background image

7

A. GENERAL

The Packaged Air Conditioner is available without heat or with 5, 7, 10, 15, or 20 kW
electric heat. Cooling capacities of 2, 2

1

2

, 3, 3

1

2

, 4 and 5 nominal tons of cooling are

available.

The units are weatherized for mounting outside of the building.

The information on the rating plate is in compliance with the FTC and DOE rating for sin-
gle phase units.

B. MAJOR COMPONENTS

The unit includes a hermetically-sealed refrigerating system (consisting of a compressor,
condenser coil, evaporator coil with refrigerant metering device), a circulation air blower,
a condenser fan, and all necessary internal electrical wiring. The cooling system of these
units is factory-evacuated, charged and performance tested. Refrigerant amount and
type are indicated on rating plate.

C. R-410A REFRIGERANT

All units are factory charged with R-410A refrigerant.

1. Specification of R-410A:

Application: R-410A is not a drop-in replacement for R-22equipment designs must
accommodate its higher pressures. It cannot be retrofitted into R-22 units.

Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22.
Recovery and recycle equipment, pumps, hoses and the like need to have design pres-
sure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-
side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a ser-
vice pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service
pressure rating. 
DOT 4BA400 or DOT BW400.

Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible. R-410A and air should never be mixed in tanks or supply lines, or
be allowed to accumulate in storage tanks. Leak checking should never be done with a
mixture of R-410A and air. 
Leak checking can be performed safely with nitrogen or a
mixture of R-410A and nitrogen.

2. Quick Reference Guide For R-410A

• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-

22. Ensure that servicing equipment is designed to operate with R-410A.

• R-410A refrigerant cylinders are pink.

• R-410A, as with other HFC’s is only compatible with POE oils.

• Vacuum pumps will not remove moisture from POE oil.

• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-

410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for
equipment charging. Post March 1999 cylinders do not have a dip tube and should
be inverted to ensure liquid charging of the equipment.

• Do not install a suction line filter drier in the liquid line.

• A liquid line filter drier is standard on every unit.

• Desiccant (drying agent) must be compatible for POE oils and R-410A.

3. Evaporator Coil / TXV

The thermostatic expansion valve is specifically designed to operate with R-410A. DO

NOT use an R-22 TXV. The existing evaporator must be replaced with the factory
specified TXV evaporator specifically designed for R-410A.

4. Tools Required For Installing & Servicing R-410A Models

Manifold Sets:

-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard

Manifold Hoses:

-Service Pressure Rating of 800 PSIG

!

WARNING

THE MANUFACTURER’S WARRAN-
TY DOES NOT COVER ANY DAM-
AGE OR DEFECT TO THE AIR CON-
DITIONER

CAUSED

BY

THE

ATTACHMENT OR USE OF ANY
COMPONENTS, ACCESSORIES OR
DEVICES (OTHER THAN THOSE
AUTHORIZED BY THE MANUFAC-
TURER) INTO, ONTO OR IN CON-
JUNCTION WITH THE AIR CONDI-
TIONER. YOU SHOULD BE AWARE
THAT THE USE OF UNAUTHO-
RIZED COMPONENTS, ACCES-
SORIES

OR

DEVICES

MAY

ADVERSELY AFFECT THE OPERA-
TION OF THE AIR CONDITIONER
AND MAY ALSO ENDANGER LIFE
AND PROPERTY. THE MANUFAC-
TURER DISCLAIMS ANY RESPON-
SIBILITY FOR SUCH LOSS OR
INJURY RESULTING FROM THE
USE OF SUCH UNAUTHORIZED
COMPONENTS, ACCESSORIES OR
DEVICES.

Содержание RSNM SERIES

Страница 1: ...Y AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN WARNING ANT SAFETY INFORMA 14 SEER ONLY THESE INSTRUCTIONS ARE INENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INST...

Страница 2: ...IX Condensate Drain Indoor Coil 10 X Electrical Wiring 10 A Power Wiring 10 B Electric Heater Kit Instructions 11 C Control Wiring 11 D Internal Wiring 12 E Grounding 12 F Thermostat 12 XI Indoor Air...

