FIGURE 26
COMFORT ALERT DIAGNOSIS CHART
SINGLE PHASE UNIT
Status
LED
Status
LED
Description
Status
LED
Troubleshooting
Informatio
n
Green “POWER”
Module has power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat demand signal
1. Compressor internal overload is open
Y1 is present, but the
2. Broken wire or connector is not making contact
compressor is not
3. Low pressure switch open, if present
running
4.
4.
4.
Compressor contactor has failed open
Yellow “ALERT”
Long Run Time
1. Low refrigerant charge
Flash Code 1
Compressor is
2. Evaporator blower is not running
running extremely
3. Evaporator coil is frozen
long run cycles
4. Faulty TXV
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
Yellow “ALERT”
System Pressure Trip
1.
Flash Code 2
Discharge or suction
2.
Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of limits or
3.
Condenser fan is not running
compressor overloaded
Return
If low pressure switch is present, check flash code (1)
information
air duct has substantial leakage
Yellow “ALERT”
Short Cycling
1.
Thermostat demand signal is intermittent
Hot gas sensor defective, if present
Flash Code 3
Compressor is running
2.
Time delay relay defective, if present
only briefly
3.
Yellow “ALERT”
Locked Rotor
1. Run capacitor has failed
Flash Code 4
2. Low line voltage (contact utility if voltage at disconnect is low)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Yellow “ALERT”
Open Circuit
1. Compressor contactor has failed open
Flash Code 5
2. High pressure switch is open, If present
3. Open circuit in compressor supply wiring or connections
4. Unusually long compressor protector reset time due to
extreme ambient temperature
5. Compressor windings are damaged
Yellow “ALERT”
Open Start Circuit
1. Run capacitor has failed
Flash Code 6
Current only in run circuit
2. Open circuit in compressor start wiring or connections
3. Compressor start winding is damaged
Yellow “ALERT”
Open Run Circuit
1. Open circuit in compressor run wiring or connections
Flash Code 7
Current only in start circuit
2. Compressor run winding is damaged
Yellow “ALERT”
Welded Contactor
1. Compressor contactor has failed closed
Flash Code 8
Compressor always runs
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Low Voltage
1. Control circuit transformer is overloaded
Flash Code 9
Control circuit < 17VAC
2. Low line voltage (contact utility if voltage at disconnect is low)
9 2 - 1 0 1 5 3 4 - 0 3 - 0 0
High head pressure
Содержание RACA14 Series
Страница 39: ...39 FIGURE 15 WIRING DIAGRAM ...
Страница 40: ...40 FIGURE 16 WIRING DIAGRAM ...
Страница 41: ...41 FIGURE 17 WIRING DIAGRAM ...
Страница 42: ...42 FIGURE 18 WIRING DIAGRAM ...
Страница 44: ...44 FIGURE 20 SYSTEM CHARGE CHARTS RACA 14 15 2 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 45: ...45 FIGURE 21 SYSTEM CHARGE CHARTS RACA 14 15 2 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 46: ...46 FIGURE 22 SYSTEM CHARGE CHARTS RACA 14 15 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 47: ...47 FIGURE 23 SYSTEM CHARGE CHARTS RACA 14 15 3 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 48: ...48 FIGURE 24 SYSTEM CHARGE CHARTS RACA 14 15 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 49: ...49 FIGURE 25 SYSTEM CHARGE CHARTS RACA 15 5 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 CM 0914 ...