Pedestrian  Automatic  Closing  time  is  stored  (see  DIP3  function  to  enable  or 
disable the Automatic Closing feature).

7 - Turn  

DIP1 to Off

 position

8 - Turn  

DIP2 to Off

 position

f

UNCTIONING Of CONTrOL ACCEssOrIEs

ATTENTION: ONLY IMPULsIVE COMMANDs HAVE TO BE CONNECTED.
Make  sure  that  any  other  type  of  command  accessories  (e.g.  mass  detectors) 
used on the installation are set in the IMPULsIVE mode, otherwise, the gate will be 
operated even without the protection of the safety devices.

sTEP BY sTEP or AUTOMATIC commands (K BUTT, PED.Button)
DIP5 - ON

   The  K  BUTT  and  PED.Button  perform  the  step  by  step  cyclic 

command open-stop-close-open-stop-etc.

DIP5 - Off

  The K BUTT and PED.Button perform the automatic command:

 

- the open command, if pressed with the gate completely closed

 

- the close command, if pressed with the gate completely opened

 

- no effect, if pressed during the gate opening  

 

- the gate re-open, if pressed while the gate is closing

The K BUTT opens the gate completely, whereas the PED.Button opens the gate 
partially as described in Point E.

sTEP BY sTEP or AUTOMATIC commands (radio command)
DIP4 - ON

 

 The RADIO COMMAND perform the step by step cyclic command 
open-stop-close-open-stop-etc.

DIP4 - Off

   The RADIO COMMAND perform the automatic command:

 

- the open command, if pressed with the gate completely closed

 

- the close command, if pressed with the gate completely opened

 

- no effect, if pressed during the gate opening  

 

- the gate re-open, if pressed while the gate is closing

OPEN BUTTON (COM-OPEN)

The button controls the opening movement when the gate is stationary. If activated 
while closing, it reopens the gate.

CLOCK fUNCTION

If you want the Clock function must request s1 with firmware 03.
ATTENTION: A CLOCK CONNECTED TO s1 with fw 04 or more ACTIVATEs 
THE  OPENING  MOVEMENT  Of  THE  GATE  WITHOUT  HAVING  THE 
PrOTECTION Of THE sAfETY DEVICEs!

The  Clock  Function  permits  to  keep  the  gate  opened  even  if,  for  example,  the 
Automatic Closing is enabled (DIP3 ON) or somebody commands the gate closing. 
It  is  useful  during  rush  hours,  when  traffic  is  heavy  and  the  flow  is  slow  (e.g. 
entrance/exit  of  employees,  emergencies  in  residential  areas  or  car  parks  and, 
temporarily, for removal vans) and it’s necessary to keep the gate opened.

CLOCK fUNCTION APPLICATION
It is necessary to request a s1 control panel with firmware 03.

It can be done by connecting a switch and/or a daily/weekly clock either in parallel 
to  the  OPEN  button  or  instead  of  the  OPEN  button.  When  the  control  board 
receives this command, the gate will open and by keeping this contact closed for all 
the time of the gate opening, the Clock Function is automatically activated. In fact, 
once reached the open position, the gate will remain opened and all of the control 
board  functions  are  blocked.  Only  when  OPEN  contact  is  released,  the  control 
board functions are re-activated and the gate will close immediately.

PEDEsTrIAN command (PED.Button - COM)

This  command  is  useful  to  open  the  gate  partially,  just  enough,  for  example,  to 
permit a pedestrian crossing, see Point E procedure.
From  the  Pedestrian  opening  position  the  Automatic  Closing  can  be  enabled 
or  disabled  with  DIP3.  From  the  Pedestrian  opening  position,  the  gate  can  be 
completely opened by the OPEN or by the K BUTT button or by the RADIO button.

AUTOMATIC CLOsING (from the COMPLETE open position)

The  Automatic  Closing  from  the  complete  open  position  can  be  enabled  turning 
ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).

AUTOMATIC CLOsING (from the PEDEsTrIAN open position)

The Automatic Closing from the pedestrian open position can be enabled turning 
ON  the  DIP3.  The  maximum  gap  of  time  that  can  be  programmed  is  5  minutes 
(see Point E).

f

UNCTIONING Of sAfETY ACCEssOrIEs

PHOTOCELL  (PHOT - COM)

In case the switch DIP6 is in the OFF position, the photocells are active both in 
gate  opening  and  in  gate  closing.  In  this  configuration,  if  an  obstacle  cuts  the 
photocell beam:
  - while the gate is closing, the gate will open
  -  while the gate is opening, the gate will stop and will restart opening when the 

obstacle is removed

  -  while the gate is still, it will not move neither in opening nor in closing
In case of the switch DIP6 is in the ON position, the photocells are active only in 
gate closing. 
In this configuration, if an obstacle cuts the photocell beam:
  - while the gate is closing, the gate will open
  - while the gate is opening, the gate will continue open
  -  while the gate is still, it will open if a open command is request, it will remain 

still if a close command is request.

The photocell input (PHOT - COM) is a NORMALLY CLOSED contact. 
In  case  there  are  more  couple  of  photocells,  the  contacts  from  all  the  photocell 
receivers could be connected in series.
In case the photocells are not installed, this contact must be short circuited with a 
wire jump (from PHOT to COM) to permit the gate to operate.

AUTOMATIC CLOsING after the transit through the photocell (DIP17 ON)

This option could be useful to close automatically the gate when the vehicle left and 
disengaged the photocell beam. If the DIP17 is turned ON, this function is activated 
and the PHOTO input will have two purposes:
-  detect the obstacle and prevent the gate movement in according with the DIP6 

position

-  close the gate as soon as the vehicle leaves the photocell beam

If DIP17 ON and DIP6 Off 

 

 If  the  gate  is  opening  and  a  vehicle  crosses  the  photo  beam,  the  gate  will 
stop. When the vehicle leaves,  the gate will close automatically after 1second 
pause.

If DIP17 ON and DIP6 ON 

 

 If  the  gate  is  opening  and  a  vehicle  crosses  the  photo  beam,  the  gate  will 
continue to open. When the vehicle leaves, the gate will stop and then closes 
automatically after 1second pause.

If the complete gate open position is reached before the vehicle leaving, the DIP17 
will be ignored and the automatic closing will be managed in according to the DIP3 
position.

PAY ATTENTION:  it is highly recommended to check photocells operation at 

least every 6 months.

sAfETY sTrIP (EDGE - COM)

If an obstacle presses the safety strip:
 

- while the gate is still, it will not move neither in opening nor in closing

 

- while the gate is closing, the gate will open

 

- while the gate is opening, the gate will close

In case the safety strip is held pressed a further quick reversion, after 2seconds, is 
performed. The gate interrupts any movement and this 

alarm state

 will be signalled 

by the Blinker for 1 minute. The normal gate operations can be restored by pressing 
any push button or radio commands. 
If  after  the  first  safety  strip  obstacle  detection,  the  safety  strip  is  released  and 
then engaged again before the end of the gate travelling, the gate interrupts any 
movement and this 

alarm state

 will be signalled by the Blinker for 1 minute. The 

normal  gate  operations  can  be  restored  by  pressing  any  push  button  or  radio 
commands. 
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact. 
In case there are more than one safety strip, all their contacts could be connected 
in series.

In case the safety strip is not installed, this contact must be short circuited 
with a wire jump (from EDGE to COM) to permit the gate to operate.
PAY ATTENTION:

 

it is highly recommended to check safety-strips operation 

at least every 6 months.

TEsTING THE sAfETY sTrIP equipment (DIP12 ON)

The DIP12 ON enables the Test of safety strip equipment. The Test is performed 
every time the gate completes a full opening. It is suitable only if the safety strip 
device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input has to be connected to the 
A+TEST and A- outputs (DIP12 ON). Automatically, every time the gate completes 
a full opening, just before closing, the control board switches OFF the A+TEST and 
A- power supply output for a very short time. While the safety strip power supply is 
switched OFF, if everything is working fine the safety strip contact (EDGE - COM) 
must open. In case the test fails, no other gate manoeuvre will be allowed and the 
alarm state will be signalled by the Blinker that will remain on. 

Содержание S1

Страница 1: ... di chiusura Non applicare K800 FAST su parti mobili che chiudono a ridosso della colonna K800 FAST ne peut être appliqué qu aux parties mobiles qui glissent à côté de la colonne de fermeture Ne pas appliquer K800 FAST sur les parties mobiles qui ferment près de la colonne Fast operators are not suitable for installations in which the mobile gate leaf ends up against a post a U shape bar because t...

Страница 2: ...INSTRUCTIONS 1 Si la centrale électrique ne dispose d aucun interrupteur il faut en installer un de type magnétothermique en amont de cette dernière omnipolaire avec ouverture minimale des contacts correspondant à 3mm la marque de cet interrupteur devra être en conformité avec les normes internationales Ce dispositif doit être protégé contre toute remise en fonction accidentelle ex en l installant...

