEN or CLOSE buttons until VOLTAGE SETUP
appears on the screen. Then press the STOP button to select. Press OPEN or CLOSE to
toggle between Voltage Selections. Press STOP to Save and return to the QUICKSTART
MENU.
MOTOR POSITION
NOTE: NOT SETTING THE CORRECT MOTOR POSITION WILL RESULT IN
THE DOOR NOT CLOSING PROPERLY.
Factory default is LEFT SIDE. If the Operator is installed on the RIGHT SIDE, push the
STOP button to enter this menu setting, then toggle with the OPEN or CLOSE button to
change to RIGHT SIDE. To save your selection and exit to the QUICKSTART MENU options,
press the STOP button.
DOOR LIMITS
NOTE: PROGRAMMING OF LIMITS SHOULD BE PERFORMED BY
TRAINED PERSONNEL ONLY. THE ENCODER WILL RETAIN THESE
LIMITS UNTIL RE-PROGRAMMED.
Press the STOP button to set the limits. Once selected, DOOR LIMITS heading will appear
with a prompt to ‘Push OPEN to Start'. Push the OPEN button, and the door will open to the
fully open position against the Limit Brackets. ENSURE THAT THE TOP ROLLERS OF THE
DOOR ARE RESTING AGAINST THE LIMIT BRACKETS. The Open Limit now needs to be
set.
SET OPEN LIMIT
Press CLOSE (OPEN functional should you overshoot desired position) to jog the door to
the desired Open Limit height.
The Open Limit Setting Should be a minimum offset of
3" from the Limit Bracket or Open Limit Switch
. Press STOP button to save Open Limit
and advance to SET CLOSE LIMIT.
SET CLOSE LIMIT
From the Open Limit, jog to the desired Close position, using the CLOSE button (OPEN
available for fine tuning). Ensure that the door is properly sealed at the bottom.
Press STOP button to save and return to QUICKSTART MENU.
SETTING DOOR SPEEDS
On initial set up please use the factory default MEDIUM speed. As noted below the Motor, Door and Drum
size may affect the opening speed of the door and the Medium setting may be all that is required to achieve
24” per second opening speed
Please note that the Dyna-Hoist has been developed with the same technology that is used in High Speed Door Operators. While we
have limited the maximum opening speed to ~24” per second for sectional doors (this is dependent on the type of door and drum used)
and maximum closing speed to ~16” per second, we recommend that you set the speed to accommodate both your requirement, and
the hardware of the door. To get the longest life out of your door, and to maximize your allowable speed, we recommend Stainless Steel
cables and nylon rollers be installed if they are not already standard on your door.