If the vent piping passes through a closed space, wrap the vent
pipe with inflammable insulation material that is at least 3/4
thick. DO NOT let the insulation material make contact with
flammable materials. A minimum clearance of 3

between the

vent pipe and ceiling should be maintained. Be sure to follow
local codes.

For maintenance and inspection purposes, the following holes
are required to be made.

Two (2) inspection openings that allow access to venting.
One (1) of these openings should be close to where the
vent pipe enters the ceiling. The other opening should be
near the vent termination.
A ventilation hole with a 16 sq. in. opening should be
made at least every 10 feet.

: Vent pipes must be completely insulated with

inflammable material when installed in alcoves, closets, and
garages and must not touch any flammable material.

NOTICE

Venting Through Closed Spaces

A UL approved vent adapter is required
for vent connection.
Read the following instructions before
installation.

Test fit the adapter over the water
heater collar before proceeding. Adjust
clamp as needed.

With an alcohol wipe, clean inside
surface "A" of adapter and outside
surface of "B" of heater collar.

Apply 1/4" wide bead of high
temperature silicone (500 F) around
outside of heater collar "B".

Slide adapter end "A" down over heater
collar "B" as far as it will go.

o

Vent Adapter

Tighten the clamp around the collar.

Inspect the inside of the adapter to
verify that the collar and adapter are
sealed. If more sealant is required,
apply sealant to a flat tool, then spread
around the collar edge on inside of
adapter.

Ensure that the clamp does not interfere
with the damper shaft.

Follow the vent adapter

manufacturer's instructions

NOTICE:

In certain conditions, installations in
unconditioned space or having long
horizontal or vertical runs may accumulate
condensate.

In order to prevent condensate from
draining back into the water heater, we
recommend a condensate trap and drain to
be installed in a horizontal vent section as
close as practical to the water heater vent
connection.

Draining the Condensate

Condensate is known to be acidic; refer to
local, state (provincial) or federal codes
for proper handling methods.

13

Содержание Residential Indoor Gas Tankless Water Heater

Страница 1: ...ion Instructions for the Installer 136 000 BTU Max Input Recognize this symbol as an indication of Important SafetyInformation California Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer birthdefects or other reproductive harm WARNING If the in formation in these instructions is not followed exactly a fire or explosion may result causing prope...

Страница 2: ...he appliance Proof of the original purchase date is needed to obtain service under the warranty Staple sales slip or cancelled check here READ THIS MANUAL Inside you will find many helpful hints on how to use and maintain your water heater properly A little preventive care on your part can save you time and money over the life of your water heater You ll find many answers to common problems in the...

Страница 3: ...ire explosion or asphyxiation from carbon monoxide never operate this water heater unless it is installed properly and has an adequate air supply for proper operation Be sure to inspect the flue terminal for proper installation at initial start up and at least annually thereafter Refer to the Care and Cleaning section of this manual for more information regarding flue terminal inspection DANGER IN...

Страница 4: ...l panel was set at 110 F before it was shipped from the factory o The illustration to the bottom left illustrates the control panel and how to adjust the water temperature Notice When this water heater is supplying general purpose hot water requirements for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of...

Страница 5: ...r LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look and smell for gas leaks Use a soapy solution to check all gas fittings and connections Bubbling at a connection indicates a leak that must be corrected When smelling to detect a gas leak be sure to...

Страница 6: ...o prevent property damage personal injury or loss of life California Law requires that residential water heaters must be braced anchored or strapped to resist falling or horizontal displacement due to earthquake motions For residential water heaters up to 52 gallon capacity a brochure with generic earthquake bracing instructions can be obtained from Office of the State Architect 400 P Street Sacra...

Страница 7: ... fire which may result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc If the water heater is installed in a garage it should be installed so that the direct ignition system and main burner are no less than 18 inches above the garage floor Raising the gas fired water heater will reduc...

Страница 8: ...r combustion and ventilation air must be made A confined space is one having a volume of less than 50 cubic feet per 1000 Btuh of the aggregate input of all appliances within that space The air must be supplied through two permanent openings of equal area One is to be located within 12 above the floor and the other is to be located within 12 below the ceiling The minimum net free area of each open...

Страница 9: ...oors additional water pressure 0 44 psi ft must be ensured The measurement should be calculated by the distance between the water inlet of the water heater ground level to the hot water faucet upper floor level Well water systems should be set at a range of 50 60 psi When the water is supplied from a water supply tank the height of the tank and the diameter of the pipes and their relation to water...

Страница 10: ...lief valve and to prevent water damage If the relief valve on the system discharges periodically a problem exists and service to the water system is required Notice Notice Notice Relief Valve Notice The above illustrates a pressure only relief valve If local codes require a combination temperature and pressure relief valve be installed an extension piece may be needed Install a Check Valve between...

Страница 11: ...sion could result in hazardous operating conditions 11 Gas Supply The supplied Manual Gas Appliance Shutoff Valve must be installed at the gas connection of the water heater at the time of installation see diagram to the left The branch gas supply line to the water heater should be clean 3 4 black steel pipe or other approved gas piping material A ground joint union or ANSI design certified semi r...

Страница 12: ...on monoxide NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting section of this manual WARNING Use UL approved Category III Stainless Steel vent material only No other vent material is permitted WARNING Refer to page 7 for clearances to combustible material MAXIMUM VENT LENGTH The system will not operate if there i...

Страница 13: ...the adapter over the water heater collar before proceeding Adjust clamp as needed With an alcohol wipe clean inside surface A of adapter and outside surface of B of heater collar Apply 1 4 wide bead of high temperature silicone 500 F around outside of heater collar B Slide adapter end A down over heater collar B as far as it will go o Vent Adapter Tighten the clamp around the collar Inspect the in...

Страница 14: ... water heater Additional Considerations 14 Horizontal Vent Terminal Location Do Not install vent terminal under any patio or deck To help prevent moisture from freezing on walls and under eaves do not locate vent terminal on the side of a building with prevailing winter winds Do Not terminate vent pipe directly on brick or masonry surfaces Use a rust resistant sheet metal backing plate 2 x 2 feet ...