RIB RIBW***B-EN3 Series Скачать руководство пользователя страница 3

902 MHz Wireless Relays Application Manual        B1867

B. Momentary Mode

•  Relay activates while switch is pressed and deactivates when switch is released.
•  Optional modes: Repeater (see page 4)

Momentary Mode Link Procedure
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH,  
      OFF (2 flashes).
4.  Press and release the button on the switch you are learning three times quickly.
5.  LED on RIB will stay ON for 4 seconds indicating telegram reception.
6.  To learn another switch, repeat steps 2-5.

C. Toggle Mode

•  Each press and release of the switch causes the relay to change state. 
•  Optional modes:  Repeater (see page 4)

 

Toggle Mode Link Procedure
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH,  
      OFF (2 flashes).
4.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH,  
      FLASH, FLASH, OFF (3 flashes).
5.  Press and release the button on the switch you are learning three times quickly. 
6.  LED on RIB will stay ON for 4 seconds indicating telegram reception.
7.  To learn another switch, repeat steps 2-6.

page 3

Lighting Applications

Simple Lighting Control: 

RIBWxxxB-EN3 or RIBWxxC-EN3  and WWS2-EN3 or WKC-EN3

A.  Rocker Mode 

•  Relay activates when Rocker ON is pressed; relay deactivates when Rocker OFF is pressed. 
•  Optional modes: Repeater (see page 4)

Rocker Mode Link Procedure
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second.  LED will blink slowly.
3.  Press and release the button on the switch you are learning three times quickly.
4.  LED on RIB will stay ON for 4 seconds indicating telegram reception.
5.  To learn another switch, repeat steps 2-4.

Occupancy Detection

A.  Manual ON–Auto OFF:  

RIB receiving from both an Occupancy / Vacancy Sensor (WVSWM-EN3  or  WVSCM-EN3) and a Wall Switch (WWS2-EN3)

•  Relay activates when Rocker ON is pressed. Relay deactivates when Rocker OFF is pressed or 30 minutes after last detection of occupancy.
•  It may take up to 2 minutes for the RIB to respond to the Occupancy / Vacancy Sensor immediately following Link.
•  Optional modes: Repeater (see page 4)

Manual ON – Auto OFF Learn Procedure
1.  Be sure the Occupancy / Vacancy Sensor is charged
2.  Apply power to RIB.
3.  Press and hold LRN button on RIB for ½ second.  LED will blink slowly.
4.  Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5.  LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6.  Press and hold LRN button on RIB for ½ second.  LED will blink slowly.
7.  Press and release rocker switch three times quickly.
8.  LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
9.  To learn another switch, repeat steps 6-8.

Continued on Page 4

Load

60Hz A/C Power

Yel

Org

Blk

Wht or Red

RIBWxxxB-EN3

or RIBWxxC-EN3

WWS2-EN3

(Rocker Switch)

or

WKC-EN3

(Keycard Switch)

LRN CLR

WWS2-EN3 Modes

WKC-EN3 Mode

Momentary Mode

•  Relay activates when card is inserted and deactivates when card is removed.
•  Optional modes: Repeater (see page 4)

Momentary Mode Link Procedure
1.  Apply power to RIB.
2.  Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3.  Press and hold LRN button on RIB for 3 seconds until LED pattern changes to  
      FLASH, FLASH, OFF (2 flashes).
4.  Insert and remove the card on the switch you are learning three times quickly.
5.  LED on RIB will stay ON for 4 seconds indicating telegram reception.
6.  To learn another switch, repeat steps 2-5.

Содержание RIBW***B-EN3 Series

Страница 1: ...ception RIBW24B EN3 will not save last state when powered from 24Vdc Each Relay can be Linked to up to 30 transmitters of any combination page 1 902 MHz Model Power Input Vac Contact Rating A Transmis...

Страница 2: ...ton for 3 seconds Device Power Dry Contact RIBWxxxB EN3 RIB 1 Device Power RIBWxxxB EN3 or RIBWxxC EN3 RIB 2 Load Bi directional Mode Two RIBWxxxB or one RIBWxxB EN3 and a PHC Gateway Controller Both...

Страница 3: ...earning three times quickly 4 LED on RIB will stay ON for 4 seconds indicating telegram reception 5 To learn another switch repeat steps 2 4 Occupancy Detection A Manual ON Auto OFF RIB receiving from...

Страница 4: ...y 3 seconds until the LED blinks 1 time 4 Release the LRN and CLR buttons Relay will return to LAST STATE at power up NOTE LAST STATE does not work with RIBW24B EN3 when powered from 24 Vdc Relay Stat...

Страница 5: ...FLASH OFF 2 flashes 4 Press and hold LRN button on RIB for 3 seconds until LED pattern changes again to FLASH FLASH FLASH OFF 3 flashes 5 Press and hold the CLR button for 3 seconds until LED blinks t...

Страница 6: ...mit Teach telegram 5 LED on RIB will stay ON for 4 seconds acknowledging telegram reception 6 To learn more WDWS EN3 repeat steps 3 5 WDWS EN3 Keycard Switch PTAC unit with RIBWxxxB EN3 in Hotel Room...

Страница 7: ...AS System In this application the BAS system dry contact output controls the transmitter on a RIBWxxxB EN3 A second RIBWxxxB EN3 receives the signal and activates it relay A current switch detects cur...