Страница 3: ...HE SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltzentrale ein thermomagnetischer Schalter installiert werden omnipolar mit einer minimalen Kontaktöffnung von 3 mm der ein von den internationalen Normen anerkanntes Konformitätszeichen besitzt Solch ei...

Страница 4: ...el sistema respetando las normas y las leyes vigentes SEGUIR TODAS LAS INSTRUCCIONES DE INSTALACIÓN 1 Este manual de instrucciones está exclusivamente dirigido a personal especializado que conozca los criterios de construcción y de los dispositivos de protección contra accidentes con cancelas puertas y portales motorizados atenerse a las normas y a las leyes vigentes 2 El instalador tendrá que dar...

Страница 5: ... un efficace chiusura Il motore è protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento I Misure in mm 1 800 24 700 4 230V 50Hz 220V 60Hz 408 590 2 08 3 2 25 13 32s 2s 9 32s 2s 400 70 21 10m COMLUBE LHITGREASE EP GR 2 12 3 70 10 55 44 K800 FAST CARATTERISTICHE TECNICHE Peso max cancello Coppia max Forza di spinta a giri costanti Cremagliera modulo...

Страница 6: ...i fermi meccanici al di sopra del cancello perché non sono sufficientemente sicuri SBLOCCO Da effettuare dopo aver tolto l alimentazione elettrica al motore Per poter agire manualmente sul cancello è sufficiente inserire l apposita chiave e ruotarla 3 volte in senso antiorario Fig 4 Per poter eseguire in modo sicuro la movimentazione manuale dell anta occorre verificare che sull anta siano present...

Страница 7: ...izionare due camme alle estremità della cremagliera Fig 7 La regolazione della corsa di apertura e chiusura si ottiene spostando le medesime sui denti della cremagliera Per bloccare le camme alla cremagliera avvitare a fondo le viti in dotazione N B Oltre alle camme di fermo elettrico sopraesposte è obbligatoria l installazione di fermi meccanici robusti che non permettono la fuori uscita del canc...

Страница 8: ...COMUNE M LAMPEGGIATORE 230Vac 40W ALIMENTAZIONE 230Vac 50 Hz ANTENNA CALZA ANTENNA FINECORSA APERTURA FINECORSA CHIUSURA COMUNE FOTOCELLULE PEDONALE APRE STOP CHIUDE PASSO PASSO 24Vdc 0 4A 15 LED R 2 2K 1 4W ENCODER COMUNE COSTE S1 cod BC07096 ...

Страница 9: ...ERTO 24VDC COMUNE DEI CONTATTI CONTATTO COSTE IN APERTURA E CHIUSURA ANTENNA RADIO COMUNE DEI CONTATTI CONTATTO FOTOCELLULE CONNETTORE PER COLLEGAMENTO SONDA RISCALDATORE Cod ACG4665 CONNETTORE PER COLLEGAMENTO ENCODER SOLO PER K PLUS CONNETTORE PER RADIO RICEVITORE ESTERNO 24VDC PULSANTE PER LA PROGRAMMAZIONE REGOLATORE ELETTRONICO DELLA VELOCITÀ LENTA IN ACCOSTAMENTO CON DIP 7 ON REGOLATORE ELET...

Страница 10: ...TORI FAST SEMPRE ATTIVO Se DIP 10 è su ON è attivo un freno HARD Se DIP 10 è su OFF è attivo un freno SOFT Al raggiungimento della totale apertura o chiusura verrà eseguita una frenata per evitare l inerzia che danneggerebbe l ingranaggeria in caso di impatto sui fermi meccanici PARTENZA GRADUALE Se DIP 11 è su ON si abilita ad ogni avvio un movimento graduale per 1 secondo Questa funzione non è a...

Страница 11: ...sono attivabili o disattivabili tramite DIP3 ON attivo FUNZIONAMENTO DOPO BLACK OUT Al momento del black out lo stato del cancello viene salvato in memoria Al ritorno della tensione di rete premete il pulsante di apertura K apre o radio Il cancello si aprirà Lasciate che il cancello si chiuda da solo con la chiusura automatica oppure date un comando di chiusura Questa operazione consentirà al canc...

Страница 12: ...3W o 5 led con resistenza in serie da 2 2 kΩ Carico massimo all uscita lampeggiatore 40W con carico resistivo Corrente disponibile per fotocellule e accessori 400mA 24Vdc Corrente disponibile su connettore radio 200mA 24Vdc Tutti gli ingressi devono essere utilizzati come contatti puliti perchè l alimentazione è generata internamente tensione sicura alla scheda ed è disposta in modo da garantire i...

Страница 13: ...RE SPARK con scheda intermittente incorporata cod ACG7059 SUPPORTO LATERALE cod ACG7042 ANTENNA SPARK 433 cod ACG5452 PROBE Sonda di rilevamento temperatura ambiente motore per riscaldamento dello stesso in climi particolarmente freddi fino a 30 C collegare a connettore J6 cod ACG4665 BLOCK SELETTORE A CHIAVE DA PARETE cod ACG1053 SELETTORE A CHIAVE DA INCASSO cod ACG1048 FIT SYNCRO FOTOCELLULE FI...

Страница 14: ... congiuntamente ad un quadro elettronico RIB è un dispositivo di protezione di Classe 2 cod ACG6202 DISPOSITIVI Wi Fi NOVA Wi Fi FOTOCELLULE SENZA FILI cod ACG8037 COPPIA COLONNINE NOVA cod ACG8039 SPARK Wi Fi LAMPEGGIATORE SENZA FILI cod ACG7064 SUPPORTO LATERALE cod ACG7042 BLOCK Wi Fi SELETTORE A CHIAVE SENZA FILI cod ACG6098 MASTER Wi Fi SCHEDA DI GESTIONE SISTEMA SENZA FILI con innesto 12 30V...

Страница 15: ...dule 4 4 Sélecteur à clé 5 Antenne radio 6 Feu clignotant 7 Limiteurs de course cames 8 Photocellules intérieures 9 Potelets de support pour photocellules 10 Arrêts mécaniques 1 Mesures en mm 800 24 700 4 230V 50Hz 220V 60Hz 408 590 2 08 3 2 25 13 32s 2s 9 32s 2s 400 70 21 10m COMLUBE LHITGREASE EP GR 2 12 3 70 10 55 44 K800 FAST CARACTERISTIQUES TECHNIQUES Poids maxi du portail Couple maxi Force ...

Страница 16: ...n arrêt mécanique au dessus du portail étant donné que les arrêts mécaniques ne sont pas suffisamment sûrs DÉBLOCAGE Cette opération ne devra être effectuée qu après avoir mis le moteur hors tension Afin de pouvoir agir manuellement sur le portail il suffit d introduire la clé destinée à cet effet et de la faire tourner 3 fois dans le sens contraire à celui des aiguilles d une montre fig 4 Afin de...

Страница 17: ...Fig 7 Pour procéder au réglage de la course d ouverture et de fermeture il suffit de déplacer les cames sur les crans de la crémaillère Pour bloquer les cames sur la crémaillère visser à fond les vis fournies avec l équipement N B En plus des cames d arrêt électrique susmentionnées il est indispensable d installer des arrêts mécaniques solides qui empêcheront le portail de sortir des glissières su...

Страница 18: ... OUVRE COMMUN M FEU CLIGNOTANT 230Vac 40W ALIMENTATION 230Vac 50 Hz FIN DE COURSE OUVERTURE FIN DE COURSE FERMETURE PIETON OUVRE STOP FERME PAS A PAS 24Vdc 0 4A 15 LED R 2 2K 1 4W COMMUN BARRE PALPEUSE ANTENNE ENVELOPPE ANTENNE COMMUN PHOTOCELLULES ENCODER ...

Страница 19: ...UVERT 24 VCC COMMUN DES CONTACTS CONTACT BARRES PALPEUSES EN OUVERTURE ET FERMETURE ANTENNE RADIO COMMUN DES CONTACTS CONTACT PHOTOCELLULES CONNECTEUR POUR CONNEXION SONDE CHAUFFANTE Code ACG4665 CONNECTEUR POUR CONNEXION ENCODEUR SEULEMENT POUR K PLUS CONNECTEUR POUR RADIO RÉCEPTEUR EXTÉRIEUR 24 VCC BOUTON POUSSOIR POUR LA PROGRAMMATION RÉGULATEUR ÉLECTRONIQUE DE LA VITESSE LENTE EN APPROCHE AVEC...

Страница 20: ... de programmation de la durée et est activé à environ 50 à 60 cm avant d atteindre le fin de course d ouverture ou de fermeture FREIN ÉLECTRONIQUE AVEC MOTEURS FAST TOUJOURS ACTIVÉS Si DIP 10 est sur ON un frein HARD est activé Si DIP 10 est sur OFF un frein SOFT est activé Lorsque l ouverture ou la fermeture totale est atteinte un freinage sera effectué pour éviter l inertie qui endommagerait l e...

