Plumbing 

 

 

It is preferable that the heat pump is connected to filtered water. 

 

 

It is essential that the water recirculating pump and pipe sizes be engineered to suit the particular 
application, giving correct water flow through the heat pump as per the specification requirements 
of the unit.  Inadequate or excessive water flow detracts from heating efficiency and can lead to 
damage to the unit.  Selection of the recirculating pump must be made in  accordance with the 
design flow rate and pressure as per the pump 

manufacturer’s specification. 

 

 

If unsure, contact Rheem Thermal for recommendations on the optimum flow rate.  Assistance 
will be provided where possible in relation to plumbing design and pump selection. 

 

 

Water connections on the unit are clearly marked as water inlet and water outlet.   
 

 

The installation of breakable unions on both inlet and outlet pipes will facilitate maintenance and 
water drainage of the system.  If the unit is situated below the pool level or an open holding tank, 
shut off valves should be fitted on the water side of both unions so that removal of the machine 
is possible without draining the system. 

 

 

A separate circuit is generally the most desirable plumbing configuration with individual flow and 
return line and filter strainer.  This may not always be possible particularly with established pools.   
 

 

Heat  pumps  may  be  plumbed  in-line  with  existing  filter  equipment,  although  thought  must  be 
given to correct flow, run time and possible over chlorinating and/or dosing by extended running 
of automatic chlorinator, feeders, etc.  Typical plumbing schematics for installation with existing 
filtration and with a dedicated heating circuit are shown in Section 6.  

 

 

A one-way check valve should be installed on the outlet of the heat pump. 

 

 

Models without an internal water flow by-pass must have an external by-pass fitted.  

 
 
 
 
 
 
 
 

 

Where multiple units are installed, the heaters must be installed in parallel to equalise pressure 
drops  and  balance  flow  through  the  heaters.    Systems  of  two  or  more  Heat  Pumps  require  a 
manifold. 

 

 

All Plumbing should be carried out by qualified tradesman (plumber). 

 

Chemical Treatment 

 
Rheem Thermal heat pumps designed for swimming pool or spa heating will include a titanium heat 
exchanger. This material is impervious to chemical corrosion and as such, variations in water quality 
will not cause damage to the titanium tube. However, it is recommended as a matter of good pool 
management that the correct chemical balance of the water be maintained as follows: 
 

  pH to be kept between 7.2 and 7.8 

  Alkalinity must not exceed 200 PPM 

  Free available chlorine must not exceed 6.0 PPM 

  Chemicals must be added downstream side of the Heat Pump. 

  In line chlorinator must be installed downstream of the Heat Pump. 

 
The maintenance of the above guidelines does not in itself ensure that water is in balance and non-
corrosive.    Various  mechanisms  are  available  to  monitor  water  conditions  and  information  on  the 
Langlier Saturation Index is provided as a commonly applied industry standard. 
 
 
 

Содержание RTHP009

Страница 1: ...ervice Manual This booklet is to be carefully read and instructions followed for efficient and trouble free operation of the Rheem Thermal Swimming Pool Heat Pump 43 Marigold Street Revesby NSW 2212 Tel 02 9684 3684 Fax 02 9684 3698 ABN 28 062 383 224 ...

Страница 2: ...RATION 6 Thermostat Operation 7 Heat Up Time 7 De Icing 7 Pool Application 7 SECTION 4 MAINTENANCE 7 Heat Exchanger Care 8 Service Assistance 8 SECTION 5 TROUBLESHOOTING 9 Machine Will Not Start 9 Pool Will Not Heat 9 Compressor Will Not Run 9 Compressor Motor Hums But Will Not Start 9 SECTION 6 INSTALLATION SCHEMATIC DRAWINGS 10 Typical Single Pool Heat Pump Schematic For Pool Filtration 10 Typic...

Страница 3: ...R134A may be used for special hot water applications The Rheem Thermal heat pump is installed to a wide diversity of commercial and industrial applications The performance of the unit varies with ambient operating conditions water flow and water temperature and as such selection should be done in conjunction with an experienced heat pump dealer or the manufacturer Each Rheem Thermal unit is manufa...

Страница 4: ...mp must be discharged by a duct away from the fresh air supply Never install in an enclosed area Service access is required at both ends of the Heat Pump as per the Clearance Guidelines See attached Where multiple units are to be installed minimum clearance requirements increase The Heat Pump requires a firm base say concrete slab Rubber mounts should be installed between the unit and slab Drainag...

Страница 5: ...h thought must be given to correct flow run time and possible over chlorinating and or dosing by extended running of automatic chlorinator feeders etc Typical plumbing schematics for installation with existing filtration and with a dedicated heating circuit are shown in Section 6 A one way check valve should be installed on the outlet of the heat pump Models without an internal water flow by pass ...

