18
Remote I/O Installation and Programming Manual
4.2
Set Setpoint Values
The Set Setpoint Values block write command is used to write setpoint information to the indicator. Table 4-4
shows the format of the command:
Table 4-4. Block Write Command 2: Set Setpoint Values
Command Number
Specifies the Set Setpoint Values command number, 2.
Setpoint Number
Specifies the setpoint number being configured. Valid values are 1 through 8, decimal.
Setpoint Kind
Specifies the kind of setpoint being configured. Table 4-5 shows the kinds of setpoints that can be specified on
this parameter:
Word
Bit Number
Word Contents
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
Command Number (2)
1
0
0
0
0
0
0
0
0
0
0
0
0
n3
n2
n1
n0
Setpoint Number (1–8)
2
0
0
0
0
0
0
0
0
0
0
0
k4
k3
k2
k1
k0
Setpoint Kind (0–18)
3
v31
Setpoint Value
v16
Setpoint Value (MSW)
4
v15
v00
Setpoint Value (LSW)
5
b31
Band Value
b16
Band Value (MSW)
6
b15
b00
Band Value (LSW)
7
h31
Hysteresis Value
h16
Hysteresis Value (MSW)
8
h15
h00
Hysteresis Value (LSW)
9
p31
Preact Value
p16
Preact Value (MSW)
10
p15
p00
Preact Value (LSW)
Value
Kind
Description
0
OFF
Setpoint turned off/ignored.
1
GROSSSP
Gross setpoint. Trips when the current gross weight matches this value.
2
NETSP
Net setpoint. Trips when the current net weight matches this value.
4
–RELSP
Negative relative setpoint. Trips at a specific value below the referenced setpoint.
6
PAUSE
Pauses the batch sequence indefinitely. Operator must activate the START digital input to continue
processing.
7
DELAY
Delays the batch sequence for a specified time. The length of the delay (in tenths of a second) is
specified on the Value parameter.
8
WAITSS
Wait for standstill. Pauses the batch sequence until the scale is at standstill.
17
TIMER
Tracks the progress of a batch sequence based on a timer.
The timer value, specified in tenths of a second on the Value parameter, determines the length of time
allowed between start and end setpoints. The indicator Start and End parameters are used to specify the
start and end setpoints. If the End setpoint is not reached before the timer expires, the digital output
associated with this setpoint is activated.
Table 4-5. Setpoint Kind Values
DISCONTINUED