Rheem P-M207 Скачать руководство пользователя страница 38

FLAME ROLL-OUT SAFETY SWITCH

Atmospheric 

heaters 

are

equipped with a thermal cutoff
device to prevent flame roll-out
in the event the heat exchang-
er becomes blocked. This is a
"single-use" type fusible link or
thermal  fuse,  that  must  be
replaced  when  disabled  by  an

over-temperature  condition,  caused  by  excessive
restriction in the heat exchanger flue passage.

HIGH LIMITS

The heater is equipped with two automatic high limits.
Both are located in the inlet/outlet header. Both are set
to open at 135°F.

38

1.   Make  sure  the  pool  filter  is

clean  before  adjusting  the
switch.

2.   Set  the  heater  control  to  the

OFF mode.

3.   Turn  the  filter  pump  on  and

confirm  that  the  pressure

TWO-SPEED PUMPS

In some cases, the flow on the low-speed is insufficient
to operate the heater. This is apparent when the water
pressure  switch  cannot  be  further  adjusted  or  if  the
heater makes banging noises or shuts off on high limit.
In these cases, the pump must be run at high speed
when heating the water.

PRESSURE SWITCH 
ADJUSTMENT RANGE

CAUTION:

Do  not  operate  the  heater  without  the

function of a properly adjusted water pressure switch
or flow switch.

5 FT.

MAX

POOL OR SPA

MAY REQUIRE ADJUSTMENT

FOR LOWER PRESSURE

MAY REQUIRE ADJUSTMENT

FOR HIGHER PRESSURE

5 FT.

MAX

switch is closed (use a multimeter to check). If the
pressure switch fails to close, either the switch set-
ting  is  too  high  or  not  enough  pressure  is  being
supplied by the filter pump.

NOTE:

If  heater  is  installed  outside  of  the  limits

shown,  a higher pressure rated (11 psi) switch may be
used. A flow switch, mounted and wired adjacent to the
heater,  may  be  used  in  place  of  the  factory-mounted
pressure  switch.  See  Parts  List  (page  52)  for  11  psi
water pressure switch.

WATER PRESSURE SWITCH

The  water  pressure  switch  ensures  that  the  heater
operates only when the filter pump is in operation. It is
located  on  the  inlet/outlet  header.  It  is  factory  set  at
1.75 PSI for deck-level installations.  When the heater
is located below the level of the spa or pool, it may be
necessary  to  adjust  the  pressure  switch  to  compen-
sate  for  the  no-flow  static  head.  If    it  is  necessary  to
adjust  the  water  pressure  switch,  utilize  the  following
procedure:

WATER PRESSURE SWITCH ADJUSTMENT

Adjustment
Knob

TIME CLOCK/FIREMAN’S SWITCH

4. Turn the heater ON.
5.  Manually turn the pressure adjustment knob clock-

wise  until  the  heater  shuts  off.  (A  flat  screwdriver
may be necessary if knob is too tight.)

6.  Slowly turn the adjustment knob counter-clockwise

until the heater calls for heat again.

7.  Turn an additional 1/2 turn counter-clockwise.
8.  While the heater is running, check the adjustment

by turning the pump off and on several times. The
burners  should  shut  off  immediately  when  the
pump is turned off. If it does not, repeat the above
steps until proper operation is observed.

To  operate  the  heater  with  a  time  clock,  connect  the
timer to the fireman’s switch connection in the heater’s
wiring.    The  time  clock  should  be  of  the  dual  switch
type  and  set  to  shut  off  the  call  for  heat  to  the  pool
heater 15 to 20 minutes prior to shutting down the pool
pump.    On  millivolt  heaters  the  fireman’s  switch  con-
nection is a wire nut located in the Violet/Black wiring
between the manual toggle switch and the gas valve.
For  AFT  heaters  the  fireman’s  switch  connection  is
located on the 14-pin header connected to the digital
control board.  Splice into the red wire jumper tagged
“Where necessary add “Fireman’s” switch circuit here”
to connect the time clock. 

The fireman’s switch con-

nection on both millivolt and AFT heaters must be
a  dry  contact  and  must  not  supply  power  to  the
heater.  Powering the fireman’s switch connection
externally may damage the heater, and is not cov-
ered by warranty.

Millivolt  heaters:    Do  not  exceed  15ft  of  total  wiring
using  14 AWG  stranded  copper  wire  rated  for  105ºC
(221ºF) minimum.

AFT heaters:  Do not exceed 50ft of total wiring using
18 AWG stranded copper wire rated for 105ºC (221ºF)
minimum.

NOTE:

When using a time clock, the heater will dis-

play “

Clock/ Fireman Sw

” when the fireman’s switch

is open, indicating that the time clock has shut off the
call for heat.

Содержание P-M207

Страница 1: ...your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and servic...

Страница 2: ...age the heater providing the water is balanced Automatic chemical dosing devices and salt chlorinators are usually more efficient in heated water unless controlled they can lead to excessive chlorine...

Страница 3: ...r Reversal Procedure 26 Electrical Wiring 26 Millivolt Models 26 Advanced Flame Technology AFT Models 27 Transformer Wiring 28 Wiring Diagram Millivolt Mechanical Therm 29 Wiring Diagram AFT Models At...

Страница 4: ...s an easy task The upper front panel of the heater contains the control center that allows you to turn the heater On or Off and adjust the temperature set tings for the pool or spa The temperature ran...

Страница 5: ...P Read the safety information above 2 Set the thermostat on the lowest setting 3 Turn On Off switch to the Off position 4 Remove heater door panel 5 Push in gas control knob slightly and turn clockwis...

Страница 6: ...ormation above 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do...

Страница 7: ...manual gas control to the heater SECTION 2 CAUTION Elevated water temperature can be hazardous The U S Consumer Product Safety Commission has these guidelines 1 Spa water temperatures should never exc...

Страница 8: ...re not moving water or your gauge is broken Try to get the pump to run at its normal flow rate CAUTION Combustion air must not be contaminat ed by corrosive chemical fumes which can damage the heater...

Страница 9: ...higher temperatures are reached Operating the heater for prolonged periods with pool water below 50 F can seriously damage the heater and is not cov ered by the warranty For cold climate areas please...

Страница 10: ...the heater STANDARD UNIT POLYMER HEADERS ASME UNIT CAST IRON HEADERS 1 Pagoda top 1 Pagoda top 2 2 CPVC union with O rings 2 2 In Out flanges 2 3 Plastic pipe finish flange for gas line 3 1 1 2 flange...

Страница 11: ...ool Heaters All heaters can be used either indoor or outdoors The appropriate top designated for each type of use is required If necessary the top can be changed at a later date to change from outdoor...

Страница 12: ...NS Top 30 Drafthood Back 6 Front Alcove Open Right Side 12 Water Side Vent 6 Left Side 6 Floor 0 Opposite Water Side OUTDOOR INSTALLATION Top Unobstructed Outdoor Stack Top 36 Stackless Top Floor 0 Ri...

Страница 13: ...any building The top surface of the heater shall be at least 3 ft above any forced air inlet or intake ducts located within 10 ft horizontally For installations in Canada pool heaters shall not be in...

Страница 14: ...eld Supplied Ea Pallet Anchor Bracket Use hole closest to unit 4 total 1 1 4 x 1 3 4 S S Tapcon Bolt Washer Field Supplied Ea Pallet Anchor Bracket Use hole closest to unit 4 total 2 x 6 x 1 8 Pallet...

Страница 15: ...t Heater must always be vented to the outside See Vent Piping section pg 18 19 for details Minimum allowable space is shown on the nameplate OUTDOOR STACK INDOOR STACK NOTE The outdoor and indoor stac...

Страница 16: ...ane gas is MP a Millivolt heater using natural gas is MN Prefix C is for cast iron ASME headers P is for plastic polymer headers Suffix X is for cupro nickel tubing C is for copper tubing EXAMPLE P R4...

Страница 17: ...SME headers P is for plastic polymer headers Suffix X is for cupro nickel tubing C is for copper tubing EXAMPLE P R407A EN X Plastic headers 407 model size AFT natural gas cupro nickel For altitudes a...

Страница 18: ...ll have a minimum net free area as noted COMBUSTION AND VENTILATION AIR Indoor Units Only The heater must have both combustion and ventilation air Minimum requirements for net free air supply open ing...

Страница 19: ...ONS Gas piping must have a sediment trap ahead of the heater gas controls and a manual shut off valve locat ed outside the heater jacket All gas piping should be tested after installation in accordanc...

Страница 20: ...well VR8304 Heater Models 206 406 and 207 407 ELECTRONIC IGNITION GAS VALVES CONTINUED Gas Pressure Adjustment Robertshaw 7200 Heater Model 206 Robertshaw 7000 BDER Heater Models 266 336 Gas Pressure...

Страница 21: ...AFFLE Manufactured after 11 08 FLOW GPM PRESSURE DROP FT OF HEAD 206 207 266 267 336 337 406 407 20 4 0 25 4 0 4 6 30 4 0 5 2 35 4 0 5 8 5 2 40 4 6 5 8 5 2 5 2 50 4 6 6 3 6 9 6 9 60 4 6 6 9 6 9 6 9 70...

Страница 22: ...d scaling temper atures U G Plug Polymer Unitherm Governor Gasket POLYMER HEADERS STANDARD MODELS Before attaching the 2 inch unions to the inlet outlet header make sure the O rings are properly seate...

Страница 23: ...nd outlet pipes at the heater Outlet pipes should be slightly warmer than inlet and comfort able to the touch If pipe is hot close bypass if cold open bypass PRESSURE RELIEF VALVE INSTALLATION To conf...

Страница 24: ...at any water leaks will not damage the structure of adjacent area PVC pipe may be glued directly into header unions Standard models only CAUTION An additional source of heated water e g a solar system...

Страница 25: ...sheets Clean off tube sheet area where the gasket seats Also clean off the header and the gasket Apply a non petrole um based lubricant to the gasket such as AquaLube Re attach the headers to the oppo...

Страница 26: ...n the far left side of the heater 8 Re route all high voltage wires and ground wires through the left jacket side of heater 9 Re install P6 connector ground wires SPG transformer junction box front do...

Страница 27: ...RIC HEATER 120V LOW NOx HEATER SUPPLY SIDE SUPPLY SIDE RETURN or NEUTRAL RETURN or NEUTRAL HEATER 4 WIRES HEATER 7 WIRES GROUND L1 L1 HOT RED RED RED BLACK BLACK BLACK BLACK HOT BLACK GREEN GREEN GREE...

Страница 28: ...28 WIRING DIAGRAM MILLIVOLT MECHANICAL THERMOSTAT...

Страница 29: ...29 WIRING DIAGRAM ATMOSPHERIC...

Страница 30: ...30 WIRING DIAGRAM LO NOx...

Страница 31: ...eader HL1 High Limit HL2 High Limit Pressure Switch Temp Sensor Well Pilot Roll Out Switch Gas Valve Transformer Drain Plug Drain Plug Located in rear header Unitherm Governor Mounted On Top Of Header...

Страница 32: ...knob stop adjustment ring illustrated below is adjustable by loosening the set screw rotating the knob stop ring to the desired location and re tightening the set screw SPA TEMPERATURE RANGE POOL TEMP...

Страница 33: ...ry press the MODE and UP buttons simultaneously for 3 to 5 seconds The heater will continue to operate normal ly while in the Service Menu The first screen dis played is the Flame Strength indicator w...

Страница 34: ...displaying Celsius as well as Fahrenheit temperatures The UP or DOWN buttons will select Fahrenheit or Celsius on the temperature display Choose the desired temperature scale Spa Max Temp Spa Set Poi...

Страница 35: ...eplace board EEPROM Fault Memory fault reset set points replace board if fault does not clear Clock Fireman Sw Time clock fireman switch circuit is open Low Temp Lockout Water temperature below 36 F T...

Страница 36: ...e circuit created by the remote wiring Typically a remote does not supply power to the heater it only provides a switching function to turn the heater On or Off If your remote is supplying its own vol...

Страница 37: ...The actual setpoint will be con trolled by the remote control 4 Turn the mode button to OFF and remove power from the heater 5 On the Remote Interface Harness connect the BLUE wire to one side of the...

Страница 38: ...located below the level of the spa or pool it may be necessary to adjust the pressure switch to compen sate for the no flow static head If it is necessary to adjust the water pressure switch utilize...

Страница 39: ...e 5 Reverse above procedure to reinstall HIGH LIMIT REMOVAL 1 Shut off main electrical power switch to heater 2 Remove inlet outlet inspection panel 3 Remove defective high limit and replace with a ne...

Страница 40: ...er straight up using caution not to damage refractory 8 Reverse above procedure to reinstall Make sure the insulation strips are properly replaced on top of the refractory retainer TUBE CLEANING PROCE...

Страница 41: ...e made of the burners ELECTRICAL Be sure that electrical service to the heater has prop er overload fuse or circuit breaker protection wire size and connections which comply with all applicable codes...

Страница 42: ...Remove 2 screws that mount the pilot assembly to the burner tray 4 Pull the pilot assembly downwards and outwards 5 Reverse above procedure to reinstall COMBUSTION BLOWER REMOVAL 1 Remove the 2 screw...

Страница 43: ...ment replace Air starvation Refer to installation instructions Improper venting Follow recommended installation instructions Insects or debris clogging burner intake ports Clean burners Pilot outage o...

Страница 44: ...ilot burner does not light Light pilot If pilot burner goes out when main burner lights or when gas valve knob is released If burner does not remain lit attach millivolt meter and read pilot output If...

Страница 45: ...d pilot operator on gas control Check for 24 VAC across PV MV PV terminals on PC board If voltage is okay replace gas control if not replace PC board NOTE If PC board goes into lockout reset system Lo...

Страница 46: ...P1 Check resistance value of the thermister Reference to chart below Replace thermister if not within 10 of values shown below If okay replace Circuit Board Temp Degrees F 40 50 60 70 80 90 100 106 Re...

Страница 47: ...acement under standard company warranties must be properly tagged with a return parts tag completely filled in with the heater serial number model number etc and shipped to the Company freight prepaid...

Страница 48: ...V 14 M I S I3 S 2 S 5 HP 4 HP 7 HP 6 HP I2 S 6 HP I5 HM 3 HP 7 S 3 R 4 S 17 HM 11 S 4 C 9 M 8 S 13 M 12 M 3 S 4 B 2 B 5 M 5 B 1 B 1 G 1 J 4 S 5 S 6 S 14 M 1 R 2 R 2 J 7 HP 3 B 10 S 10 M 4 M 2 M 3 M 5...

Страница 49: ...V 9 M I S I3 S 2 S 5 HP 4 HP 7 HP 6 HP I2 S 6 HP I5 HM 3 HP 7 S 3 R 4 S 17 HM 11 S 4 C 6 M 8 S 8 M 7 M 3 S 3 B 4 B 1 G 10 S 1 B 2 B 2 M 3 J 10 M 6 B 5 B 7 C 1 J 4 S 5 S 6 S 9 M 1 R 2 R 2 J 13 M 4 V 12...

Страница 50: ...OPTIONAL POLYMER IN OUT HEADER AND ACCESSORIES 1 M 3 C 6 C 5 HM 17 HM 14 HM 13 HM 2 HM 4 HM 7 HM 3 HM 6 HM 2 S 9 S 4 S HONEYWELL IID ATMOSPHERIC PILOT 2 P 7 P 9 P 8 P 1 P 5 P 6 P 3 P 9 P HONEYWELL MIL...

Страница 51: ...4306F 004306F HP HEAT EXCHANGER POLYMER 1 HP Heat Exchange Assy Copper 010043F 010044F 010045F 010046F Heat Exchange Assy Cupro Nickel 010356F 010357F 010358F 010359F 2 HP Inlet Outlet Header Complete...

Страница 52: ...90F 9 M Control Bezel MV Includes Dial Decal 009489F 009489F 009489F 009489F 10 M Dial Decal MV 009858F 009858F 009858F 009858F 11 M Control Bezel Includes Switch Decal Units manufactured prior to 5 2...

Страница 53: ...505 009505 009505 009505 9 S High Limit Cover 010319F 010319F 010319F 010319F 10 S Base Heat Shield 010320F 010320F 010320F 010320F 11 S Up Front Control Panel Green 010321F 010322F 010323F 010324F Co...

Страница 54: ...12 HP Bypass Spring All Sizes Included 006718F 006718F 006718F 006718F 13 HP Unitherm Governor 006719F 006719F 006719F 006719F 14 HP Unitherm Governor Plug 006720F 006720F 006720F 006720F 15 HP Drain...

Страница 55: ...1926F 011926F 011926F 5 P Hi Tension Wire IID 010349F 010349F 010349F 010349F 6 P Adapter Nut Metric 011927F 011927F 011927F 011927F R REFRACTORY 1 R Refractory Common Left Right 010079F 010079F 01007...

Страница 56: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: