902 MHz Wireless Relays Application Manual B1867
Delay Mode
• Typically used with Hotel Room Energy Control (see page 5).
• Activating Delay Mode allows the relay to ignore
temporary
changes in switch states.
• The Delay Mode causes a delay of 10 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also prevents the relay from activating following a
deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring window and door contacts that may be
briefly opened and then closed. If the contact remains open for longer than 90 seconds the relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again,
to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks
twice
indicating
Delay Mode is enabled.
Disabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH,
FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to
FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks
three
times indicating
Delay Mode is disabled.
<10s
Off
On
Off
On
>10s
10s
90s
90s
90s
Wireless
Command
Relay
State
page 5
Clearing ID’s from Memory
Global Clear (Reset to default settings)
Clears all linked devices, disables optional modes, and turns relay OFF.
Performing Global Clear
1. Press and hold CLR button on RIB for 3 seconds until LED begins slowly blinking.
a. Clear Mode will time out and exit in 30 seconds.
Single Device Clear
• Allows the user to Un-link a single transmitter from RIB receiver.
• Maintains all optional mode settings.
Performing Single Device Clear
1. Repeating the Link procedure for a currently Linked device will Un-link that device.