Страница 6: ...Ideally the unit would be switched off either at the main switch the isolating switch located on or adjacent to the unit or at a control sub board For systems comprised of multiple Heat Pump units the thermostat sensor and well may be provided as follows depending on client requirement Provided loose to allow installation of thermostat controller display in heat pump control panel located separate...

Страница 7: ...re signals PRECAUTIONS Where damage to property can occur in the event of the heat pump leaking the unit must be installed in a drained drip tray in accordance with AS NZS3500 4 and local codes and regulatory authority requirements The heat pump must be maintained in accordance with the Owners Guide and Installation Instructions If the heat pump is to be used in a commercial application you should...

Страница 8: ...or pools 3 The unit is fully automatic and after commissioning the operation of the unit will be triggered by water flow and the set temperature parameters 4 In low ambient temperature ice may form on the evaporator coil If this occurs the machine will automatically go into defrost operation 5 The unit can be controlled via time clock through water pump The unit has in built water flow pressure sw...

Страница 9: ...eaned periodically 2 Check condensate drain for blockages 3 Ensure that water is not collecting in the base of the unit RECOMMENDED RHEEM THERMAL SERVICE PROCEDURE 1 Depending on the location of the unit fins of the coil must be cleaned periodically 2 In locations where ambient temperature can be very low if unit is not used for a long period it is essential to drain all water from unit to prevent...

Страница 10: ...nosed as the cause of failure For shutdowns in locations experiencing freezing conditions the piping system and heater must be drained The heater should be flushed with clean fresh water for several minutes to wash away all traces of chemicals then drained It is recommended that the entire system is purged using pressurised air to force remaining water from the system If water enters the refrigera...

Страница 11: ...ing that the heater is working Check inlet louvres outlet grill and evaporator coil has satisfactory airflow and is not clogged Check that thermostat is correctly set Check that water pump is running Check water filter is operational Check that inlet valves are not closed Check ambient air temperature suits design standards Compressor Will Not Run Possible Cause Possible Solution Overload switch c...

Страница 12: ...CAL INPUT MUST BE DOWN STREAM OF HEAT PUMP RETURN TO POOL PIPE SCHEMATIC FOR HEAT PUMP INSTALLED POOL CHLORINATOR SUPPLY FROM POOL INTO POOL FILTRATION SYSTEM HEAT PUMP CHECK VALVE FILTER PUMP CHEMICAL INPUT MUST BE DOWN STREAM OF HEAT PUMP RETURN TO POOL PIPE SCHEMATIC FOR HEAT PUMP INSTALLED WITH SEPARATE PUMP FOR HEATING APPLICATION POOL CHLORINATOR OUTLET INLET PUMP SUPPLY FROM POOL CHECK VALV...

Страница 13: ... STEEL FLANGE BUTTERFLY VALVE TEE PIPE CLASS 9x6 PRIMER GLUE PIPE CLASS 9 FLANGES PVC ELBOW 18 x 80mm x 100mm x 80mm x 100mm 10 12 6 2L FLANGES HANGER x 80mm 24m 100mmØ POOL FROM TO POOL RETURN VALVE BUTTERFLY 100mmØ FLANGES VALVE BUTTERFLY INLINE PUMP VALVE CHECK FILTRATION PUMP 100mmØ PVC FLANGE STEEL FLANGE TANK 250Ø HEAT PUMP HEAT PUMP BUTTERFLY BUTTERFLY BUTTERFLY BUTTERFLY 80mmØ 80mmØ 100mmØ...

Страница 14: ... owner s responsibility 2 6 Where the unit is installed in a position that does not allow safe or ready access the cost of that access including the cost of additional materials handling and or safety equipment shall be the owner s responsibility In other words the cost of dismantling or removing cupboards doors or walls and the cost of any special equipment to bring the pool heater to floor or gr...

Страница 15: ... at no cost to the Customer Should the remedial action fail to achieve the designed performance the limit of our liability either the negligence or for breach of statutory duty or otherwise shall be for us to remove the equipment at our expense or to refund to the buyer the purchase price in full 3 WHAT IS COVERED BY THE RHEEM THERMAL WARRANTY FOR THE UNITS DETAILED IN THIS DOCUMENT 3 1 Rheem Ther...

Страница 16: ...ber from the rating label on the heater b Rheem Thermal will arrange for the heater to be tested and assessed on site c If Rheem Thermal determines that you have a valid warranty claim Rheem Thermal will repair or replace the heater in accordance with this warranty 5 2 Any expenses incurred in the making of a claim under this warranty will be borne by you 6 THE AUSTRALIAN CONSUMER LAW 6 1 Our good...

Отзывы: