38
WARNING
!
FIGURE 24
COOLING TROUBLESHOOTING CHART
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAIL-
URE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• Power off or loose electrical connection
• Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high
• Reset
• Failed contactor
• Check for 24 volts at contactor coil - replace if contacts are
open
• Blown fuses
• Replace fuses
• Transformer defective
• Check wiring-replace transformer
• High pressure control open (if provided)
• Reset-also see high head pressure remedy-The high pressure
control opens at 610 PSIG
• Interconnecting low voltage wiring damaged
• Replace thermostat wiring
Condenser fan runs, compressor
• Loose connection
• Check for correct voltage at compressor -
doesn’t
check & tighten all connections
• Compressor stuck, grounded or open motor winding
• Wait at least 2 hours for overload to reset.
open internal overload.
If still open, replace the compressor.
• Low voltage condition
• At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
• Low voltage condition
• Increase voltage
Insufficient cooling
• Improperly sized unit
• Recalculate load
• Improper airflow
• Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge
• Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system
• Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage
• At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles
• Incorrect voltage
• At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector
• Replace - check for correct voltage
• Refrigerant undercharge
• Add refrigerant
Registers sweat
• Low evaporator airflow
• Increase speed of blower or reduce restriction - replace air
filter
High head pressure-
• Restriction in liquid line, expansion device or filter drier
• Remove or replace defective component
low vapor pressures
• TXV does not open
• Replace TXV
High head pressure-high or
• Dirty condenser coil
• Clean coil
normal vapor pressure -
• Refrigerant overcharge
• Correct system charge
Cooling mode
• Condenser fan not running
• Repair or replace
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
Low head pressure-high vapor
• Defective Compressor valves
• Replace compressor
pressures
Low vapor pressure -
• Low evaporator airflow
• Increase speed of blower or reduce restriction - replace air
cool compressor -
filter
iced evaporator coil
• Operating below 65°F outdoors
• Add Low Ambient Kit
• Moisture in system
• Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure
• Excessive load
• Recheck load calculation
• Defective compressor
• Replace
Fluctuating head & vapor
• TXV hunting
• Check TXV bulb clamp - check air distribution on coil - replace
pressures
TXV
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
Gurgle or pulsing noise at
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
expansion device or liquid line
X. TROUBLESHOOTING
Содержание B180CL25E
Страница 48: ...48 FIGURE 33 RKNL B SERIES B 241 MODELS 00 90 42517 56 10 5 18 PCB PRESSURE CONTROL BOARD RKNL B241 ...
Страница 50: ...50 FIGURE 35 RKNL C SERIES 208V 208V 208V 208V 04 ...
Страница 54: ...54 FIGURE 39 RKNL H SERIES 208V 208V 208V 208V 01 ADDED RED 208V LEAD TO IDM S VYM Y 0655S251 04 04 18 01 ...
Страница 60: ...60 97B0055N24 97B0055N24 CM 0418 ...