902 MHz Wireless Relays Application Manual B1867
B. Momentary Mode
• Relay activates while switch is pressed and deactivates when switch is released.
• Optional modes: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH,
OFF (2 flashes).
4. Press and release the button on the switch you are learning three times quickly.
5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. To learn another switch, repeat steps 2-5.
C. Toggle Mode
• Each press and release of the switch causes the relay to change state.
• Optional modes: Repeater (see page 4)
Toggle Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH,
OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH,
FLASH, FLASH, OFF (3 flashes).
5. Press and release the button on the switch you are learning three times quickly.
6. LED on RIB will stay ON for 4 seconds indicating telegram reception.
7. To learn another switch, repeat steps 2-6.
page 3
Lighting Applications
Simple Lighting Control:
RIBWxxxB-EN3 or RIBWxxC-EN3 and WWS2-EN3 or WKC-EN3
A. Rocker Mode
• Relay activates when Rocker ON is pressed; relay deactivates when Rocker OFF is pressed.
• Optional modes: Repeater (see page 4)
Rocker Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and release the button on the switch you are learning three times quickly.
4. LED on RIB will stay ON for 4 seconds indicating telegram reception.
5. To learn another switch, repeat steps 2-4.
Occupancy Detection
A. Manual ON–Auto OFF:
RIB receiving from both an Occupancy / Vacancy Sensor (WVSWM-EN3 or WVSCM-EN3) and a Wall Switch (WWS2-EN3)
• Relay activates when Rocker ON is pressed. Relay deactivates when Rocker OFF is pressed or 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy / Vacancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Manual ON – Auto OFF Learn Procedure
1. Be sure the Occupancy / Vacancy Sensor is charged
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
7. Press and release rocker switch three times quickly.
8. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
9. To learn another switch, repeat steps 6-8.
Continued on Page 4
Load
60Hz A/C Power
Yel
Org
Blk
Wht or Red
RIBWxxxB-EN3
or RIBWxxC-EN3
WWS2-EN3
(Rocker Switch)
or
WKC-EN3
(Keycard Switch)
LRN CLR
WWS2-EN3 Modes
WKC-EN3 Mode
Momentary Mode
• Relay activates when card is inserted and deactivates when card is removed.
• Optional modes: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Insert and remove the card on the switch you are learning three times quickly.
5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. To learn another switch, repeat steps 2-5.