Properly maintained, this water heater will provide years 

of dependable, trouble free service. It is strongly sug-

gested that a regular routine maintenance program be 

established and followed by the owner. It is further rec-

ommended that a periodic inspection of the relief valve 

and venting system should be made by service techni-

cians qualified in gas appliance repair.

1.  ROUTINE PREVENTIVE MAINTENANCE

A. PRESSURE SWITCH

 — Inspect the inlet to the pressure 

switch and the tubing for debris or blockage. Clean out 

the tubing periodically to prevent buildup of debris.

B  COLLECTOR PAN

 —Remove any particles.

C. CONDENSATE TRAP

 — Check for blockages.

D. ELECTRICAL CONNECTIONS

  — Periodic inspection 

of all electrical connections and wiring conditions.

  Label all wires prior to disconnection when servicing controls.  

Wiring errors can cause improper and dangerous operation.

 

VERIFY PROPER OPERATION AFTER SERVICING !

  Make certain all power to the water heater is turned 

"OFF" before performing any maintenance or inspec-

tion work on this water heater.

 

  Before manually operating the relief valve, make certain 

no one will be exposed to the danger of coming in contact 

with the hot water released by this valve. The water may be 

hot enough to create a SCALD hazard. The water released 

should be directed to a suitable drain to prevent injury or 

damage.

 

NOTICE: If the temperature and pressure relief 

valve on the water heater discharges periodically, 

this may be due to thermal expansion in a “closed” 

water system. Contact the water supplier or local 

plumbing inspector on how to correct this. DO NOT 

plug the relief valve outlet.

E. TANK

— Good maintenance requires that the tank 

be cleaned of deposits. Unless the water supply is 

soft (0 to 5 grains hardness), scale or lime deposits 

will accumulate in the tank. Hard water scale is de-

posited at an increasingly high rate in proportion to 

increased water temperature. Accumulation of these 

deposits may reduce efficiency, and shorten the life 

of the water heater. Any new installation should have 

a tank inspection program set up initially for frequent 

inspection. The first inspection should be within a six 

month period. Once the scaling tendencies have been 

established, the inspection program can be modified 

to suit the water conditions. Cleaning should be per-

formed if the scale has accumulated above the drain 

valve opening.

  A wet-dry shop vac with a nozzle fashioned from 1” 

and/or 3/4” polyethylene pipe makes a good tool for 

scraping and removing scale.

TO CLEAN OR INSPECT TANK:

1. Shut off gas valve and drain tank.

2. Remove tank clean-out cover on jacket and with 

pocket knife cut and remove a circular plug of in-

sulation the full size of jacket opening.

3. Loosen bolts and remove plate and gasket.

4. Remove as much built-up scale from flue tubes 

and tank bottom as practical. 

DO NOT

 attempt to 

clean so thoroughly that the tool used damages 

the glass lining.

5. Clean the seal plate and install a new gasket. Wipe 

clean the interior surface of the tank that contacts 

the gasket. Reinstall the seal plate and tighten in 

position. Fill tank with water and check for leaks. 

If no leaks are found, install insulation plug and 

clean-out cover on jacket and re-light the water 

heater.

  If chemical lime dissolving cleaners are preferred, 

cautiously follow the instructions supplied with the 

cleaner. 

DO NOT 

use a muriatic or hydrochloric acid 

(HCl) base cleaner.

2.   ANODE INSPECTION

 — The water supply in certain 

areas contains very aggressive elements. In these 

areas, periodic inspection of the anode is recom-

mended to determine if replacement is necessary. 

The anode(s) supplied in this water heater is slowly 

consumed, thereby eliminating or minimizing corro-

sion and protecting the glass lined tank. The anode(s) 

should be replaced when more than 6 inches (15 cm) 

of core wire is exposed at either end.

3.  SEASONAL OPERATION

 - If the water heater is to 

remain idle for an extended period (60 days or more) 

the heater should be turned off. The water heater and 

piping should be drained if they might be subjected 

to freezing temperatures. It is recommended that the 

water heater's operation is thoroughly checked (by a 

qualified service technician) before it is placed back 

in service. 

NOTICE: Refer to the Hydrogen Gas caution notation 

on page 23

.

F.  VENTING SYSTEM

 — Inspect venting system at least 

yearly to make certain the passageways are free and 

unobstructed, and that the vent connector from the 
water heater’s blower assembly is properly positioned 
and securely attached. Remove any obstructions in 
vent connector or vent terminal. 

Maintenance

CAUTION

!

CAUTION

!

Содержание GHE 125-500A

Страница 1: ...rmed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage person...

Страница 2: ...zards that can kill or hurt you and others All safety messages will follow the safety alert sym bol and either the word DANGER WARNING CAUTION or NOTICE These words mean DANGER An imminently hazardous...

Страница 3: ...for altitudes greater than 2 000 up to 5 400 FT HA2 LP Gas Approved for altitudes greater than 5 400 up to 7 800 FT For LP Models see table 6 for approved altitude ranges FOR NATURAL GAS MINIMUM GAS S...

Страница 4: ...lations the temperature was set at 120 F before water heater was shipped from the factory The illustration infor mation on pages 25 shows the Display and how to adjust the water temperature Hotter wat...

Страница 5: ...ion Section Pages 23 26 prior to any installation work Gasoline as well as other flammable materials and liquids adhesives solvents etc and the vapors they produce are extremely dangerous DO NOT handl...

Страница 6: ...of the ser viceable components D RESTAURANT INSTALLATION If the water heater is to be installed in a restaurant or other lo cation where NSF International listing is required this unit must be sealed...

Страница 7: ...ure Pressure Temperature and Pressure Relief Valves and Vacuum Relief Valves is provid ed with the water heater No valve is to be placed between the relief valve and the water heater For a circulating...

Страница 8: ...nnecting the exhaust vent pipe the condensate elbow assembly supplied but not factory installed must be connected to the ex haust pipe on the water heater See Figure 2 The free end of the 3 x 3 x 1 5...

Страница 9: ...earances shown in Figure 4 NOTICE DO NOT use in conjunction with a GFCI To avoid the risk of fire explosion or asphyxiation from carbon monoxide NEVER operate this water heater unless it is properly v...

Страница 10: ...he Thermal Expansion Tank if required A manual valve union and a sediment trap shall be provided in front of the gas valve All gas piping must conform to local codes and or the National Fuel Gas Code...

Страница 11: ...tarting the vent installation careful planning should be given to the routing and termination of the vent pipes The length of the vent pipes inlet and outlet should be kept to a minimum Also see Figur...

Страница 12: ...ruc tions Manual for complete instructions on venting and condensate drainage Stress levels in the pipe and fittings can be signifi cantly increased by improper installation If rigid pipe clamps are u...

Страница 13: ...ent and Air Intake Pipe Lengths 6 Pipe Table 4 Minimum and Maximum Vent and Air Intake Pipe Lengths 4 Pipe 50 0 240 Fuel Type Fuel Type NAT or LP NAT or LP Vent4 ft 20 GHE119 500 GHE125 500A 50 50 120...

Страница 14: ...d However improper location or installation can result in severe damage to the structure or exterior finish of the building VERTICAL VENT INSTALLATION Once the vent terminal location has been determin...

Страница 15: ...lbow A screen that significantly restricts airflow will reduce the performance of the water heater and could cause nuisance control lockouts Com plete the installation of the remainder of the vent and...

Страница 16: ...equal to 12 30 5 cm and above expect ed snow level from the ground the instal lation must be modified as shown below See Figure 14 Vent Terminal Low ground clearance Terminate exhaust vent with 45 elb...

Страница 17: ...rdance with current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves bot...

Страница 18: ...s 2 In accordance with current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and...

Страница 19: ...nt pipe To prevent this from happening the pipe should be installed with a slight upward slope of 1 8 per foot The vent system must be supported every 5 feet of vertical run and every 3 feet of hori z...

Страница 20: ...20 Installation Schematic Diagram Figure 18...

Страница 21: ...ically grounded Elec trical power should be supplied through a fused disconnect switch located near the water heater Where local codes permit use the supplied power cord for field connection A groundi...

Страница 22: ...ater heater and piping air vented Water connections tight and free of leaks C Gas Supply Gas line equipped with shut off valve union and sediment trap drip leg Approved pipe joint compound used Soap a...

Страница 23: ...ith the application Hotter water increases the Potential for Hot Water SCALDS When this water heater is supplying general purpose hot water requirements for individuals a thermostatically con trolled...

Страница 24: ...as valve is opened and ignitor remains energized for 3 seconds Is flamed detected within 5 seconds Control is manually reset by pressing the i button Blower is de energized and control goes into locko...

Страница 25: ...25 Operation Steps to adjust the setpoint temperature Figure 21...

Страница 26: ...e knob will not turn by hand don t try to repair it call a qualified service technician Force or attempt to repair may result in a fire or explosion C Do not use this appliance if any part has been un...

Страница 27: ...established the inspection program can be modified to suit the water conditions Cleaning should be per formed if the scale has accumulated above the drain valve opening A wet dry shop vac with a nozzl...

Страница 28: ...should be less than 25 ppm In the combustion readings are outside of the specified ranges check the manifold pressure on the gas control at the outlet pressure tap See figure 21 for the location of t...

Страница 29: ...n the tank Drain the water heater to remove scale and sediment Insufficient hot water Heater undersized for load Reduce hot water usage rate Check display for error code See tables 8 and 9 Temperature...

Страница 30: ...t WZ hZ D K Khd K s Ed Table 8 shows a list of lockout error codes A lockout code will be visible on the control dis play in the form of a code letter A followed by a number and a short message Lockou...

Страница 31: ...E ZZKZ h E KZ KZd h D d Zd ZKhE ZZKZ t d Z d E KZ KW E t ZZKZ W ZZKZ Table 9 shows a list of blocking error codes A blocking code will be visible on the control dis play in the form of a code letter...

Страница 32: ...i t e h t f o t s o m s p m a o r c i m 7 e r u l i a f e m a l f A d e y a l p s i d o s l a s i s e r u l i a f e m a l f f o r e b m u n e h t f o l a t o t g n i n n u r A l a i r t e h t g n i r...

Страница 33: ...the measurement is taken after the cycle Besides resistance the continuity of the ignitor circuit can be checked With the multimeter probes still in the terminal switch the meter to check for continui...

Страница 34: ...Sensors 2 in 1 T P Relief Valve Condensate Elbow Assembly Trim Plate 2 pcs Flue Gas Temperature Sensor Blocked Exhaust Switch Inlet Pipe Nipple Power Supply Junction Box Insulation Tank Top Air Intake...

Страница 35: ...trol Panel Parts Stando 3 5 in length Transformer 120 VAC 24 VAC Relay Terminal Block Main Operating Control Control Display Display Bracket Description Description Fuse 5A delay Stando 2 5 in length...

Страница 36: ...ting ange insulation disk retaining plate and bolts Flange Assembly Gasket blower to transition tube Blower Gas Control Gasket burner to mounting ange Burner Gas Pressure Switch Gas Control Flange w g...

Страница 37: ...37 Notes...

Страница 38: ...38 Notes...

Страница 39: ...39 Notes...

Страница 40: ...ng information should be made available a Model and serial numbers of the water heater as shown on the rating plate attached to the jacket of the heater b Address where water heater is located and can...

Отзывы: