Active protection occurs under the following conditions:
1) Flash Code 2 -
System Pressure Trip
Condition: Four consecutive compressor protector trips occur where the
average run time until trip is between 1 minute and 15 minutes
Possible causes:
Low suction pressure
• Low pressure switch is open
• Low system charge
Blocked condenser coil
Restricted condenser air flow
Active Thermostat Reaction:
The thermostat will cycle the system ON for 5 minutes and OFF for
five minutes to verify system fault. If this ON/OFF cycling repeats for
30 ten-minute cycles, the thermostat concludes there is a system
problem and implements a hard lockout.
2) Flash Code 3 -
Short Cycling
Condition: A pattern of short cycling emerges where the run time for the
previous four cycles is less than three minutes each.
Possible causes:
High head pressure
• High pressure switch is open
• System overcharged
• Non-condensables in system
Faulty thermostat
Intermittent contactor
Active Thermostat Reaction:
The thermostat will cycle the system ON for 5 minutes and OFF for
five minutes to verify the system fault. If this ON/OFF cycling repeats for
30 ten-minute cycles, the thermostat concludes there is a system
problem and implements a hard lockout.
3) Flash Code 4 -
Locked Rotor
Condition: The compressor internal overload trips where the average run
time is less than 15 seconds.
Possible causes:
Bad run capacitor
Low line voltage
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Faulty hard start components
Active Thermostat Reaction:
The thermostat implements a hard lockout once this error is sensed.
4) Flash Code 6 -
Open Start Circuit
Condition: Current is detected in the run circuit but not in the start circuit.
Possible causes:
Bad run capacitor
Open circuit in compressor start wiring or connections.
Compressor start winding is damaged
Active thermostat reaction:
The thermostat implements a hard lockout after 3 hours.
5) Flash Code 7 -
Open Run Circuit
Condition: Open circuit in compressor run wiring or connections.
Compressor run winding is damaged.
Active Thermostat Reaction:
The thermostat implements a hard lockout after 3 hours.
Содержание RACA14 Series
Страница 39: ...39 FIGURE 15 WIRING DIAGRAM ...
Страница 40: ...40 FIGURE 16 WIRING DIAGRAM ...
Страница 41: ...41 FIGURE 17 WIRING DIAGRAM ...
Страница 42: ...42 FIGURE 18 WIRING DIAGRAM ...
Страница 44: ...44 FIGURE 20 SYSTEM CHARGE CHARTS RACA 14 15 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 45: ...45 FIGURE 21 SYSTEM CHARGE CHARTS RACA 14 15 2 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 46: ...46 FIGURE 22 SYSTEM CHARGE CHARTS RACA 14 15 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 47: ...47 FIGURE 23 SYSTEM CHARGE CHARTS RACA 14 15 3 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 48: ...48 FIGURE 24 SYSTEM CHARGE CHARTS RACA 14 15 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 49: ...49 FIGURE 25 SYSTEM CHARGE CHARTS RACA 15 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 CM 0914 ...