C. LP CONVERSION TWO STAGE GAS HEAT
Convert the valve to use liquefied petroleum (LP) gas by replacing with the gas valve sup-
plied in the conversion kit. The LP gas valve maintains the proper manifold pressure for LP
gas. The correct burner LP orifices are included in the kit.
IMPORTANT: To remove the natural gas valve, remove the four screws securing the mani-
fold pipe to the burner tray. Remove the manifold pipe with gas valve attached.
NOTE:
Order the correct LP conversion kit from the furnace manufacturer.
See
Conversion Kit Index shipped with unit for proper LP kit number. Furnace conver-
sion to LP gas must be performed by a qualified technician.
D. NOx MODELS
When converting units equipped with NOx inserts to LP gas, the stainless steel mesh
inserts in the entrance of the tubular exchangers are not required to meet SCAQMD NOx
emission levels. Carefully remove these inserts before firing this furnace on LP gas. This
furnace is not designed to operate on LP gas with the NOx inserts in place.
Step by step instructions on removing the NOx inserts and retaining rod are included in the
Conversion Kit Installation Instructions.
E. ADJUSTING OR CHECKING FURNACE INPUT
– Natural Gas Line Pressure 5” - 10.5” W.C.
– LP Gas Line Pressure 11” - 13” W.C.
– Natural Gas Manifold Pressure 3.5” W.C
– LP Gas Manifold Pressure - 10” W.C.
Supply and manifold pressure taps are located on the gas valve body 1/8” N.P.T.
Use a properly calibrated manometer gauge for accurate gas pressure readings.
Only small variations in the gas flow should be made by means of the pressure regulator
adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch
supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas con-
trol valve.
To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw
clockwise to increase pressure or counterclockwise to decrease pressure.
Then replace
the regulator cap securely.
Any necessary major changes in the gas flow rate should be made by changing the size of
the burner orifices. To change orifice spuds, shut off the manual main gas valve and
remove the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings apply. For high altitudes (elevations
over 2,000 ft.), see conversion kit index 92-21519-47 for derating and orifice spud sizes.
Check of input is important to prevent over-firing of the furnace beyond its design-
rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use
the following table or formula to determine input rate.
Heating Value of Gas
(BTU/Cu. Ft.) x 3600
Cu. Ft. Per Hr. Required =
Time in Seconds
(for 1 Cu. Ft.) of Gas
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum
gases (at 11 inches water column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
TABLE
2
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Nominal
Iron Pipe
Size, Inches
10
20
30
40
50
60
70
80
90
100
125 150
275
189
152
129
114
103
96
89
83
78
69
63
567
393
315
267
237
217
196
182
173
162
146 132
1,071
732
590
504
448
409
378
346
322
307
275 252
2,205 1,496 1,212 1,039
913
834
771
724
677
630
567 511
3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023
976
866 787
6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
1/2
3/4
1
1-1/4
1-1/2
2
Length of Pipe, Feet
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4
”
IPS required.
!
WARNING
THIS UNIT IS EQUIPPED AT THE FACTORY FOR USE ON NATURAL GAS ONLY.
CONVERSION TO LP GAS REQUIRES A SPECIAL KIT SUPPLIED BY THE DIS-
TRIBUTOR OR MANUFACTURER. MAILING ADDRESSES ARE LISTED ON THE
FURNACE RATING PLATE, PARTS LIST AND WARRANTY. FAILURE TO USE
THE PROPER CONVERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POI-
SONING, EXPLOSION, PERSONAL INJURY, PROPERTY DAMAGE OR DEATH.
24
Содержание RRNL-B
Страница 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Страница 40: ...FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8 40...
Страница 77: ...FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS 77...
Страница 78: ...FIGURE 36 WIRING DIAGRAM 78...
Страница 79: ...FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL 79...
Страница 80: ...FIGURE 38 WIRING DIAGRAM 80...
Страница 81: ...FIGURE 39 WIRING DIAGRAM 81...
Страница 82: ...FIGURE 40 WIRING DIAGRAM 82...
Страница 83: ...FIGURE 41 WIRING DIAGRAM 83...
Страница 84: ...FIGURE 42 WIRING DIAGRAM 84...
Страница 85: ...FIGURE 43 WIRING DIAGRAM 85...
Страница 86: ...86 FIGURE 44 WIRING DIAGRAM...
Страница 87: ...87 FIGURE 45 WIRING DIAGRAM...
Страница 88: ...FIGURE 46 SYSTEM CHARGE CHARTS XVI CHARGE CHARTS RNL RPL 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 88...
Страница 90: ...FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 90...
Страница 91: ...FIGURE 49 SYSTEM CHARGE CHARTS RNL RPL 3 1 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 91...
Страница 92: ...FIGURE 50 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 92...
Страница 94: ...FIGURE 52 SYSTEM CHARGE CHARTS RPL 5 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 94...
Страница 95: ...FIGURE 53 SYSTEM CHARGE CHARTS RPL 5 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 95...
Страница 96: ...FIGURE 54 SYSTEM CHARGE CHARTS RRRL 2 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 96...
Страница 97: ...FIGURE 55 SYSTEM CHARGE CHARTS RRRL 2 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 97...
Страница 98: ...FIGURE 56 SYSTEM CHARGE CHARTS RRRL 3 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 98...
Страница 99: ...FIGURE 57 SYSTEM CHARGE CHARTS RRRL 3 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 99...
Страница 100: ...FIGURE 58 SYSTEM CHARGE CHARTS RRRL 4 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 100...
Страница 101: ...FIGURE 59 SYSTEM CHARGE CHARTS RRRL 4 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 101...
Страница 102: ...FIGURE 60 SYSTEM CHARGE CHARTS RRRL 5 TON COOLING 1st LOW STAGE CHARGE CHART R 410A REFRIGERANT 102...
Страница 103: ...FIGURE 61 SYSTEM CHARGE CHARTS RRRL 5 TON COOLING 2nd HIGH STAGE CHARGE CHART R 410A REFRIGERANT 103...
Страница 108: ...108 CM 0314...