Страница 21: ...t le mouvement d ouverture il n a pas d effet S il est actionné quand le portail est ouvert il le ferme S il est actionné durant le mouvement de fermeture il le fait s ouvrir de nouveau FERMETURE AUTOMATIQUE AVEC OUVERTURE TOTALE OU POUR PIÉTONS Les temps de pause avant d avoir la fermeture automatique en ouverture totale ou pour piétons du portail sont enregistrés durant la programmation des laps...

Страница 22: ...STIQUES TECHNIQUES Humidité 95 sans condensation Tension d alimentation 230 ou 120V 10 Fréquence 50 60 Hz Absorption maximale de la carte 30 mA Microinterruptions de réseau 100 ms Puissance maximale du voyant portail ouvert 3 W équivalent à 1 ampoule de 3W ou 5 voyant DEL avec résistance en série de 2 2 kΩ Charge maximale à la sortie clignotant 40W avec charge résistive Courant disponible pour pho...

Страница 23: ...suscités il est indispensable d installer une antenne accordée sur la fréquence du radiorécepteur installé N B Veiller à ce que le fil central du câble n entre pas en contact avec l enveloppe extérieure en cuivre dans le cas contraire le fonctionnement de l antenne serait nul L antenne doit être installée de façon perpendiculaire et être en vue de la télécommande FEU CLIGNOTANT SPARK avec carte in...

Страница 24: ...FILS code ACG7064 SUPPORT LATERAL code ACG7042 BLOCK Wi Fi SÉLECTEUR À CLÉ SANS FILS code ACG6098 TRANSMETTEUR RADIO RED pour barre palpeuse mécanique ou électrique à alimenter par 3 piles de type AA de 1 5V non comprise RED permet la réalisation d une installation avec barres palpeuses fixées également sur le battant en mouvement sans l adoption de systèmes d assemblage de câbles Il est conforme ...

Страница 25: ...ells 3 Rack of Module 4 4 Key selector 5 Radio antenna 6 Blinker 7 Travel limiting devices cams 8 Internal Photocells 9 Photocell posts 10 Mechanical stops 1 800 24 700 4 230V 50Hz 220V 60Hz 408 590 2 08 3 2 25 13 32s 2s 9 32s 2s 400 70 21 10m COMLUBE LHITGREASE EP GR 2 12 3 70 10 55 44 K800 FAST TECHNICAL DATA Max gate weight Max torque Thrust force to constant turns Rack module Power supply Moto...

Страница 26: ...e these mechanical stops are not safe enough RELEASE To operated after the power supply to the motor has been interrupted In order to work manually on the gate you just need to insert the fitting key and rotate it 3 times counterclockwise fig 4 In order to carry out the manual operation of the gate leaf the followings must be checked That the gate is endowed with appropriate handles That these app...

Страница 27: ...ck Fig 7 Move the cams on the rack teeth to adjust their opening and closing travel To fix the cams to the rack tighten the screws issued N B In addition to the electric stop cams mentioned above you must also install strong mechanical stops preventing the gate from sliding out of the top guides MAINTENANCE To be carried out exclusively by skilled persons after the power supply to the motor has be...

Страница 28: ...OR CAPACITOR M BLINKER 230Vac 40W POWER SUPPLY 230Vac 50 Hz LIMIT SWITCH OPEN LIMIT SWITCH CLOSE PEDESTRIAN OPEN STOP CLOSE STEP BY STEP 24Vdc 0 4A 15 LED R 2 2K 1 4W COMMON SAFETY STRIP ANTENNA ANTENNA BRAIDING COMMON PHOTOCELLS ENCODER S1 code BC07096 ...

Страница 29: ...all the command and safety inputs SAFETY STRIP CONTACT NC RADIO ANTENNA COMMON CONTACT common line for all the command and safety inputs PHOTOCELLS CONTACT NC Temperature sensor cable connection PROBE Code ACG4665 optional ENCODER connection K PLUS operators CONNECTOR FOR EXTERNAL RADIO RECEIVER 24Vdc PROGRAMMING BUTTON ELECTRONIC REGULATOR FOR LOW SPEED ON APPROACH ELECTRONIC TORQUE REGULATOR DO ...

Страница 30: ...nd for further future controls 1 Unlock the operator with the Manual Release slide the leaf open about halfway and lock the operator again 2 Turn DIP1 to ON position LED DL1 starts blinking 3 Press and hold the PROG Button the gate will open or close Release the button and the gate will stop Press and hold again the gate will move in the opposite direction The S1 control board has two movement led...

Страница 31: ...ts the photocell beam while the gate is closing the gate will open while the gate is opening the gate will stop and will restart opening when the obstacle is removed while the gate is still it will not move neither in opening nor in closing In case of the switch DIP6 is in the ON position the photocells are active only in gate closing In this configuration if an obstacle cuts the photocell beam wh...

Страница 32: ... s a cable ended with a sensor to detect the motor temperature and if necessary to active automatically the motor warming code ACG4665 TECHNICAL SPECIFICATIONS Humidity 95 without condensation Power voltage 230V 10 120V 60Hz upon request Frequency 50 60Hz Maximum board absorption 30mA Interruptions in electricity supply 100ms Maximum load of open gate output 3 W equal to 1 3W bulb or to 5 LEDs con...

Страница 33: ...MODULE 4 with zinc plated angle Iron in 2 m bars Ideal for gates up to 1 000 kg 2 200 lbs weight code ACS9050 PLATE TO BE CEMENTED code ACG8107 BLOCK BLOCK KEY SELECTOR FOR WALL INSTALLATION code ACG1053 BLOCK KEY SELECTOR TO BUILA IN code ACG1048 FIT SYNCRO FIT SYNCRO PHOTOCELLS for the wall installation code ACG8026 The range you can set is 10 20 m 30 60ft You can fit many couples close together...

Страница 34: ...T WIRES code ACG3016 SPARK Wi Fi BLINKER WITHOUT WIRES code ACG7064 LATERAL SUPPORT code ACG7042 BLOCK Wi Fi KEY SELECTOR WITHOUT WIRES code ACG6098 RED RADIO TRANSMITTER for mechanical and electrical safety strip Batteries not included RED allows to make a system made with edges fixed to the moving shutter without having to use cable sleeving systems It complies with EN13849 1 2007 Standard if in...

Страница 35: ...nstange Modul 4 4 Schlüsselwählschalter 5 Radioantenne 6 Blinkleuchte 7 Laufbegrenzer Nocken 8 Interne Fotozellen 9 Standsäulen für Fotozellen 10 Mechanische Anschläge 1 Abmessungen in mm 800 24 700 4 230V 50Hz 220V 60Hz 408 590 2 08 3 2 25 13 32s 2s 9 32s 2s 400 70 21 10m COMLUBE LHITGREASE EP GR 2 12 3 70 10 55 44 K800 FAST TECHNISCHE EIGENSCHAFTEN Max Torgewicht Max Drehmoment Max Schubkraft Za...

Страница 36: ...echanischen Anschläge über dem Tor vorhanden sein da diese nicht ausreichend sicher sind ENTRIEGELUNG Die Entriegelung darf erst nach dem Abschalten der elektrischen Motorstromversorgung erfolgen Um das Tor manuell richtig zu pruefen muessen folgende Punkte beachtet werden Das Tor muss einen geeigneten Griff haben Dieser Griff muss so angebracht sein das er kein Risiko ist beim Test Daß die physis...

Страница 37: ...erung des Öffnungs und Schließlaufes wird erhalten indem diese entlang der Zahnstangenzähne verschoben werden Um die Zahnstangennocken festzustellen müssen die mitgelieferten Schrauben am Boden befestigt werden ANMERKUNG Außer den o g elektrischen Feststellnocken müssen ebenfalls robuste mechanische Anschläge montiert werden die ein Herausgleiten des Tors aus den oberen Führungen verhindern INSTAN...

Страница 38: ...LLGEMEINE M BLINKER 230Vac 40W SPEISUNG 230Vac 50 Hz ENDSCHALTER ÖFFNUNG ENDSCHALTER SCHLIESSUNG FUSSGÄNGER ÖFFNE STOP SCHLIESSE SCHRITT BEI SCHRITT 24Vdc 0 4A 15 LED R 2 2K 1 4W ALLGEMEINE RIPPE ANTENNE BEFLECHTUNG ANTENNE ALLGEMEINE FOTOZELLEN ENCODER S1 Kode BC07096 ...

Страница 39: ...richtungen zu 24 Vdc Kontrollleuchte Tor geöffnet zu 24 Vdc Gemeinsame Erdungseinheit der Kontakte Kontakt Kontaktleisten bei Öffnung und SchlieSung Funkantenne Gemeinsame Erdungseinheit der Kontakte Kontakt Fotozellen Steckverbinder für Anschluss Heizfühler KODE ACG4665 Steckverbinder für Anschluss Encoder nur für K Plus Steckverbinder für externen Funkempfänger 24 Vdc Programmiertaste Elektronis...

Страница 40: ...r Phase der Zeitprogrammierung bestimmt und wird in ca 50 60 cm Entfernung aktiviert bevor der Endschalter die Endlage der Öffnungs und Schließbewegung erreicht hat ELEKTRONISCHE BREMSE BEI FAST MOTOREN IMMER AKTIV Wenn DIP 10 auf EIN steht ist eine harte Bremse aktiv Wenn DIP 10 auf AUS steht ist eine weiche Bremse aktiv Bei Erreichen der vollständigen Öffnung oder Schließung erfolgt eine Bremsun...

Страница 41: ...d der Schließbewegung sorgt sie dafür dass sich das Tor wieder öffnet AUTOMATISCHE SCHLIESSUNG MIT VOLLSTÄNDIGER ÖFFNUNG ODER ÖFFNUNG FÜR FUSSGÄNGER Der Pausenzyklus bis zur automatischen Schließung bei vollständiger Öffnung oder bei Öffnung für Fußgänger des Tores wird während der Zeitprogrammierung eingestellt Der maximale Pausenzyklus beträgt 5 Minuten sowohl für den Modus Vollständige Öffnung ...

Страница 42: ...tleistung Kontrollleuchte Tor geöffnet 3 W entspricht 1 Glühbirne mit 3 W oder 5 LEDs mit serienmäßigem Widerstand von 2 2 kΩ Maximale Spannung am Blinkerausgang 40 W mit ohm scher Last Verfügbarer Strom für Fotozellen und Zusatzsteuereinrichtungen 400mA 24 Vdc Verfügbarer Storm an der Funkgerätesteckverbindung 200mA 24Vdc Damit die doppelte bzw verstärkte Isolierung gegenüber Teilen mit gefährlic...

Страница 43: ... Leistungen mit den o g Apparaten zu erhalten muss eine auf die Frequenz des Funkempfängers abgestimmte Antenne montiert werden Anmerkung Besonders muss darauf geachtet werden dass das Zentralkabel der Leitung nicht mit der externen Kupferumwicklung in Kontakt kommt da dies die Funktion der Antenne außer Kraft setzt Die Antenne muss senkrecht von dem Fernbetätigungsgerät aus sichtbar montiert werd...

Страница 44: ... Kode ACG7064 SEITENLAGER Kode ACG7042 BLOCK Wi Fi SCHLÜSSELSCHALTER OHNE KABEL Kode ACG6098 RADIO SENDER RED Für mechanische oder elektrische Kontaktleiste Versorgung mit Mignon Batterien vom Typ AA zu 1 5V nicht im Lieferumfang enthalten RED erlaubt die Realisierung einer Anlage mit Kontaktleisten die auch auf dem sich bewegenden Tor angebracht sein können ohne dass man Kabelsammelsysteme benöti...

Страница 45: ... 4 4 Interruptor de llave 5 Antena de radio 6 Intermitente 7 Limitadores de recorrido leva 8 Fotocélulas internas 9 Columnas para las fotocélulas 10 Fermi meccanici 1 Medidas en mm 800 24 700 4 230V 50Hz 220V 60Hz 408 590 2 08 3 2 25 13 32s 2s 9 32s 2s 400 70 21 10m COMLUBE LHITGREASE EP GR 2 12 3 70 10 55 44 K800 FAST CARACTERÍSTICAS TÉCNICAS Peso máx verja Coppia máx Fuerza a revoluciones consta...

Страница 46: ...tiene que haber topes mecánicos por encima de la verja porque no son suficientemente seguros DESBLOQUEO A efectuar tras haber cortado la alimentación eléctrica al motor Para poder abrir manualmente la cancela en el caso de que faltase la corriente eléctrica con introducir la llave y girarla 3 veces en sentido opuesto a las agujas del reloj Fig 4 Para poder realizar en modo seguro el desplazamiento...

Страница 47: ...itadores de recorrido en los extremos de la cremallera Fig 7 La regulación de la abertura y el cierre se obtiene desplazando la misma sobre los dientes de la cremallera Para fijar las limitadores de tope de recorrido a la verja atornillar a fondo los tornillos suministrados N B además de los citados limitadores de recorrido eléctricos es obligatorio instalar unos topes mecánicos resistentes que im...

Страница 48: ...7096 CIERRA ABRE COMÚN M ALIMENTACIÓN 230Vac 50 Hz INTERMITENTE 230Vac 40W FINAL DE CARRERA ABRE FINAL DE CARRERA CIERRA PEATONAL ABRE STOP CIERRA PASO PASO 24Vdc 0 4A 15 LED R 2 2K 1 4W COMÚN COSTAS ANTENA MASA ANTENA COMÚN FOTOCÉLULAS ENCODER ...

Страница 49: ...INDICADOR LUMINOSO CANCELA ABIERTA 24 VDC COMÚN DE LOS CONTACTOS CONTACTO COSTAS EN APERTURA Y CIERRE ANTENA DE RADIO COMÚN DE LOS CONTACTOS CONTACTO FOROCÉLULAS CONECTOR PARA CONEXIÓN SONDA CALEFACTOR Cód ACG4665 CONECTOR PARA CONEXIÓN ENCODER SOLO PARA K PLUS CONECTOR PARA RADIO RECEPTOR EXTERNO 24 VDC PULSADOR PARA PROGRAMACIÓN REGULADOR ELECRÓNICO DE VELOCIDAD LENTA EN ACERCAMIENTO A DIP 7 ON ...

Страница 50: ...ión de los tiempos La misma se activa aproximadamente a 50 60 cm antes de alcanzar el final de carrera de apertura o de cierre FENO ELECTRÓNICO CON MOTORES FAST SIEMPRE ACTIVO Si DIP 10 está en posición ON se encuentra activo el freno HARD Si SIP 10 está en posición OFF se encuentra activo el freno SOFT Al alcanzar la apertura o el cierre total se activará una frenada para evitar la inercia que en...

Страница 51: ...ATONAL Los tiempos de pausa antes del cierre automático en apertura total o peatonal de la cancela son registrados durante la programación de los tiempos El tiempo de pausa máximo es de 5 minutos tanto para la modalidad de apertura total como para la de apertura peatonal Los tiempos de pausa pueden activarse o desactivarse mediante el DIP3 ON activo FUNCIONAMIENTO POST BLACK OUT Cuando se produce ...

Страница 52: ...ondensación Tensión de alimentación 230 o 120V 10 Frecuencia 50 60 Hz Absorción máxima tarjeta 30 mA Microinterruptor de red 100ms Potencia máxima indicador luminoso de cancela abierta 3 W equivalente a 1 bombilla de 3W o 5 led con resistencia en serie de 2 2 kΩ Carga máxima salida intermitente 40W con carga resistiva Corriente disponible para fotocélulas y accesorios 400mA 24Vdc Corriente disponi...

Страница 53: ... hasta 30 C conector al J6 cód ACG4665 SPARK Para obtener las mejores prestaciones de los citados aparatos es necesario instalar una antena sintonizada con la frecuencia del radioreceptor Importante Controlar con atención que el hilo central del cable no esté en contacto con la protección de cobre externa Esto impediría el funcionamiento de la antena Instale la antena verticalmente y de tal manera...

Страница 54: ...ERMITENTE SIN CABLES cód ACG7064 SOPORTE LATERAL cód ACG7042 BLOCK Wi Fi SELECTOR DE LLAVE SIN CABLES cód ACG6098 TRANSMISOR RADIO RED para costa mecánica o eléctrica para alimentar con 3 pilas estilo tipo AA de 1 5V no incluidas RED permite realizar una instalación con costas colocadas incluso sobre la hoja en movimiento sin la adopción de sistemas recoge cables Conforme a la norma EN13849 1 2007...

Страница 55: ...res éléments Aussi rentre t il dans le champ d application de l art 6 paragraphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant que l installation ait été déclarée conforme aux dispositions prévues par la Directive This product can not work alone and was designed to be fitted into a system made up of various other elements Hence it...

Страница 56: ...io Cuscinetto motore Cond 25µF 450V per K800 FAST 230 50V Passacavo IP55 GW50431 AC50 Codice Denominazione Particolare CEL1543 CME2026 CME2028 CME2036 CME2046 CMO1191 CPL1177 CPL1178 CPL1224 CTC1012 CTC1018 CTC1164 CTC1205 CTC1221 Trasformatore toroidale 20VA 230V Albero traino Perno di sblocco Corona K800 FAST Vite rullata K800 FAST Motore K800 FAST 230V 50 60Hz Guida porta micro Tappo ingranaggi...

Отзывы: