ELECTRONIC CONTROL FOR TERMINAL UNITS 

I.2.3.3 

Setting the operating mode 

 

By pressing the Mode key several times, you can 
change the operating mode of the unit. The 
operating mode selected appears on the display: 

 

AUTO

 

Fully automatic operation 

 

WARM

 

Heating mode 

 

COLD 

Cooling mode 

 

BLAST

 

Ventilation only mode 

 
The successful reception of the command is signaled by a short sound 
feedback. 
 

I.2.3.4 Ventilation 

setting 

 

By pressing the FAN keys it is possible to set the 
fan speed among the three available or activate 
the AUTO function that automatically adjusts the 
fan speed according to the difference between the 
Set-point temperature and the room temperature. 
The operating mode and the selected speed 
appear on the display. 

 

Automatic control of the speed  

 

Minimum speed 

 

Medium speed 

 

Maximum speed 

 

 
 

I.2.3.5 

Setting the desired temperature 

 

By pressing these keys it is possible to increase or 
decrease the desired temperature value.  The 
display shows the value of the selected 
temperature.  
The resolution is 1 ° C. The range is 8 ÷ 30 ° C. 

 

Setting the desired temperature value in COOL, 

HEAT modes. 

23°C

 

 

 

 

I.2.3.6 Serial 

address 

setting 

In the case of a serial network (the KIF485 serial board is mounted on 
the board), it is possible to configure address, communication speed 
and parity by remote control. 
Refer to the instruction sheet for the KIF485 accessory. 
 
 

I.2.3.7 Batteries 

exhausted 

If the batteries are almost empty, the display will work normally, but the 
transmission of commands may not be performed correctly. Ensure that 
the KRLT receiver beeps after a key is pressed. 
Note: KRLTI and KRLTM do not have the acoustic signal. 
 
 

I.2.3.8 

Features of the remote control 

The maximum distance between the remote control and the receiver is 
10m (with charged batteries). 
The angle of action in free field is equal to 20 °. 
 
 
 
 

I.2.4 

WALL RECEIVER (KRLT) 

The three LEDs present are used to indicate the operating status of the 
machine. They can also indicate the presence of a fault that prevents 
the unit from operating. 

 

 

DL1 = Green

DL2 = Yellow  DL3 = Red

At each restart after a power failure, all the LEDs flash for a few 
seconds until the self-diagnosis of the system is completed.  

Mode 

DL1 

Green 

DL2 

Yellow 

Dl3

Red 

OFF

Turned off 

Turned off 

Turned off 

AUTO

(*) 

(*) 

(*) 

COOL

Switched 

on 

Turned off 

Turned off 

FAN

Turned off 

Switched 

on 

Turned off 

HEAT

Turned off 

Turned off 

Switched 

on 

(*) By selecting this operating mode, the unit is positioned in the FAN 
mode (yellow LED on) for a programmed time after which the unit 
decides in which mode to operate (HEAT / COOL). 
 
Local operation 
If the remote control fails or fails, the unit can be operated using a 
button on the front of the appliance (use a pointed object). 
In this case, preset values are used for the temperature set point and 
fan speed. 
By pressing the button in succession, it is possible to select the desired 
operating mode (highlighted by the lighting of the relative LEDs). 
 

 

 

The set point for the various modes is defined by parameter P11 (23 ° 
C). 
The fan speed is the last stored. 

Содержание KCF/B

Страница 1: ...ONES DE USO KCF B KCF P KPLTB KPLTW KTLT KRLT KRLTI KRLTM Controllo elettronico per unit terminali Electronic control for terminal units Controle electronique pour unites terminales Elektronische Steu...

Страница 2: ...disposition de l utilisateur pour fournir toute information suppl mentaire sur ses produits dans le cas o les notices fournies s av reraient insuffisantes RHOSS S p A conserve la facult de modifier s...

Страница 3: ...mation en nergie et en autres ressources des produits li s l nergie le cas ch ant CEI EN 60335 2 40 Appareils lectrodomestiques et analogues S curit Partie 2 r gles particuli res pour les pompes chale...

Страница 4: ...I 4 1 Preliminary checks before start up 22 II 4 2 Decommissioning 22 II 4 3 Restart after prolonged shutdown 22 II 5 Instructions for maintenance 22 II 6 Indications for dismantling the unit 22 II 7...

Страница 5: ...ts which can be configured as ON OFF call summer winter call unit alarm KIF485 SS RS485 serial board with unit addressing from control panel or remote control On board installation only for Yardy vers...

Страница 6: ...be fixed near the metal plafon Note not LEDs are present to indicate the functioning mode KDO2 DO2 Additional board with 2 digital relay outputs which can be configured as ON OFF call summer winter c...

Страница 7: ...he range is 15 30 C Set the desired temperature value in the COOL HEAT and AUTO modes 23 5 I 2 1 5 Selecting the ambient probe The ambient temperature is detected by means of the probe inside the KPLT...

Страница 8: ...USING THE REMOTE CONTROL KTLT I 2 3 1 Introduction of batteries DANGER Take precautions to prevent children from mishandling or accidental use of batteries ATTENTION If you do not use the remote contr...

Страница 9: ...are almost empty the display will work normally but the transmission of commands may not be performed correctly Ensure that the KRLT receiver beeps after a key is pressed Note KRLTI and KRLTM do not...

Страница 10: ...neric alarm hot start too cool EC fan waiting time after mode change 4 ON on BLINK flashing Note OFF from digital input is not displayed in case of failure of the water probe operation is guaranteed w...

Страница 11: ...stacking no more than four units and must be stored in dry conditions and protected from the sun and rain II 1 4 SPACES OF RESPECT POSITIONING IMPORTANT Incorrect positioning or installation of the u...

Страница 12: ...ed in parallel Use the clean contacts of an external relay not supplied II 3 2 2 Control panel connection KPLT The connection between the board and the control panel must be carried out with a shielde...

Страница 13: ...l 0 2 C P11 Set Point Legend V valve status Ta room temperature in case of Yardy I with EC Brushless motor speeds are defined by the following parameters P80 Minimum speed value set manually 10 P81 Av...

Страница 14: ...6 Dip switches configuration IMPORTANT In the case of an EC motor at each mode change the fan is stopped for 90 seconds On the on board control panel or on the wall the fan led flashes On the wall rec...

Страница 15: ...t2 output activates the water valve cold Fancoil summer winter winter head contact 2tubi radiante This function is obtained by configuring the fancoil in 2tubi radiant see Dip switches configuration t...

Страница 16: ...ot Start Too Cool 1 C Legend Fan fan status ST2 main exchanger temperature ST2 probe II 3 4 3 PERIODIC VENTILATION CONTINUED IMPORTANT To counteract the air stratification phenomenon the terminal unit...

Страница 17: ...there are units switched on in the same mode and others switched off by set reached Alarms the alarms are managed independently in each control board Inputs digital inputs can be local Local or global...

Страница 18: ...ed cable consisting of 2 twisted conductors of 0 5 mm and the shield type Belden 8762 20 AWG The screen must be connected to the GND The maximum distance is 10m Digital inputs between different boards...

Страница 19: ...e following parameters Use the up down keys to set the desired set point Change the SdE interval to the desired value 3 default Change the parameter LOC 2 blocked set point Example with set point at 2...

Страница 20: ...an Off it remains closed default II 3 8 SETTING AND MODIFICATION OF PARAMETERS WITH CONTROL PANEL The parameter map is resident in the touch control panel or on board control panel when this is conne...

Страница 21: ...imultaneously for 5 seconds The rEA indication appears on the display Use the UP DOWN key to scroll through the parameters until you reach the desired parameter whose value you want to display Press t...

Страница 22: ...IONS FOR MAINTENANCE DANGER Always act on the main switch to isolate the unit from the mains before any maintenance operation on it even if purely inspective Make sure that no one supplies power to th...

Страница 23: ...rovided by the TOO COOL and HOT START functions are active Remote control or remote security is active The unit produces inadequate cooling or heating Clogged air filter Difficulty of air circulation...

Страница 24: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 24 A1 SCHEMI ELETTRICI WIRING DIAGRAMS SCH MAS LECTRIQUES SCHALTPL NE ESQUEMAS EL CTRICOS...

Страница 25: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 25...

Страница 26: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 26...

Страница 27: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 27...

Страница 28: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 28...

Страница 29: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 29...

Страница 30: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 30...

Страница 31: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 31...

Страница 32: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 32...

Страница 33: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 33...

Страница 34: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 34...

Страница 35: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 35...

Страница 36: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 36...

Страница 37: ...ALLEGATI ENCLOSED DOCUMENTS ANNEXES ANLAGEN ANEXOS 37...

Страница 38: ...KCF B KCF P KPLTB KPLTW KTLT KRLT KRLTI KRLTM RHOSS S p A Via Oltre Ferrovia 33033 Codroipo UD Italia tel 0432 911611 fax 0432 911600 rhoss rhoss it www rhoss it H58545 06 18 PS RM LF...

Отзывы: