background image

8

Recovery Cylinders:

-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400

VI.

INSTALLATION

A. GENERAL

1. PRE-INSTALLATION CHECK-POINTS

Before attempting any installation, the following points should be carefully consid-
ered:

a. Structural strength of supporting members.

(rooftop installation)

b. Clearances and provision for servicing.
c. Power supply and wiring.
d. Air duct connections.
e. Drain facilities and connections.
f. Location for minimum noise.

2. LOCATION

These units are designed for outdoor installations. They can be mounted on a
slab or rooftop. They are not to be installed within any part of a structure such as
an attic, crawl space, closet, or any other place where condenser air flow is
restricted or other than outdoor ambient conditions prevail. Since the application
of the units is of the outdoor type, it is important to consult your local code authori-
ties at the time the first installation is made.

B. OUTSIDE SLAB INSTALLATION

(Typical outdoor slab installations are shown in Figure 2.)

1. Select a location where external water drainage cannot collect around the unit.

2. Provide a level concrete slab extending 3" beyond all four sides of the unit. The

slab should be sufficient above grade to prevent ground water from entering the
unit.

IMPORTANT: To prevent transmission of noise or vibration, slab should not be
connected to building structure.

3. The location of the unit should be such as to provide proper access for inspection

and servicing.

4. Locate unit where operating sounds will not disturb owner or neighbors.

5. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter

or other shielding at roof level. Do not locate unit in an area where excessive
snow drifting may occur or accumulate.

C. CLEARANCES

The following minimum clearances must be observed for proper unit performance
and serviceability.

1. Provide 30" minimum clearance at the front and 18" on the right side of the unit

for service access. Provide 12" minimum clearance on the left side of the unit for
air inlet.

2. Provide 60" minimum clearance from top of unit.

3. Unit is design certified for application on combustible flooring with 0" minimum

clearance.

4. See Figure 2 for illustration of minimum installation-service clearances.

D. ROOFTOP INSTALLATION

1. Before locating the unit on the roof, make sure that the strength of the roof and

beams is adequate at that point to support the weight involved. (See specification
sheet for weight of unit.) This is very important and user’s responsibility.

2. The unit should be placed on a solid and level platform of adequate strength.

!

CAUTION

R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.

Содержание RSNM SERIES

Страница 1: ...Y AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN WARNING ANT SAFETY INFORMA 14 SEER ONLY THESE INSTRUCTIONS ARE INENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INST...

Страница 2: ...IX Condensate Drain Indoor Coil 10 X Electrical Wiring 10 A Power Wiring 10 B Electric Heater Kit Instructions 11 C Control Wiring 11 D Internal Wiring 12 E Grounding 12 F Thermostat 12 XI Indoor Air...

Страница 3: ...SUCH DEVICES MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PROPERTY DAMAGE SEVERE PERSONAL INJURY OR DEATH WARNING DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING TO CHANGE BL...

Страница 4: ...year to remove matter that will not wash off with water Several different types of protective coatings are offered in some areas These coatings may provide some benefit but the effectiveness of such...

Страница 5: ...CONTROL BOX ACCESS 211 16 266 7 mm CONDENSATE DRAIN PAN ACCESS FRONT VIEW BOTTOM VIEW ELECTRICAL CONNECTIONS PRIMARY HIGH VOLTAGE ENTRANCE 123 32 43 7 mm 413 32 111 8 mm 59 64 130 5 mm 197 8 505 mm 57...

Страница 6: ...NS 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 IMPORTANT DO NOT SCREW OR DRILL OUTSIDE THE DESIGNATED AREAS ROUND DUCT CONNECTIONS 14 355 6 mm 14 355 6 mm DO...

Страница 7: ...checking can be performed safely with nitrogen or a mixture of R 410A and nitrogen 2 Quick Reference Guide For R 410A R 410A refrigerant operates at approximately 60 higher pressure 1 6 times than R 2...

Страница 8: ...RTANT To prevent transmission of noise or vibration slab should not be connected to building structure 3 The location of the unit should be such as to provide proper access for inspection and servicin...

Страница 9: ...e registers or diffusers are located on the wall or in the ceiling Consider a slab installation when the registers are low on a wall or in the floor On ductwork exposed to outside air conditions of te...

Страница 10: ...red by installation X ELECTRICAL WIRING Field wiring must comply with the National Electrical Code and applicable local codes C E C in Canada A POWER WIRING 1 It is important that proper electrical po...

Страница 11: ...heater kit fuse block and connect ground lead to ground lug on heater kit fuse block Connect the second set of high voltage field power leads to L1 and L3 on the unit contactor Connect ground lead to...

Страница 12: ...sources READ installation instructions in air conditioner thermostat package CAREFULLY because each has some different wiring requirements XI INDOOR AIR FLOW DATA All 208 230 volt units are equipped w...

Страница 13: ...8 1049 1091 1108 Watts 826 806 784 762 734 702 658 626 546 512 CFM 1431 1394 1348 1302 1258 1208 1140 1030 849 557 11x9 Low RPM 540 579 633 686 724 776 831 868 1035 1076 3 5 Low 1225 1575 1 2 Watts 48...

Страница 14: ...1032 1083 Watts 704 694 675 655 638 606 581 548 464 CFM 1279 1237 1196 1151 1098 1032 950 846 717 13 11x9 Low RPM 490 539 598 653 709 772 811 887 928 3 5 Low 1225 1575 1 2 Watts 401 400 393 391 381 3...

Страница 15: ...38 1386 1335 1283 1231 1180 1128 1076 11x9 RPM 598 617 662 714 758 800 849 876 913 951 1 2 Watts 244 231 237 254 270 285 304 313 326 340 2 Speed CFM 1740 1695 1649 1604 1558 1513 1467 1422 1376 1331 X...

Страница 16: ...8 1154 1101 1047 11x9 RPM 602 619 668 715 757 801 844 878 918 954 1 2 Watts 238 227 236 251 266 281 296 307 320 333 2 Speed CFM 1724 1678 1632 1586 1540 1495 1449 1403 1357 1311 X 13 Motor RPM 639 671...

Страница 17: ...HEAT Unit should stop Wait 5 minutes then raise temperature setting to above room temperature After about 30 to 50 seconds auxiliary heaters if installed should come on 9 Check the refrigerant charge...

Страница 18: ...n an automatic open overload device or blow a fuse Poor electrical service can cause nuisance tripping in overloads or blow fuses IMPORTANT The compressor has an internal overload protector Under some...

Страница 19: ...4 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 3400 1604 3400 1604 No Motors HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 875 875 875 875...

Страница 20: ...Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 4200 1982 4200 1982 No Motors HP 1 at...

Страница 21: ...Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11x9 279 4x...

Страница 22: ...609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 3400 1604 3400 1604 No Motors HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP Motor...

Страница 23: ...er Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 4200 1982 4200 1982 No Motors HP 1...

Страница 24: ...e Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11x9 279...

Страница 25: ...4 5 4 5 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 12 8 12 8 17 17 13 5 13 5 17 9 17 9 14 7 14 7 21 2 21 2 16 16 26 4 26 4 Amps LRA 54 54 73 73 95 95 96 7 96 7...

Страница 26: ...2 5 3 3 3 5 3 5 4 4 4 5 4 5 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 12 8 12 8 17 17 13 5 13 5 17 9 17 9 14 7 14 7 21 2 21 2 16 16 26 4 26 4 Amps LRA 58 3 58...

Страница 27: ...07J 1 1 5 4 7 2 18 42 24 56 26 30 36 41 40 40 45 45 33 38 35 40 10J 2 1 7 2 9 6 24 57 32 76 34 7 40 47 54 50 50 60 60 44 50 45 50 15J 3 2 10 8 14 4 36 85 49 13 52 60 69 79 70 70 80 80 65 75 70 80 20J...

Страница 28: ...50 60 No Heat 24 24 30 35 30 35 24 24 30 35 30 35 10C 2 1 7 2 9 6 24 57 32 76 20 23 1 29 33 30 30 35 35 25 29 25 30 15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 42 48 45 45 50 50 38 44 40 45 20C 4 2 14 4 1...

Страница 29: ...5 05J 1 1 3 6 4 8 12 28 16 38 17 33 20 30 33 35 45 35 45 22 25 25 25 07J 1 1 5 4 7 2 18 42 24 56 26 30 40 45 40 40 45 45 33 38 35 40 10J 2 1 7 2 9 6 24 57 32 76 34 7 40 51 58 60 60 60 60 44 50 45 50 1...

Страница 30: ...50 60 No Heat 27 27 30 40 30 40 27 27 30 40 30 40 10C 2 1 7 2 9 6 24 57 32 76 20 23 1 33 37 35 35 40 40 25 29 25 30 15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 46 51 50 50 60 60 38 44 40 45 20C 4 2 14 4 1...

Страница 31: ...31 FIGURE 7 WIRING DIAGRAM RSNM...

Страница 32: ...32 FIGURE 8 WIRING DIAGRAM RSNM...

Страница 33: ...33 FIGURE 9 WIRING DIAGRAM RSPM WITH X 13 BLOWER MOTOR...

Страница 34: ...34 FIGURE 10 WIRING DIAGRAM RSPM WITH X 13 BLOWER MOTOR...

Страница 35: ...35 FIGURE 11 2 TON AIR CHARGING CHART...

Страница 36: ...36 FIGURE 12 2 5 TON AIR CHARGING CHART...

Страница 37: ...37 FIGURE 13 3 0 TON CHARGING CHART...

Страница 38: ...38 FIGURE 14 3 5 TON CHARGING CHART...

Страница 39: ...39 FIGURE 15 4 0 TON CHARGING CHART...

Страница 40: ...PERATURE TO OUTDOOR COIL PLACE AN X ON THE APPROPRIATE CHART WHERE THE SUCTION AND LIQUID PRESSURES CR OSS IF X IS BELOW AMBIENT TEMPERATURE LINE ADD CHARGE AND REPEAT STEP 3 IF X IS ABOVE AMBIENT TEM...

Страница 41: ...weat Low evaporator airflow Increase speed of blower or reduce restriction replace air filter High head low vapor pressures Restriction in liquid line expansion device or filter drier Remove or replac...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44 CM 0408...

Отзывы: