While scroll compressors usually do not require
crankcase heaters, there are instances when a
heater should be added. Refrigerant migration
during the off cycle can result in a noisy start up.
Add a crankcase heater to minimize refrigerant
migration and to help eliminate any start up noise
or bearing wash out.
NOTE:
A crankcase heater should be installed if:
• The system charge exceeds the values listed in
the adjacent tables,
• The system is sub ect to low voltage variations,
or
• hen a low ambient control is used for system
operation below 55°F.
All heaters are located on the lower half of the
compressor shell. Its purpose is to drive refrigerant
from the compressor shell during long off cycles,
thus preventing damage to the compressor during
start-up.
At initial start-up or after extended shutdown
periods, make sure the heater is energized for at
least 12 hours before the compressor is started.
(Disconnect switch is on and wall thermostat is off.)
Compressor Crankcase Heat (CCH)
High- and Low-Pressure Controls (HPC and LPC)
HPC and LPC are factory installed on
RA17**AJ2CB. These controls keep the
compressor from operating in pressure ranges
which can cause damage to the compressor. Both
controls are in the low-voltage control circuit.
The high-pressure control (HPC) is an automatic-
reset which opens near 610 PSIG and closes near
420 PSIG.
The low-pressure control (LPC) is an automatic-
reset which opens near 15 PSIG and closes near
40 PSIG.
CAUTION:
The compressor has
an internal overload protector. Under some
conditions, it can take up to 2 hours for this
overload to reset. Make sure overload has had
time to reset before condemning the compressor.
COMPONENTS AND CONTROLS
Components
MAXIMUM SYSTEM CHARGE VALUES
Charge Limit
Without Crankcase
Heat (1 Phase)
RA17
Model
Size
Compressor
Model Number
24AJ
36AJ
48AJ
60AJ
ZPS20K5E-PFV-130
ZPS30K5E-PFV-130
ZPS40K5E-PFV-130
ZPS49K5E-PFV-130
9.6 lbs.
9.6 lbs.
12 lbs.
12 lbs.
Содержание RA17 Series
Страница 16: ...16 N R Application not recommended INSTALLATION Table 2 Tubing...
Страница 17: ...17 N R Application not recommended INSTALLATION Table 3 Tubing...
Страница 54: ...54 R C For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...
Страница 55: ...55 WIRING DIAGRAMS Wiring Diagrams...
Страница 56: ...56 NOTES...