Start the furnace and measure the time required to burn one cubic foot of gas. Prior to
checking the furnace input, make certain that all other gas appliances are shut off, with
the exception of pilot burners. Time the meter with only the furnace in operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS):
The main
burner orifices in your furnace and in these kits are sized for the nameplate input and
intended for installations at elevations up to 2,000 feet in the USA or Canada, or for ele-
vations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated
at the factory. For elevations above 2,000 feet (610 meters)
IN THE USA ONLY
(see
ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1,000
feet (305 meters) above sea level.
NOTICE: DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD
IS UNLAWFUL IN CANADA (REFER TO CAN/CGA 2.17). UNITS INSTALLED IN
ALTITUDES GREATER THAN 2,000 FEET (610 METERS) MUST BE SHIPPED FROM
THE FACTORY OR FROM A FACTORY AUTHORIZED CONVERSION STATION
WITH THE HEATING INPUT DERATED BY 10% SO AS TO OPERATE PROPERLY IN
ALTITUDES FROM 2,000 - 4,500 FEET (610 - 1,373 METERS).
F. CONDENSATE DRAIN
The evaporator coil condensate drain ends with a threaded 3/4” nominal PVC stub. A
trap is built in for proper condensate drainage and to prevent debris from being drawn
into the unit. Do not connect the drain to a closed sewer line. Connection to a vented
sewer line is allowed. It is recommended that a PVC cement not be used so that the
drain line can be easily cleaned in the future.
IMPORTANT: DO NOT INSTALL AN EXTERNAL TRAP. DOING SO CAN CAUSE
IMPROPER DRAINAGE OF THE CONDENSATE AND RESULT IN FLOODING WITH-
IN THE UNIT.
VIII.WIRING
A. POWER SUPPLY
!
WARNING
TURN OFF THE MAIN ELECTRICAL POWER AT THE BRANCH CIRCUIT DISCON-
NECT CLOSEST TO THE UNIT BEFORE ATTEMPTING ANY WIRING. FAILURE
TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL
INJURY OR DEATH.
ONE
1
21
1
30
1
34
1
39
3
45
40,000
TEN
13
30
15
0
15
36
16
30
37
30
ONE
0
54
1
0
1
3
1
6
2
30
60,000
TEN
9
0
10
0
10
24
11
0
25
0
ONE
0
41
0
45
0
47
0
50
1
53
80,000
TEN
6
45
7
30
7
48
8
15
18
45
ONE
0
33
0
36
0
38
0
40
1
30
100,000
TEN
5
24
6
0
6
15
6
36
15
0
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
OR LP GAS
INPUT
BTU/HR
METER
SIZE
CU. FT.
HEATING VALUE OF GAS BTU PER CU. FT.
900
1000
1040
1100
2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
TABLE
3
25
Содержание RRNL-B
Страница 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Страница 40: ...FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8 40...
Страница 77: ...FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS 77...
Страница 78: ...FIGURE 36 WIRING DIAGRAM 78...
Страница 79: ...FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL 79...
Страница 80: ...FIGURE 38 WIRING DIAGRAM 80...
Страница 81: ...FIGURE 39 WIRING DIAGRAM 81...
Страница 82: ...FIGURE 40 WIRING DIAGRAM 82...
Страница 83: ...FIGURE 41 WIRING DIAGRAM 83...
Страница 84: ...FIGURE 42 WIRING DIAGRAM 84...
Страница 85: ...FIGURE 43 WIRING DIAGRAM 85...
Страница 86: ...86 FIGURE 44 WIRING DIAGRAM...
Страница 87: ...87 FIGURE 45 WIRING DIAGRAM...
Страница 88: ...FIGURE 46 SYSTEM CHARGE CHARTS XVI CHARGE CHARTS RNL RPL 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 88...
Страница 90: ...FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 90...
Страница 91: ...FIGURE 49 SYSTEM CHARGE CHARTS RNL RPL 3 1 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 91...
Страница 92: ...FIGURE 50 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 92...
Страница 94: ...FIGURE 52 SYSTEM CHARGE CHARTS RPL 5 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 94...
Страница 95: ...FIGURE 53 SYSTEM CHARGE CHARTS RPL 5 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 95...
Страница 96: ...FIGURE 54 SYSTEM CHARGE CHARTS RRRL 2 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 96...
Страница 97: ...FIGURE 55 SYSTEM CHARGE CHARTS RRRL 2 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 97...
Страница 98: ...FIGURE 56 SYSTEM CHARGE CHARTS RRRL 3 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 98...
Страница 99: ...FIGURE 57 SYSTEM CHARGE CHARTS RRRL 3 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 99...
Страница 100: ...FIGURE 58 SYSTEM CHARGE CHARTS RRRL 4 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 100...
Страница 101: ...FIGURE 59 SYSTEM CHARGE CHARTS RRRL 4 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 101...
Страница 102: ...FIGURE 60 SYSTEM CHARGE CHARTS RRRL 5 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 102...
Страница 103: ...FIGURE 61 SYSTEM CHARGE CHARTS RRRL 5 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 103...
Страница 108: ...108 CM 0314...