Страница 3: ...SUCH DEVICES MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PROPERTY DAMAGE SEVERE PERSONAL INJURY OR DEATH WARNING DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING TO CHANGE BL...

Страница 4: ...year to remove matter that will not wash off with water Several different types of protective coatings are offered in some areas These coatings may provide some benefit but the effectiveness of such...

Страница 5: ...CONTROL BOX ACCESS 211 16 266 7 mm CONDENSATE DRAIN PAN ACCESS FRONT VIEW BOTTOM VIEW ELECTRICAL CONNECTIONS PRIMARY HIGH VOLTAGE ENTRANCE 123 32 43 7 mm 413 32 111 8 mm 59 64 130 5 mm 197 8 505 mm 57...

Страница 6: ...NS 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 14 00 355 6 mm 14 00 355 6 mm 19 05 mm 3 4 IMPORTANT DO NOT SCREW OR DRILL OUTSIDE THE DESIGNATED AREAS ROUND DUCT CONNECTIONS 14 355 6 mm 14 355 6 mm DO...

Страница 7: ...checking can be performed safely with nitrogen or a mixture of R 410A and nitrogen 2 Quick Reference Guide For R 410A R 410A refrigerant operates at approximately 60 higher pressure 1 6 times than R 2...

Страница 8: ...RTANT To prevent transmission of noise or vibration slab should not be connected to building structure 3 The location of the unit should be such as to provide proper access for inspection and servicin...

Страница 9: ...e registers or diffusers are located on the wall or in the ceiling Consider a slab installation when the registers are low on a wall or in the floor On ductwork exposed to outside air conditions of te...

Страница 10: ...red by installation X ELECTRICAL WIRING Field wiring must comply with the National Electrical Code and applicable local codes C E C in Canada A POWER WIRING 1 It is important that proper electrical po...

Страница 11: ...heater kit fuse block and connect ground lead to ground lug on heater kit fuse block Connect the second set of high voltage field power leads to L1 and L3 on the unit contactor Connect ground lead to...

Страница 12: ...sources READ installation instructions in air conditioner thermostat package CAREFULLY because each has some different wiring requirements XI INDOOR AIR FLOW DATA All 208 230 volt units are equipped w...

Страница 13: ...8 1049 1091 1108 Watts 826 806 784 762 734 702 658 626 546 512 CFM 1431 1394 1348 1302 1258 1208 1140 1030 849 557 11x9 Low RPM 540 579 633 686 724 776 831 868 1035 1076 3 5 Low 1225 1575 1 2 Watts 48...

Страница 14: ...1032 1083 Watts 704 694 675 655 638 606 581 548 464 CFM 1279 1237 1196 1151 1098 1032 950 846 717 13 11x9 Low RPM 490 539 598 653 709 772 811 887 928 3 5 Low 1225 1575 1 2 Watts 401 400 393 391 381 3...

Страница 15: ...38 1386 1335 1283 1231 1180 1128 1076 11x9 RPM 598 617 662 714 758 800 849 876 913 951 1 2 Watts 244 231 237 254 270 285 304 313 326 340 2 Speed CFM 1740 1695 1649 1604 1558 1513 1467 1422 1376 1331 X...

Страница 16: ...8 1154 1101 1047 11x9 RPM 602 619 668 715 757 801 844 878 918 954 1 2 Watts 238 227 236 251 266 281 296 307 320 333 2 Speed CFM 1724 1678 1632 1586 1540 1495 1449 1403 1357 1311 X 13 Motor RPM 639 671...

Страница 17: ...HEAT Unit should stop Wait 5 minutes then raise temperature setting to above room temperature After about 30 to 50 seconds auxiliary heaters if installed should come on 9 Check the refrigerant charge...

Страница 18: ...n an automatic open overload device or blow a fuse Poor electrical service can cause nuisance tripping in overloads or blow fuses IMPORTANT The compressor has an internal overload protector Under some...

Страница 19: ...4 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 3400 1604 3400 1604 No Motors HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 875 875 875 875...

Страница 20: ...Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 4200 1982 4200 1982 No Motors HP 1 at...

Страница 21: ...Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11x9 279 4x...

Страница 22: ...609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 3400 1604 3400 1604 No Motors HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP 1 at 1 3 HP Motor...

Страница 23: ...er Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 609 6 Drive Type No Speeds Direct 1 Direct 1 Direct 1 Direct 1 CFM L s 3400 1604 3400 1604 4200 1982 4200 1982 No Motors HP 1...

Страница 24: ...e Type No Speeds Direct 1 Direct 1 CFM L s 4000 1888 4000 1888 No Motors HP 1 at 1 3 HP 1 at 1 3 HP Motor RPM 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal No Used Diameter in mm 1 11x9 279...

Страница 25: ...4 5 4 5 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 12 8 12 8 17 17 13 5 13 5 17 9 17 9 14 7 14 7 21 2 21 2 16 16 26 4 26 4 Amps LRA 54 54 73 73 95 95 96 7 96 7...

Страница 26: ...2 5 3 3 3 5 3 5 4 4 4 5 4 5 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 Amps RLA 13 5 13 5 14 1 14 1 12 8 12 8 17 17 13 5 13 5 17 9 17 9 14 7 14 7 21 2 21 2 16 16 26 4 26 4 Amps LRA 58 3 58...

Страница 27: ...07J 1 1 5 4 7 2 18 42 24 56 26 30 36 41 40 40 45 45 33 38 35 40 10J 2 1 7 2 9 6 24 57 32 76 34 7 40 47 54 50 50 60 60 44 50 45 50 15J 3 2 10 8 14 4 36 85 49 13 52 60 69 79 70 70 80 80 65 75 70 80 20J...

Страница 28: ...50 60 No Heat 24 24 30 35 30 35 24 24 30 35 30 35 10C 2 1 7 2 9 6 24 57 32 76 20 23 1 29 33 30 30 35 35 25 29 25 30 15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 42 48 45 45 50 50 38 44 40 45 20C 4 2 14 4 1...

Страница 29: ...5 05J 1 1 3 6 4 8 12 28 16 38 17 33 20 30 33 35 45 35 45 22 25 25 25 07J 1 1 5 4 7 2 18 42 24 56 26 30 40 45 40 40 45 45 33 38 35 40 10J 2 1 7 2 9 6 24 57 32 76 34 7 40 51 58 60 60 60 60 44 50 45 50 1...

Страница 30: ...50 60 No Heat 27 27 30 40 30 40 27 27 30 40 30 40 10C 2 1 7 2 9 6 24 57 32 76 20 23 1 33 37 35 35 40 40 25 29 25 30 15C 3 2 10 8 14 4 36 85 49 13 30 1 34 7 46 51 50 50 60 60 38 44 40 45 20C 4 2 14 4 1...

Страница 31: ...31 FIGURE 7 WIRING DIAGRAM RSNM...

Страница 32: ...32 FIGURE 8 WIRING DIAGRAM RSNM...

Страница 33: ...33 FIGURE 9 WIRING DIAGRAM RSPM WITH X 13 BLOWER MOTOR...

Страница 34: ...34 FIGURE 10 WIRING DIAGRAM RSPM WITH X 13 BLOWER MOTOR...

Страница 35: ...35 FIGURE 11 2 TON AIR CHARGING CHART...

Страница 36: ...36 FIGURE 12 2 5 TON AIR CHARGING CHART...

Страница 37: ...37 FIGURE 13 3 0 TON CHARGING CHART...

Страница 38: ...38 FIGURE 14 3 5 TON CHARGING CHART...

Страница 39: ...39 FIGURE 15 4 0 TON CHARGING CHART...

Страница 40: ...PERATURE TO OUTDOOR COIL PLACE AN X ON THE APPROPRIATE CHART WHERE THE SUCTION AND LIQUID PRESSURES CR OSS IF X IS BELOW AMBIENT TEMPERATURE LINE ADD CHARGE AND REPEAT STEP 3 IF X IS ABOVE AMBIENT TEM...

Страница 41: ...weat Low evaporator airflow Increase speed of blower or reduce restriction replace air filter High head low vapor pressures Restriction in liquid line expansion device or filter drier Remove or replac...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44 CM 0408...

Отзывы: